ABU DHABI NATIONAL OIL COMPANY (ADNOC) GHASHA CONCESSION PROJECTS HAIL & GHASHA DEVELOPMENT PROJECT PACKAGE 2 - ONSHORE FACILITIES
AGREEMENT NO. 4700021829 CONTRACTOR DOC NO: 4422-SS-FP-
**EMERGENCY SAFETY SHOWER AND EYE WASH DATASHEETS Document class:2B**
**COMPANY DOC NO: 2-MM5173-40-SPE-1907-00 Rev.**
# ABU DHABI NATIONAL OIL COMPANY (ADNOC)
# GHASHA CONCESSION PROJECTS
# HAIL AND GHASHA DEVELOPMENT PROJECT
# PACKAGE 2 - ONSHORE FACILITIES
# EMERGENCY SAFETY SHOWER AND EYE WASH
# DATASHEETS
01 27-JAN-2025 Issued^ for^ Purchase A.Jadhao A. Carnelli F. Di Vito 00 4-SEP-2024 Issued^ for^ Purchase P.Payer A. Carnelli F. Di Vito B1 15-May-2024 Issued^ for^ Approval A.Jadhao A. Carnelli F. Di Vito A1 17-Apr-2024 Issued for Review A.Jadhao K. Arolkar F. Di Vito
**Rev (DD/MMM/YYYY)Date Reason for Issue
PREPARED**
N. Surname
CHECKED N. Surname
APPROVED N. Surname This Document is intended for use by ADNOC and its nominated Consultants, Contractors, Manufacturers and Suppliers.
2 of 5
COMPANY DOC NO: 2-MM5173-40-SPE-1907-00 CONTRACTOR DOC NO: 4422-SS-FP-
REV
REVISION
01 EMERGENCY SAFETY SHOWER AND EYE WASH DATASHEETS Sheet 1 EQUIPMENT: SAFETY SHOWER AND EYE WASH MODEL: * 2 TYPE : SHOWER+UNIT SELF^ EYECONTAINED^ WASH^ STATION^ +^ OVERHEAD^ TANK^ WITH^ CHILLER 3 LOCATION : OUTDOORS CERTIFICATION : ANSI Z358. 4 QUANTITY : PROCESS UNIT:(NON-HYDROGEN) 16 24 (NOTE-7) 5 PROCESS UNIT:(HYDROGEN) 9 1 (NOTE-7) 6 UTILITY UNIT (OUTSIDE 0.5 LFL CONTOUR): 12 15 (NOTE-7) 7 8 OPERATING CONDITIONS 9 AMBIENT TEMPERATURE MIN. 3 °C Max. 58°C MAXIMUMTEMPERATURE^ METAL (SOLAR):^ BODY 85 °C
10 HUMIDITY Min. 50% MAX.97% at 43°C
11 ATMOSPHERE MARINE, SALIFEROUS, DUST & SAND
12 WATER TEMPERATURE OPERATING - AMBIENT BETWEEN 15.6 to 37.8 C
13 OPERATINGSHOWER^ PRESSURE^ OF^ SAFETY 2 to 6 BARG DESIGNINCOMING^ PRESSURE POTABLE^ OF WATER 14 BARG
14 FLOWRATE : FOR SAFETY SHOWER : 76 LPM FOR EYE WASH : 11.4 LPM
15 FLUID HANDELLED POTABLE WATER TYPE SELF CONTAINED
16
17 **DESCRIPTION – ACCESSORIES**
18
19 ACTUATOR PULL ROD OPERATED FOR OVERHEAD SHOWER AND PUSH FLAG FOR EYE WASH (NOTE-15)(NOTE-8)
20 MINIMUM DISCHARGE TIME 15 MINUTES
21 SHOWER SHOWERSHOWER^ HEADSHOULD^ ATTACHMENTS BE INSIDE INSULATED^ SHALL^ BE CABINATE60°^ AND^ 120° (NOTE-11)^ SPRAY^ ANGLE
22 EYEWASH EYE WASH FITTED WITH SCREEN FILTER OR STRAINER (NOTE-2)
23 OVERHEAD TANK THEINSULATION.^ TANK^ MATERIAL (NOTE-14)^ SHALL^ BE^ MADE^ OF^ MEDIUM^ DENSITY^ POLYETHYLENE^ WITH^ GRP^ JACKET^ AND^ POLYURETHANE
24 PIPING * BRASS OR STAINLESS STEEL
25 WEIGHT *
26 WATER TANK CAPACITY * 1500 LITER (MINIMUM FOR 15 MINUTES)
27 CHILLER UNIT (HAZARDOUS)) SUITABLE FOR MAINTAINING THE WATER TEMPERATURE TO 16-38°C AT THE SAFETY SHOWERS AND EYE-WASHES,EX PROOF
28 CHILLER UNIT (NON-HAZARDOUS) SUITABLE FOR MAINTAINING THE WATER TEMPERATURE TO 16-38°C AT THE SAFETY SHOWERS AND EYE-WASHES.
29 SELF DRAINING YES
30 BACTERIOSTATIC ADDITIVE * YES
31 LIMIT SWITCH YES (ONE FOR SHOWER AND ONE FOR EYE WASH) SEE TYPICAL ARRANGEMENT ON PAGE NO. 4
32 FLOAT VALVE BALL FLOAT VALVE ON INLET WATER FILLING LINE
33 FRAME MATERIAL * (NOTE-5) (NOTE-11)
34 LEVEL HIGH ALARM REQUIRED (NOTE -8)
35 LOCAL TANK LEVEL INDICATOR VISUAL LEVEL INDICATOR WITH FLOAT
36 LOW LEVEL SWITCH REQUIRED (NOTE-16)
37 SAFETY SIGN SAFETY SIGNS AND OPERATING INSTRUCTIONS SHALL BE PROVIDED ARABIC AND ENGLISH
38 PAINTING FINISH IN GREEN, RAL
39 **CONNECTIONS**
40 LOCAL WATER LEVEL INDICATOR REQUIRED
41 OVERFLOW NOZZLE REQUIRED
42 SUPPLY LINE SIZE 2” FLANGE TIE-IN
43 DRAINAGE LINE SIZE *
44 ELECTRICAL FITTINGS FOR ALL ELECTRICAL/INSTRUMENTATION (NOTE -7)
45 POWER REQUIREMENTS * 4.00 kW 415 V 3PH
46
47
48
49
50
51
52
3 of 5
##### COMPANY DOC NO: 2-MM5173-40-SPE-1907-
##### CONTRACTOR DOC NO:
##### 4422-SS-FP-
##### REV
##### REVISION
##### 01
##### EMERGENCY SAFETY SHOWER AND EYE WASH DATASHEETS
Sheet 1 NOTES 2 1 * VENDOR TO PROVIDE / CONFIRM INFORMATION MARKED. 3 2 DUST COVERS FOR EYEWASH SHALL BE PROVIDED AND AUTOMATICALLY RELEASE WITH WATER PRESSURE. 4 3 OPERATING INSTRUCTION (IN PICTOGRAM) SHALL BE PROVIDED IN ARABIC AND ENGLISH. 5 4 MATERIAL USED SHALL BE SUITABLE FOR MARINE, HUMID, SALINE ATMOSPHERE WITH AIR-BORNE DUST AND SAND (OUTDOOR).
6 5 SELF-SUPPORTEDFRAME FOR SELF SUPPORTINGFREE^ STANDING UNIT^ COMBINATION SHALL BE PAINTED.^ SAFETY^ SHOWER^ AND^ EYE^ BATH^ SHALL^ BE^ CAPABLE^ OF^ OPERATING^ THE^ UNITS^ SIMULTANEOUSLY.
7 6 OVERHEADWATER BY SOLAR^ WATER RADIATION.^ TANK^ SHALL^ BE^ PROVIDED^ WITH^ SUNSHADE,^ INSULATION^ AND^ CHILLER^ UNIT^ OR^ ALTERNATIVE^ OPTION^ TO^ PREVENT^ OVER^ HEATING^ OF
##### 8 7
##### VENDOR SHALL COMPLY WITH MINIMUM REQUIREMENT OF HAZARDOUS AREA CLASSIFICATION INCLUDED IN HSE PHILOSOPHY ( 4422-SZ-SG-
##### 2-CN0000-40-PHL-0002-00) SECT ION 10 AND AGES-SP-03-005 "SPECIFICATION FOR HAZARDOUS AREA CLASSIFICATION (SUPPLEMENT TO EI 15)".
##### AREA CLASSIFICATION SHALL FOLLOW THE REQUIREMENTS OF THE PROJECT:
a. ALL FIELD INSTRUMENTS SHALL BE SUITABLE FOR INSTALLATION AND CONTINUOUS OPERATION WITHIN A ZONE 1, GAS GROUP IIB AND IGNITION TEMPERATURE CLASS T3 HAZARDOUS AREA AS PER IEC 60079 AS A MINIMUM. b. ALL FIELD INSTRUMENTS LOCATED WITHIN H2 HANDLING UNIT SHALL BE SUITABLE FOR INSTALLATION AND CONTINUOUS OPERATION WITHIN A ZONE 1,GAS GROUP IIC AND IGNITION TEMPERATURE CLASS T3 HAZARDOUS AREA AS PER IEC 60079 AS A MINIMUM. c. FOR PROCESS AREA AND INSIDE LFL COUNTOUR, ELECTRICAL ITEMS SHALL BE SUITABLE FOR ZONE 2, GAS GROUP IIB T3 IF THEY COULD BE DE-ENERGIZED DURING EMERGENCY, OTHERWISE ZONE 1, GAS GROUP IIB T3 SHALL BE CONSIDERED d. FOR UTILITY OUTSIDE 0.5 LFL CONTOUR, ELECTRICAL ITEMS SHALL BE SUITABLE FOR SAFE AREA e. FOR UTILITY INSIDE 0.5 LFL CONTOUR, ELECTRICAL ITEMS SHALL BE SUITABLE FOR SAFE AREA IF THEY COULD BE DE-ENERGIZED DURING EMERGENCY, OTHERWISE ZONE 1, GAS GROUP IIB T3 SHALL BE CONSIDERED
##### 01
##### 9 8
##### INDICATION SHALL BE GENERATED IN CONTROL ROOM UPON THE ACTIVATION OF SAFETY SHOWER AND EYEWASH STATION. LIMIT SWITCH SHALL BE
##### PROVIDED BY VENDOR PART OF SAFETY SHOWER FOR REMOTE INDICATION. ALL ELECTRICAL CONNECTION TERMINATE AT JUNCTION BOX BY
##### VENDOR.PROVIDE LOCAL AUDIBLE AND VISUAL ALARM.
##### 10 9 SAFETY SHOWER AND EYEWASH REQUIREMENTS SPECIFIED IN ADNOC STANDARD AGES-SP-03-001 TO BE COMPLIED.
##### 11 10 VENDOR TO SPECIFY ELECTRICAL CONSUMPTION AND TYPE OF ELECTRIC FEED.
##### 12 11 THEENCLOSED^ SAFETY WITHIN^ SHOWER A CABINET.^ IS^ PLACED^ ON^ THE^ AREA^ WHICH^ IS^ EXPOSED^ TO^ DIRECT^ SUNLIGHT.^ HENCE^ SAFETY^ SHOWER^ SHOULD^ BE^ INSULATED^ AND
##### 13 12 FOR OUTDOOR EQUIPMENT IP RATING FOR ONSHORE SHALL BE IP 55
##### 14 13 QUANTITY IS PRELIMINARY
##### 15 14 TANK REFILLING IS AUTOMATIC. INLET VALVE SHALL BE OPEN ONCE LEVEL SWITCH DETECT LOW LEVEL IN THE TANK
##### 16 15 THE VALVES ONCE OPERATED, SHALL REMAIN OPEN UNTILTHEY ARE SHUT-OFF MANUALLY
##### 17 16 LOW LEVEL SWITCH SHALL GUARANTEE THE AUTOMATIC REFILLING OF THE TANK IN CASE OF LOW LEVEL
##### 18 17 CHEMICAL USED IN WATER TANK TO MAINTAIN WATER QUALITY SHALL BE SAFE TO USE FOR EYEWASH & SAFETY SHOWER 01
##### 19
##### 20
##### 21
##### 22
##### 23
##### 24
##### 25
##### 26
##### 27
##### 28
##### 29
##### 30
##### 31
##### 32
##### 33
##### 34
##### 35
##### 36
##### 37
## COMPANY DOC NO: 2-MM5173-40-SPE-1907-00 CONTRACTOR DOC NO:
##### REV
**EMERGENCY SAFETY SHOWER AND EYE WASH DATASHEETS** Sheet
1 **TYPICAL ARRANGEMENT**
- 4 of
- 4422-SS-FP-
- REVISION
- 2 EQUIPMENT SAFETY SHOWER AND EYE WASH
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
5 of 5
##### COMPANY DOC NO: 2-MM5173-40-SPE-1907-00 CONTRACTOR DOC NO:
#### 4422-SS-FP-
##### REV
##### REVISION
##### 01
EMERGENCY SAFETY SHOWER AND EYE WASH DATASHEETS Sheet
1 EQUIPMENT: PORTABLE EYE WASH MODEL: *
2 TYPE : SELFWATER^ CONTAINED DISPOSAL^ PORTABLECART^ EYEWASH^ PROVIDED^ WITH 3 LOCATION : INDOOR (BATTERY ROOM) CERTIFICATION : ANSI Z358. 4 QUANTITY : 26 25 (NOTE-2) 4 OPERATING CONDITIONS 5 6 AMBIENT TEMPERATURE MIN. 3 °C Max. 54°C MAXIMUMTEMPERATURE^ METAL (SOLAR):^ BODY 85 °C 9 ATMOSPHERE MARINE, SALIFEROUS, DUST & SAND
10 WATER TEMPERATURE *15.6^ OPERATING to 37.8 C^ -^ AMBIENT^ BETWEEN
11 OPERATING PRESSURE * 2 to 6 BARG
12 FLOWRATE : 11.4 LPM
13 FLUID HANDELLED POTABLE WATER
14
15 **DESCRIPTION – ACCESSORIES**
16
17 ACTUATOR PULL DOWN MANIFOLD FOR OPERATION (NOTE-5)
18 MINIMUM DISCHARGE TIME 15 MINUTES
19 EYEWASH * EYE WASH FITTED WITH SCREEN FILTER OR STRAINER
20 MATERIAL * HIGH DENSITY POLYETHYLENE
21 WEIGHT *
22 BACTERIOSTATIC ADDITIVE * WATER TREATMENT ADDITIVE TO PREVENT GROWTH OF HARMFUL ORGANISM IN EYEWASH WATER
23 INSTALLATION WALL MOUNTING BRACKETS/HOOKS FOR INSTALLATION EYEWASH UNIT
24 SAFETY SIGN SAFETY SIGNS AND OPERATING INSTRUCTIONS SHALL BE PROVIDED ARABIC AND ENGLISH
25
26 **NOTES**
27
28 1 * VENDOR TO PROVIDE / CONFIRM INFORMATION MARKED.
29 2 QUANTITY IS PRELIMINARY
30 3 VENDORSECTION^ SHALL 10 AND^ COMPLY AGES-SP-03-005^ WITH^ MINIMUM "SPECIFICATION^ REQUIREMENT FOR HAZARDOUS^ OF^ HAZARDOUS AREA^ AREA CLASSIFICATION^ CLASSIFICATION (SUPPLEMENT^ INCLUDED TOIN^ HSE EI 15)".^ PHILOSOPHY^ (4422-SZ-SG-000000000002)
31 4 MATERIAL USED SHALL BE SUITABLE FOR MARINE, HUMID, SALINE ATMOSPHERE WITH AIR-BORNE DUST AND SAND (OUTDOOR).
32 5 FLUID DISPOSAL CART SHALL BE PROVIDED TO COLLECT THE DRAINED FLUID.
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48