FeatureMarjan ProjectRiyas Project
Material of ConstructionSS 316/316L dual grade for piping and bowls; chrome-plated brass heads; ABS float-off coversSS 316/316L dual grade for piping and bowls; chrome-plated brass heads; ABS float-off covers
Pipe SizesShower: 1-1/4” NPS\nEyewash: 1/2” NPS\nInlet/Drain: 1-1/4” NPSShower: 1-1/4” NPS\nEyewash: 1/2” NPS\nInlet/Drain: 1-1/4” NPS
MountingPedestal or floor-mountedPedestal or floor-mounted
Flow RequirementsShower: ≥75.7 l/min for ≥15 min\nEyewash: ≥1.5 l/min for ≥15 minShower: ≥75.7 l/min for ≥15 min\nEyewash: ≥1.5 l/min for ≥15 min
Temperature Range15°C to 38°C16°C to 38°C
Activation MethodStep press with optional handleStep press with optional handle
Pressure ControlSelf-regulating valves or pressure controllersSelf-regulating valves or pressure controllers
Pressure GaugeSS316 wetted parts, 4.5” dial, ½” MNPT, 30–70% of scaleSS316 wetted parts, 4.5” dial, ½” MNPT, 30–70% of scale
Anti-Freezing ValveRequiredNot specified
Flow SwitchDPDT, piston/shuttle type, 0.5A @ 125VDC, Ex d, IP66, SS316 or copper-free aluminumDPDT, piston/shuttle type, 0.5A @ 125VDC, Ex d, IP66, SS316 or copper-free aluminum
Alarm SystemOptional: red beacon + sounder, 24VDC converter\nNote - ‘Optional’ but was provided for MarjanMandatory: red beacon + 90 dB sounder, 24VDC converter, mounted on unit
Lighting (LED)100 Lux, CRI ≥80, 5000K, Ex nA/nR, IP66100 Lux, CRI ≥80, 5000K, Ex nA/nR, IP66
PhotocellNot specified - but was provided for MarjanRequired for auto light-off during daylight
DrainageRequired for all units (e.g., gravel pit, catch basin)Required for 2 elevated units
CertificationANSI Z358.1-2014ANSI Z358.1-2014
TestingHydrostatic test mandatory; functional and electrical inspection requiredHydrostatic test mandatory; functional and electrical inspection required
Coatingaccording to APCS-1Baccording to APCS-1B
MarkingBilingual signage; SS tagBilingual signage; SS tag
Instrumentation TaggingRequiredRequired
Documentation & QA/QCExtensive VDDR, QA/QC, and HSE complianceExtensive VDDR, QA/QC, and HSE compliance