EQUIPMENT TAG
007100SH001A/B/C/D/E/F/G/H/I/J
(HOLD : 2)
SERVICE
NOMINAL CAPACITY DESIGN PRESSURE INSULATION
SAFETY SHOWER & EYE WASH
1.1 2.1
m³ Bar(g) YES/No
FROM PORTABLE
313400DPFM12198
WATER PUMP
85 -29 AMB 3
12
0
PTJ
SLB
DW8301-2”-46A
2”
2”
DW8301-2”-46A
LO 7100RB001
7100RC001
LAH
0001
HOLD : 2
LAL
0001
IZ 0001
IZ 0002
LSH
0001
LSL
0002
3/4” SBB
3/4” SBB
COMMON FAULT ALARM
UA
0001
IZ 0003
TAL
0001
TAH
0001
IZ 0004
IZ 0005
TSL
0001
TSH
0001
” 4 / 3
B B S
” 4 / 3
B B S
ATM
” 1
A 6 4
” 1
3 0 3 8 W D
2 0 0 B R 0 0 1 7
POTABLE WATER TANK STORAGE
A 6 4
” 1
2 0 3 8 W D
” 1
C L
3 0 0 B R 0 0 1 7
TO GRADE
1”
LO 7100RB004
HOLD : 1
SAFETY SHOWER
PULL ROD
A 6 4
” 1
3 0 3 8 W D
EYE WASH
HOLD : 1
STR
0001
DW8303-1”-46A
85 -29 37.8 2.1
12
0
SP
7100FT001
Y-TYPE STRAINER
EYE WASHER/ SAFETY SHOWER
REFERENCE DRAWINGS
SL.NO
DWG / DOC. NO
DWG / DOC. DESCRIPTION
CLIENT REV
01
02
03
04
05
20198.VAR.LCI.STD
ITEM NUMBERING
313400DPFM12064 TO 12085
P&ID LEGENDS SHEET
313400DPPT12026
313400DPEA12224
313400DPEQ12219
P&ID PREPARATION PROCEDURE
EQUIPMENT LIST
CAUSE AND EFFECT DIAGRAM
09
01
00
00
00
GENERAL NOTES:
ALL INSTRUMENT TAG AND LINE NUMBERS SHALL BE PREFIX BY SUB FACILITY CODE (00) FOLLOWED BY FUNCTIONAL FACILITY CODE (710) AND TRAIN NUMBER (0) UNLESS OTHERWISE SPECIFIED. (LINE NO EXAMPLE. 007100RG0016-18”-43A-V), (INSTRUMENT NO EXAMPLE. 007100PT1901). ALL VALVE AND SPECIALITY ITEM TAG NUMBERS SHALL BE PREFIX BY SUB FACILITY CODE (00) UNLESS OTHERWISE SPECIFIED (VALVE TAG NO. EXAMPLE 007100RG001, SPECIALITY ITEM TAG NO. EXAMPLE. 007100LZ003). PIPING SHALL BE PROVIDED WITH HIGH POINT VENT AND LOW POINT DRAINS, THESE ARE NOT SHOWN IN P&IDS. UNLESS OTHERWISE SPECIFIED SLB WILL SUPPLY EQUIPMENT, MANUAL VALVES, SPECIALITY ITEMS AND INSTRUMENTS. HOWEVER, PTJ WILL BE RESPONSIBLE FOR THE INTERCONNECTING PIPING AS PART OF THEIR SCOPE OF SUPPLY. SEE DRAWING NUMBER “313400DPDD12283” FOR EYE WASHER / SAFETY SHOWER LOCATIONS. REFER EYE WASHER / SAFETY SHOWER PROJECT SPECIFICATION DOCUMENT 313400DPSG12306.
NOTES:
SHOWER SHALL BE A FREE-STANDING FREEZE PROOF EMERGENCY SHOWER/EYEWASH COMBINATION. SHOWER SHALL BE ACTIVATED BY STAINLESS-STEEL PULL ROD THAT OPERATES A 1-INCH STAY-OPEN BALL A PUSH FLAG THAT OPERATES A 1/2”-INCH STAY-OPEN BALL VALVE SHALL ACTIVATE EYEWASH. SHOWER SHALL BE BRADLEY S19-310AC, SPEAKMAN SE-612, OR EQUAL THE SAFETY SHOWERHEAD SHALL BE PLACED BETWEEN 2.0 MTR AND 2.4MTR ABOVE THE FLOOR WHERE USER STANDS. THE EYEWASH OUTLET HEADS SHALL BE POSITIONED BETWEEN 0.8 MTR AND 1.1 MTR FROM THE FLOOR WHERE USER STANDS. THE CENTRE OF EYEWASH OUTLETS SHALL BE AT LEAST 0.15 MTR FROM THE WALL OR NEAREST OBSTRUCTION. EASILY ACCESSIBLE SAFETY SHOWER ACTUATOR SHALL BE PLACED NO HIGHER THAN 1.7 MTR ABOVE THE FLOOR WHERE USER STANDS. CLEAR SIGN SHALL BE INSTALL : EMERGENCY SHOWER AND EYEWASH. TERMINATE THE EYEWASH DRAIN 4-INCHES ABOVE FINISHED FLOOR. THE SAFETY SHOWER AND EYEWASH UNITS SHALL BE CONNECTED TO POTABLE WATER SUPPLY ONLY. DO NOT CONNECT OR INSTALL PROVISION FOR CONNECTION OF SAFETY SHOWERS TO PLANT WATER, FIRE WATER OR ANY OTHER SOURCE OF WATER. THE WATER SUPPLIED TO SAFETY SHOWER AND EYEWASH UNITS SHALL BE LUKEWARM. A RECOMMENDED TEMPERATURE RANGE FOR LUKEWARM WATER IS 15.6 °C TO 37.8 °C. THE WATER TEMPERATURE SHALL NOT EXCEED 38 °C IN ANY CIRCUMSTANCES. THE SAFETY SHOWER AND EYEWASH UNITS SHALL BE OF THE TYPE THAT REMAINS OPEN AND REQUIRES A MANUAL TURN-OFF. THE SAFETY SHOWERS AND EYE WASH UNITS SHALL BE EQUIPPED WITH A 12 MM BIB TAP ATTACHED JUST BEFORE THE EYEWASH NOZZLES. NO PROVISION SHALL BE MADE FOR ATTACHING ANY HOSE TO IT. A MANUAL ISOLATING VALVE SHALL BE INSTALLED IN THE SUPPLY LINE TO EACH SAFETY SHOWER STATION. THE VALVE MUST BE IN AN ACCESSIBLE LOCATION AND AS CLOSE TO THE STATION AS POSSIBLE TO PERMIT EASY MAINTENANCE OF THE EQUIPMENT. A STRAINER SHALL BE INSTALLED DOWNSTREAM OF THE ISOLATING VALVE TO REMOVE PARTICLES FROM THE WATER AND PREVENT POSSIBLE ADDITIONAL EYE DAMAGE.
-
WHERE THE POSSIBLITY OF FREEZING CONDITIONS EXIST, PROTECT EQUIPMENT FROM FREEZING OR INSTALL
FREEZE PROTECTED EQUIPMENT. LOCATE EMERGENCY EQUIPMENT IN ACCESSIBLE LOCATIONS THAT REQUIRED NO MORE THAN 10 SECONDS TO REACH AND WITHIN 100 FEET OF THE HAZARD. WHEN THE HAZARD IS HIGHLY CORROSIVE, SUCH AS A STRONG ACID OR CAUSTIC, THE EQUIPMENT SHOULD BE WITHIN 3 MTR. OF THE HAZARD. THE ROUTE TO GET TO EMERGENCY UNITS MUST HAVE NO CHANGE IN ELEVATION (I.E. STEPS OR UNEVEN GROUND). PASSAGE THROUGH NO MORE THAN ONE DOORWAY, AND NO PATHWAY OBJECTS.
- WHERE THE POSSIBLITY OF FREEZING CONDITIONS EXIST, PROTECT EQUIPMENT FROM FREEZING OR INSTALL
FREEZE PROTECTED EQUIPMENT.
HOLD:
EYE WASHER / SAFETY SHOWER AS PER VENDOR OFFER. EYE WASHER / SAFETY SHOWER EQUIPMENT TAG.
EX-DE Validity Status
Client Rev. No.
A SLB Rev. No.
Vendor Rev. No.
Revision Index
02/10/2023
ISSUED FOR IDC
Damu/Nidya S Satish K/Deepa R David/Shyam S
John K
Date
Description
Prepared by
Checked by
Approved by
Contractor Approved
Company Approved
PETROJET (PTJ) /SLB
Worley
LCI Activity Code LCI-EG-2023-0004
Project Code 000532
Company Document ID:
313400DPFM12217
Job N.:
Contractor Document ID:
PF0009-SLB-HS-PID-0008
Job N.:
Vendor Document ID:
NA
Purchase Order N.:
Facility and Sub Facility description
3134 & 00 - General
Project and SoW description Melehia Phase II- New Gas Treament Plant (EPF)
Scale
NTS
Sheet of Sheets
001/001
Document Title
PIPING AND INSTRUMENTATION DIAGRAM SAFETY SHOWERS AND EYE WASH
Superseeded N.
Superseeded by N.
Plant Area NA
Functional Unit 710
This document is property of Agiba Petroleum Company. It shall neither be shown to Third Parties nor used for purposes other than those for which it has been sent.
Software: Autocad
File Name: 313400DPFM12217_EXDE00_01.DWG
Project: Q-31757 - Sanco - Meleiha Folder: RFQ Files