Infinity

Not logged in
Home

❯

Reference Examples

❯

Q 32794 Tecnicas Stade LNG

❯

Options 2 & 3 EXP AH 5GS 45G Outdoor Shower

Product Datasheet

Trace tape heated safety shower with ASA closed bowl eye wash

EXP-AH-5GS/45G

A floor mounted safety shower with eye/face wash unit designed

for use where there is the risk of water within the pipework

freezing in cold climates. Trace tape heating and insulation

ensures workers exposed to hazardous substances can utilize

the safety shower without the risk of malfunction due to freezing

conditions.

Meets EN and ANSI requirements.

Supplied with safety signage conforming to BS EN 7010 mounted

to the unit and foot treadle for hands-free operation of the eye/

face wash.

Specifications

MATERIALS OF CONSTRUCTION

PIPEWORK & FITTINGS

Stainless steel

OPERATING VALVE

SHOWER NOZZLE

EYE WASH

Stainless steel, full bore, stay open ball valve

Injection moulded nylon 6

ASA

EYE WASH DIFFUSERS

Chrome plated brass retaining ring, stainless steel filter mesh, plastic body

INSULATION & OUTER CASING

Polyurethane foam insulation with a medium density polyethylene impact resistant outer casing

SERVICES

ELECTRICAL EQUIPMENT

ELECTRICAL SUPPLY

HEATING TYPE

HEATING LOAD

WATER INLET

OPERATING PRESSURE

MINIMUM FLOW RATES

AMBIENT OPERATING TEMPERATURE

MINIMUM

MAXIMUM

OPERATION

SHOWER

EYE WASH

DIMENSIONS & WEIGHT

DIMENSIONS (WxDxH)

WEIGHT

ATEX Zone 1 & 2. Gas groups IIA and IIB. Temp Class T3 (IIC available)

240V, single phase, 50/60Hz

Trace tape heated and insulated

57 watts

11/4” male BSP

2 to 6 BAR G / 29 to 87 PSI (higher supply pressures accommodated with the incorporation of the optional pressure reducing valve)

Shower: 76 L per minute / 20 US gal per minute

Eye wash: 12 L per minute / 3 US gal per minute

-25C / -13F

35C / 95F

Pull handle

Pull lid down

338mm (13.3in) x 884mm (34.8in) x 2570mm (101.2in)

25kg (55lb)

www.hughes-safety.com

General Arrangement Drawing

Trace tape heated safety shower with ASA closed bowl eye wash

EXP-AH-5GS/45G

1

PROJECTION

2

658

3

4

5

6

7

8

PICTOGRAM ‘SHOWER & EYEWASH’ SIGN WITH BRACKETS

SAFETY SHOWER BALL VALVE

POLYETHENE INSULATED JACKET

TRACE TAPE HEATING

AIR THERMOSTAT

JUNCTION BOX FOR ELECTRICAL CONNECTION

TRACE TAPE HEATING

SELF-DRAINING SPRAY NOZZLE (60 ANGLE)

PULL HANDLE FOR SHOWER ACTIVATION

AERATED DIFFFUSER NOZZLES

HINGED LID

OPERATING VALVE

1-1/2 INCH BSP MALE DRAIN OUTLET

FLOW REGULATOR

DETAIL B SCALE 1 : 10

C

G-TREADLE TYPE FOOT CONTROL FOR EYEWASH ACTIVATION

A

A

150

100

4 X 15 HOLES FOR M12 FIXING BOLTS (NOT SUPPLIED)

0 0 2

5 5 1

SECTION A-A SCALE 1 : 10

REV

A

DRAWN

REASON

LS

1st Release

1-1/4 INCH BSP MALE WATER INLET

5 3 1

DETAIL C SCALE 1 : 10

ISOMETRIC VIEW

NOTE: 1.

EXP-AH-5GS/45G FREEZE PROOF EMERGENCY SAFETY SHOWER WITH EYE/FACEWASH FOUNTAIN MODULES ARE REMOVABLE WITH STANDPIPE IN SITU ELECTRICAL SUPPLY TO BE 240V/1PH/50 OR 60HZ SUITABLE FOR USE IN ZONE 1&2 AREAS, GAS GROUPS IIA,IIB

E

ECN #

CHECKED

APPROVED

DATE

1st Rel

AV

AV

04/07/2024

B

0 7 5 2

E L Z Z O N R E W O H S O

T

1 5 1 2

S R E S U F F D O

I

T

7 9 0 1

884

8 3 3

NAME

LS

AV

AV

DATE

25/03/2021

14/04/2021

04/07/2024

DRAWN:

CHECKED:

APPROVED:

MATERIAL:

DEBUR AND BREAK SHARP EDGES

TITLE:

DIMENSIONS ARE IN MILLIMETRES UNLESS SPECIFIED OTHERWISE

TOLERANCES LINEAR: ANGULAR:

20mm > 1000mm / 15mm < 1000mm 0.5

VARIOUS

SCALE:1:18 @ A3

FINISH:

Whitefield Road, Bredbury Stockport, Cheshire, SK6 2SS T: +44(0)161-430-6618 E: sales@hughes-safety.com

1

2

3

DO NOT SCALE OFF DRAWING

MODEL NO: EXP-AH-5GS/45G(F2)

CODE: 03 H HEG S6 FP 00570|ZS002

OUTDOOR EMERGENCY SAFETY SHOWER WITH EYE/FACEWASH FOUNTAIN

CLEAN

SHEET 1 OF 1

EXP-AH-5GS-45G(F2)

DWG NO.

A

B

C

D

REVISION

A

A3

A

B

C

D

E

F

www.hughes-safety.com

Hughes Safety Showers Ltd, Whitefield Road, Bredbury, Stockport SK6 2SS UK T: +44 (0)161 430 6618 E: sales@hughes-safety.com

Project: Q-32794 - Tecnicas - Stade LNG Folder: Project Root


Loading authentication...

Graph View

Backlinks

  • Index - Q-32794 - Tecnicas - Stade LNG

Created with Infinity Constructor © 2025

  • Elynox | Go Further