A
B
C
D
E
F
G
H
I
J
Classification: Internal
1
2
3
4
5
6
7
8
9
10
PLATFORM NORTH
45°
45°
N
TRUE NORTH
TRUE NORTH
PREVAILING WIND
A
0 0 0
,
0 0 1
.
E
10160
4289
2011
1200
1469
1900
3025
I
C R T C E L E N O T 2
3 0 0 2 B X
5 3 2
T.O.G EL. +15532
235-XZ9501B
LAYDOWN AREA ‘D’ 2500(L)x 2500(W)
T.O.G EL. +15532
T.O.G EL. +18315
N D
UP
TO LER 2ND FLR
235-XZ9501A
UP
ML235503
FUTURE BRIDGE
) .
.
.
(
S O B 1105 0 0 2 0 2 + L E
C
0 0 0 5 1 1
,
.
E
15000
235-XZ8313
NOTE 15 235-FE830038 235-FE830039 235-FE830040
X3
CO2 4.5 kg
11
B
235-XZ8303
12
4152
235-XZ8304
235-XZ8334
235-XZ8329
235-XZ8330
SC T.O.G EL. +15532 235-XZ8334
235-XZ8304
n=12
n=12
0 0 0 0 3 1
,
.
E
235-XZ8303
ML235502
13 WHP9S & RP9S KEY PLAN
14
B
2
1
45°
PREVAILING WIND
E U R T
H T R O N
C
A
DROP ZONE FROM SECOND FLOOR 1300 (L)x1300(W)
235-XZ8329
235-XZ8330
LADDER TO LER 2ND FLOOR
HOLDS:
- TAG NOS.
NOTE 14
T.O.P. EL. +16800
2 0 3 8 Z X
5 3 2
235-FE830003
9 Kg
FIRE/BLAST WALL
T.O.P. EL. +16800
FIRE/BLAST WALL
235-XB2002 20 TON ELECTRIC EL+20000 (B.O.S.)
235-X2001
COAMED AREA
235SDV 49 001
235MOV 50 072
235FCV 23 022
235FE 50 022
235MOV 50 077
235MOV 50 071
235-US-04
235 FCV 23 021
235FE 50 001
235MOV 50 078
235MOV 50 074
XXX-XZXXXX (HOLD-1)
BAM 6
235-FE830026
235-FE830004
BC 56.7 kg
9 Kg
LAYDOWN AREA ‘A’ CAP. 20MT 13400(L) x 5300(W)
235-XB2001 20 TON ELECTRIC EL+20000 (B.O.S.)
235-X2001
235-XZ8316
COAMED AREA
235SDV 49 020
REMOVABLE HANDRAIL
REFER DETAIL-2
235-T8702
235-V9501
REFER DETAIL-1
235-P9701
UP
UP
TO TOP DECK
SPACE PROVISION FOR FUTURE TEST SEPARATOR 3250(L) x 3100(W)
100
0 0 2
100
0 0 2
MIN. CRANE RADIUS 6.7M
400
400
ML235504
T.O.G. EL. +18282
235-XZ8315
9 Kg
235-FE830005
BAM 6
XXX-XZXXXX (HOLD-1)
235MOV 50 073
235-US-03
° 7 1
) E L G N A E N O Z O G O N (
2
1
235-XZ8354 FE
235-XZ8302 NOVEC
235-XZ8332 WV
235-XZ8308
n=4
N. 114,000
2
235-FE830007
9 Kg
235-XZ8314
BC 56.7 kg
235-FE830027
N. 100,000
1
235-FE830006
9 Kg
2 8 8 2 1
0 7 7 1
0 0 0 4 1
0 3 5 8
ML235501
BRIDGE BR9S-1 TO EXISTING WHP9S PLATFORM (REFER 235-20-PI-PLN-0002 FOR OVERALL FIELD LAYOUT OF RP9S)
1M
0
1M
2M
3M
4M
5M
C
0 0 0 , 5 1 1 .
E
B
0 0 0 , 0 3 1 .
E
B
C
AREA, MEASURED VERTICALLY FROM DECK SURFACE OF LANDING OR PLATFORM.
A
- THE PORTABLE EXTINGUISHERS LOCATED OUTDOOR SHALL BE
15
16
NOTES:
- ALL DIMENSIONS AND ELEVATIONS ARE IN MILLIMETERS
UNLESS STATED OTHERWISE.
- PRIMARY ESCAPE ROUTE: 1.12M WIDTH & 2.286M HEIGHT,
SECONDARY ESCAPE ROUTE 0.76M WIDTH & 2.286M HEIGHT (TYP.)
-
BREATHING AIR MANIFOLD 6 PERSON IS PROVIDED, AS PER TECHNICAL SAFETY BASIS OF DESIGN (OFFSHORE) FOR COMP3 PROJECT (200-20-SH-DEC-00013).
-
AS PER TECHNICAL SAFETY BASIS OF DESIGN (OFFSHORE)
FOR COMP3 PROJECT (200-20-SH-DEC-00013) - DEDICATED 45 MINUTES 4 SCBA SETS WITH CABINETS SHOULD BE PROVIDED FOR INVESTIGATION TEAM USE ONLY.
- THIS LAYOUT SHALL BE USED ONLY FOR QUANTITY AND
LOCATION OF FIREFIGHTING, SAFETY, LIFESAVING EQUIPMENT AND DIRECTION OF ESCAPE ROUTES.
- THE MINIMUM HEADROOM HEIGHT SHALL BE PROVIDED IN ALL
PROVIDED WITH WEATHER-PROOF CABINET.
- WHEELED EXTINGUISHERS LOCATED OUTDOOR SHALL BE
PROVIDED WITH A UV-RESISTANT RED-VINYL COVER. 9. ARROWS SHOWN ON THE ESCAPE ROUTE INDICATE THE
PREFERRED DIRECTION OF EGRESS TOWARDS THE PRIMARY MUSTER AREA. IN CASE OF EMERGENCY AT RP, PERSONNEL SHALL USE BRIDGE TO REACH PRIMARY MUSTER AREA LOCATED AT WELLHEAD PLATFORM 9S LER BUILDING TR. IN CASE ESCAPE THROUGH BRIDGE TOWARDS WELLHEAD IS NOT FEASIBLE, PERSONNEL TO PROCEED TO SECONDARY MUSTER AREA LOCATED AT RP LER BUILDING TR FOR MUSTERING.
10.LOCATION OF FIREFIGHTING, SAFETY, LIFE SAVING
EQUIPMENT AND DIRECTIONAL ARROWS INDICATIVE ONLY. THE EXACT LOCATION WILL BE BASED ON ACTUAL SITE CONDITION.
11.STAIRCASES SHOULD ALLOW TRANSPORTATION OF AN
INJURED PERSON THROUGH STRETCHER, TO BE CARRIED BY TWO PERSONS.
- ALL FIRE & SAFETY EQUIPMENT SHALL BE LOCATED IN SUCH A
WAY THAT THEY ARE EASILY ACCESSIBLE.
13.NOVEC 1230 (FK-5-1-12) CLEAN AGENT SYSTEM PROTECTION SHALL BE PROVIDED FOR ELECTRICAL & INSTRUMENT ROOM AND UPS, INSTRUMENT & TELECOM ROOM IN THE LER. 14.REFER TO FIRE, SAFETY EQUIPMENT AND ESCAPE ROUTE
LAYOUT - LOCAL EQUIPMENT ROOM-RP9S (235-83-SH-PLN-00002) FOR THE DETAIL ARRANGEMENT OF FIRE, SAFETY EQUIPMENT AND ESCAPE ROUTE LAYOUT INSIDE THE LER.
-
THREE (3) NOS. CO2 PORTABLE FIRE EXTINGUISHERS SHALL BE LOCATED AT THE MAIN ENTRANCE TO THE ELECTRICAL & INSTRUMENT ROOM FOR FIRE BRIGADE USE.
-
ALL ESCAPE ROUTES SHALL BE MARKED WITH ESCAPE MARKER PAINTED ON THE FLOOR IN OIL RESISTANT PHOTOLUMINESCENT PAINT THAT IS VISIBLE, DURABLE AND ANTI-SLIP.
-
AS PER TECHNICAL SAFETY BASIS OF DESIGN
(200-20-SH-DEC-00013) – FOR OUTDOOR AREAS, THE DEAD END SHALL NOT EXCEED 6 M OF TRAVEL DISTANCE.
LEGENDS:
LEGEND
CO2 4.5 kg
9 Kg
BC 56.7 kg
n=4
FE
SC
BAM 6
n=12
WV
DESCRIPTIONS PRIMARY ESCAPE ROUTE 1.12m(WIDTH) X 2.286m (HEAD CLEARANCE) SECONDARY ESCAPE ROUTE 0.76m(WIDTH) X 2.286m (HEAD CLEARANCE) 4.5kg CO2 PORTABLE FIRE EXTINGUISHER
9 kg POTASSIUM BICARBONATE DRY CHEMICAL POWDER (BC) PORTABLE FIRE EXTINGUISHER
56.7kg DRY CHEMICAL POWDER (BC) WHEELED FIRE EXTINGUISHER
LIFEBUOY WITH LIFELINE
LIFE RAFT n=(NUMBERS OF PERSON CAPACITY)
SELF CONTAINED BREATHING APPARATUS (45 MINUTES) (NOTE 4) CABINET FOR 4 UNITS OF SCBA
FIREMAN EQUIPMENT
SCRAMBLE NET
BREATHING AIR MANIFOLD CABINET WITH 6 NUMBERS OF HOSE UNIT (NOTE 3) LIFE JACKET
CABINET FOR 12 UNITS OF LIFE JACKET
WORK VEST
CABINET WITH 24 UNITS OF WORK VEST
NOVEC
NOVEC 1230 (FK-5-1-12) FIRE SUPPRESSION SYSTEM PACKAGE (NOTE-13)
QTY
3
5
2
4
2
4
1
1
1
2
24
2
24
1
1
200-20-SH-DEC-00013
TECHNICAL SAFETY BASIS OF DESIGN (OFFSHORE) FOR COMP3 PROJECT
235-23-PI-PLP-00005
EQUIPEMENT ARRANGEMENT PLAN LER LEVEL 2 FOR RP9S
235-23-PI-PLP-00003
EQUIPMENT ARRANGEMENT PLAN MAIN DECK FOR RP9S
REFERENCE No.
TITLE
REFERENCES
A
A1
No.
ISSUED FOR REVIEW
ISSUED FOR IDC
DESCRIPTION
MTA
MTA
JB
JB
BPB
13/05/25
BPB
28/04/25
BY
CHKD
APVD
DATE
REVISIONS
PROJECT TITLE :
COMP3 - NFPS OFFSHORE RISER / WELLHEAD PLATFORM & INTRAFIELD PIPELINES PROJECT
A
B
C
D
E
F
G
H
I
J
K
L
K
TYPICAL DETAIL-1
TYPICAL DETAIL-2
N.T.S
N.T.S
L
EQUIPMENT NO. 235-X2001 235-XZ9501A/B 235-XB2001 235-XB2002 235-XB2003 235-XZ8302 ML235501 ML235502
1
EQUIPMENT LIST
DESCRIPTION
PIPELINE PIG LAUNCHER TEMPORARY CASCADE BREATHING AIR PACKAGE
MONORAIL 20 MT ELECTRIC MONORAIL 20 MT ELECTRIC MONORAIL 2 TON ELECTRIC NOVEC 1230 (FK-5-1-12) CLEAN AGENT SKID NAVAID LANTERN NAVAID LANTERN
2
SIZE (MM)
28” X 32”(OD) X 6022(L) 1360(L) X 1360(W) X 3000(H)
HEB600 HEB600 UB254X146X43
400 (L)X400(W)X1834(H) 400 (L)X400(W)X1834(H) 3
EQUIPMENT NO. ML235503 ML235504 235-P9701 235-T8702 235-US-03 235-US-04 235-V9501 235-XZ8303
4
EQUIPMENT LIST
DESCRIPTION
NAVAID LANTERN NAVAID LANTERN
MEG TRANSFER PUMP CP SEPARATOR UTILITY STATION UTILITY STATION INSTRUMENT AIR RECEIVER LIFE RAFT 5
SIZE (MM) 400 (L)X400(W)X1834(H) 400 (L)X400(W)X1834(H)
1910 (L) X 900 (W) X 1834 (H) 3400(L) X 2200(W) X 1800 (H)
EQUIPMENT NO. 235-XZ8304 235-XZ8334
1700 ID x 4000 (T/T) 1300 (L) X 713(W) X 685(H)
7
6
MAIN DECK (T.O.S. EL. +15500) FROM EL.+ 14000 TO 20400
MIN. NO GO ZONE (R=30.177M)
NO GO ZONE FOR BRIDGE
DROP ZONE 2600(L) x1300 (W)
MAX. CRANE RADIUS 35M MAIN HOIST SWL 22.5MT
EQUIPMENT LIST
DESCRIPTION
LIFE RAFT SCRAMBLE NET
SIZE (MM)
1300 (L) X 713(W) X 685(H)
T.O.G EL. +22810
UP TO TOP DECK
DN
TO MAIN DECK
UP
Qatar Energy LNG
T.O.G EL. +21610
T.O.P EL. +21588
Qatar Energy LNG
THIS DOCUMENT IS PROPERTY OF QATARENERGY LNG. THIS DRAWING OR MATERIAL DESCRIBED THEREON MAY NOT BE COPIED OR DISCLOSED IN ANY FORM OR MEDIUM TO THIRD PARTIES, OR USED FOR OTHER THAN THE PURPOSE FOR WHICH IT HAS BEEN PROVIDED, IN WHOLE OR IN PART IN ANY MANNER EXCEPT AS EXPRESSLY PERMITTED BY QATARENERGY LNG.
CONSULTANT / CONTRACTOR :
Saipem S.p.A.
AIR LOCK
NOTE 14
LADDER TO MAIN DECK
TITLE :
CONTRACTOR DRAWING No. :
033764-H-D00-12-SPM-LP-D-00042-0001
FIRE, SAFETY EQUIPMENT AND ESCAPE ROUTE LAYOUT - MAIN DECK - RP9S
SCALE :
1:100
PROJECT No. :
LTC/C/NFP/5129/20
PROJECT
033764
DRAWING No.
SHT
SIZE REVISION
235-83-SH-PLN-00003
0001
A1
A
BLAST WALL
N. 114,000
2
BLAST WALL
LER LEVEL 2 (SCALE:NTS)
10
11
12
13
14
15
16
Project: Q-32705 - Saipem COMP3 Folder: 1. 26.06.25