Infinity

Not logged in
Home

❯

Reference Examples

❯

Less Complex

❯

Q 32332 Tyco ADNOC Train 9

❯

SAMPLE GA Drawing

A

B

C

D

E

F

1

2

3

4

5

A

B

GRP INSULATED TANK LID

PROJECTION

1 1 0 4

OVERFLOW CONNECTION

SECTION A-A 1720

658

SUN CANOPY

AUDIBLE ALARM (FLP)

VISUAL LEVEL INDICATOR

TEMPERATURE GAUGE

1 INCH BSP OVERFLOW

FLOW TRANSMITTER

JUNCTION BOX FOR REMOTE ALARM

254

1-1/2 INCH BSP 316L SS B16.5 150LB RAISED FACE FLANGE AT WATER INLET

PROXIMITY SWITCH FOR EYEWASH - REMOTE ALARM (FLP)

JUNCTION BOX FOR LOCAL ALARM

T E L N

I

R E T A W O

T

8 7 1 2

EYE/FACEWASH C/W LOW PRESSURE DIFFUSER NOZZLES

PROXIMITY SWITCH FOR EYEWASH - LOCAL ALARM (FLP)

C

WATER INLET CONNECTION

EYEBATH CONNECTION

SHOWER VALVE CONNECTION

2 INCH BSP 316L SS B16.5 150LB RAISED FACE FLANGE AT DRAIN OUTLET

K-TREADLE FOOT CONTROL FOR EYEWASH ACTIVATION

FLASHING BEACON (FLP)

ARABIC PICTOGRAM SHOWER / EYEWASH SIGNS

TEMPERATURE TRANSMITTER

FLOW TRANSMITTER MONITOR LEVEL TRANSMITTER MONITOR PROXIMITY SWITCH FOR SHOWER - REMOTE ALARM (FLP)

PROXIMITY SWITCH FOR SHOWER - LOCAL ALARM (FLP)

SHOWER CONTROL PANIC BAR C/W TEST HANDLE

E S O R R E W O H S O

T 6 4 1 2

6 6 1

A

B

710

1366 CRS

S R E S U F F D O

I

T 8 4 9

9 7

C

S R C 0 5 2 1

BALLCOCK FLOAT VALVE

5 6 0 3

SECTION C-C

GRP FOOT CONTROL GRATING FOR SHOWER ACTIVATION

6

LIFTING LUGS (REMOVABLE)

7

8

STAINLESS STEEL FRAME

ASA / STAINLESS STEEL SHOWER ROSE

JUNCTION BOX FOR LEVEL, FLOW& TEMPERATURE TRANSMITTER

WHITE GRP PANELLING FITTED TO THREE SIDES OF LEGS

M12 316 STAINLESS STEEL EARTHING BOSS

GRP SUMP

SUPPORT BRACKETS FOR CHILLER PIPELINE

SECTION B-B

4 OFF

18 HOLES

FOR M16 X 150mm THROUGH BOLTS (SUPPLIED LOOSE)

ISOMETRIC VIEW

SS CHILLER SECURED INTERCONNECTING PIPEWORK (WITH ARMAFLEX INSULATION)

ZONE 1 CHILLER - 415V 10%/3PH, 50HZ 5% TOTAL COOLING DUTY 3KW

2 7 1 1

SAMPLE DRAWING - FOR INFORMATION ONLY

NOTES:

1500 LITRE CAPACITY TANK IN MEDIUM DENSITY POLYTHENE

ALL PIPEWORK & FITTINGS IN 316 STAINLESS STEEL

SUPPORT FRAME & LEGS MANUFACTURED FROM STAINLESS STEEL

ELECTRICAL SUPPLY TO BE 240V/1PH/50 OR 60HZ

ELECTRICAL SUPPLY FOR CHILLER TO BE 415V 10%/3PH, 50HZ 5%

SUITABLE FOR USE IN ZONE 1, IIB, T3

SUPPLIED WITH TAG PLATE

4 OFF FOR M12 FIXING BOLTS (SUPPLIED LOOSE)

DRAWN:

CHECKED:

APPROVED:

MATERIAL:

CHILLER FRONT VIEW

NAME

AV

KM

DATE

18/07/2024

12/06/2024

DEBUR AND BREAK SHARP EDGES

DIMENSIONS ARE IN MILLIMETRES UNLESS SPECIFIED OTHERWISE

TOLERANCES LINEAR: ANGULAR:

10mm > 1000mm / 5mm < 1000mm 0.5

A

AV

1st Release

TITLE:

1st Rel

MODEL: EXP-J-14KS/1500 CODE: 03 H TKU S4 NFP 01140 EMERGENCY TANK SHOWER, STAINLESS STEEL FRAME, 1500L

REV

DRAWN

REASON

ECN #

CHECKED

APPROVED

DATE

1

2

3

DO NOT SCALE OFF DRAWING

VARIOUS

SCALE:1:33 @ A3

FINISH:

DWG NO.

CLEAN

SHEET 1 OF 1

Q-24700

0 0 0 1

S R C 7 6 4

830 CRS

Whitefield Road, Bredbury Stockport, Cheshire, SK6 2SS T: +44(0)161-430-6618 E: sales@hughes-safety.com

A

B

C

D

E

REVISION

A

A3

Project: Q-32332 - Tyco - ADNOC Train-9 Folder: Project Root


Loading authentication...

Graph View

Backlinks

  • Index - Q-32332 - Tyco - ADNOC Train-9

Created with Infinity Constructor © 2025

  • Elynox | Go Further