10.0 SAFETY EQUIPMENT (SE)

11.0 COMBINED SAFETY SHOWER AND EYEWASH UNIT

11.1 General

Accidental chemical exposures can still occur even if suitable PPE are worn; emergency shower and

eyewash are a necessary backup to minimize the effects of accident exposure to chemicals. Emergency

showers can also be used effectively in extinguishing clothing fires or for flushing contaminants off clothing.

In general, the technical requirements of combined safety shower and eyewash are as follows:

  1. Emergency shower and eyewashes shall be manufactured in accordance with ANSI Z358.1[25];

  2. Safety stations will be constituted by an eyewash and emergency shower combination;

  3. Safety shower and eyewash shall be provided with a flow rate of at least 75.7 Liter/min (20 gpm)

and 1.5 Liter/min (0.4 gpm) respectively for a minimum of 15 minutes using tepid water in a

suitable temperature range of 16-38°C.

  1. Water shall be always held at the adequate temperature (16-38°C); Water supply tank and piping

design (i.e. pipe wall thickness, insulation, tracing etc.) shall be sufficient to provide water within

this temperature range.

  1. The proposed tank shall be adequately insulated on all sides with minimum 40 mm thick

polyurethane material with aluminium foil cover and additional white GRP sun shields protection

against solar radiation to minimize the effects of temperature gain.

  1. Material of construction of safety shower and eye wash unit shall be:

Tank Heavy density polyethylene HDPE /MDPE / Stainless Steel.

40 mm thick polyurethane material insulation with aluminium cover

Additional white GRP sun shield(for tank) protection against solar radiation

Shower components, piping, valves, frames and all other metallic components in

stainless steels (SS316 /SS316L).

GRP Panelling on 3 sides.

All exposed water piping components shall be thermally insulated.

  1. The walking distance from the location of hazard to the safety shower/eyewash should not

exceed 10 seconds.

  1. Emergency showers and stations shall be identified with a highly visible sign and suitably lighted;

  2. The unit shall have signboards for identification with operational instruction with English and local

language.

  1. All fixation points shall be provided for mounting to concrete plinth and/or foundation.

This document is property of Agiba Petroleum Company It shall neither be shown to Third Parties nor used for purposes other than those for which it has been sent.

Company Document ID

Contractor Document ID

Vendor Document ID

313400DPSH12244

PF0009-SLB-HS-SPC- 0001

NA

Validity Status

Revision Number

EX-DE

00

Sheet of Sheets 21 / 33

  1. Emergency showers and stations shall be capable to operate for suitable flushing period;

  2. Emergency shower and eyewash of the safety stations shall be able to be used simultaneously

by the same individual;

  1. Emergency shower and eyewash shall not come into contact with any electrical equipment that

may become a hazard when wet.

11.2 Location

Combined Safety showers and eyewash shall be:

  1. Provided in all areas where operators may manage or be accidentally exposed to chemicals;

  2. Located as close to the hazard as possible;

  3. Located on an unobstructed path between the workstation and the hazard (i.e. workers should

not have to pass through doorways or weave through machinery or other obstacles to reach

them);

  1. Located where workers can easily see them;

  2. Located in an area where further contamination will not occur;

12.0 EYEWASH UNIT

Self-contained eye wash unit shall be installed in Battery room, with main requirements as follows.

  1. A self contained eye wash unit shall have container capacity of 34 litres. The eye wash unit shall

be capable of providing potable water to eyes at not less than 1.6 LPM for 15 minutes.

  1. The eyewash unit shall be fixed in a place and capable of being removed by designated

personnel for inspection and maintenance.

  1. The eyewash unit shall be on the same floor as the hazard (no stairs to travel between the

workstation and the emergency equipment);

  1. The eyewash unit shall be located near an emergency exit where possible so that any responding

emergency response personnel can reach the victim easily.

13.0 WINDSOCK

Windsock is a wind direction indicator to be provided in the facility as well as in the flare area. It gives an

indication of the direction of the cloud dispersion, supporting personnel moving away during an emergency

event (e.g. toxic and flammable clouds dispersion). Windsocks shall be located in such a way they are highly

visible from all areas.