Section Requirement Compliance Criteria

General Safety

Presence of emergency showers and
eyewash stations in hazardous areas
Install in areas with chemical/Hâ‚‚S
exposure; align with ANSI Z358.

Location

Accessible within 10 seconds; same level as
hazard
No doors or obstructions; max 15m
distance from hazard source

Red/Amber Zones

Avoid placing safety showers inside red zones
if possible
Locate outside red zones with direct
access from safe zones

Water Supply

Tepid water with adequate pressure and
duration
Flow for 15 mins at 75.7 L/min
(shower) and 1.5 L/min (eye wash)

Activation Hands-free activation within 1 second

No twisting/pinching; self-activating
valve mechanism

Visibility Highly visible with proper signage

Use reflective green/yellow signage
per ANSI; visible in low light

Testing & Maintenance

Weekly activation and annual performance
test
Documented tests; check flow, temp,
pressure, and drain function

Drainage Prevent standing water and flooding

Drainage to safe location; avoids
pooling or ice buildup

Enclosure (Outdoor) Thermal protection for outdoor units

Use heated/insulated enclosures in
extreme temps (<16°C or >38°C)

Integration Optional alarm to ICSS/local alert system

Send alarm to CCR/operator on
activation in high-risk zones

Materials Corrosion-resistant construction

Use SS316 or similar for harsh
marine/desert conditions