Infinity

Not logged in
Home

❯

Reference Examples

❯

Q 32859 NMDC Ruwais

❯

RFQ Files

❯

RLNG 000 EL PP 5003_1 (1)

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 1 OF 8

ADNOC GAS

Instruction to Vendor - Declaration of Conformity for EMC

COMPANY Contract No.

4700022871

JV TJN RUWAIS Contract No

215122C

Document Class

Class 3

Document Category (for Class 1)

NA

OPERATING CENTER Contract No.

OPERATING CENTER Doc Ref.

SR-000-13808-0803

1

Issued for Construction

27-Aug-2024

K.M.M.Raja

E. Papeil S. Pandey A. Ghosh

M.Sano / I.Sawaki

Rev.

Revision Purpose

Date

Prepared by

Checked by Approved by

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

1 / 8

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 2 OF 8

Table of Contents

Contents

Page

1.0 1.1 1.2 2.0 2.1 2.2 3.0 4.0 4.1 5.0

INTRODUCTION … 4 Purpose … 4 Holds List … 4 REFERENCES … 5 Codes and Standards. … 5 Project Documents. … 5 DEFINITIONS … 5 GENERAL REQUIREMENT … 5 Electromagnetic Compatibility (EMC) … 5 ATTACHMENT … 5

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

2 / 8

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 3 OF 8

Table of Changes compared to previous revision

Paragraph

Modification description

Remarks / Origin

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

3 / 8

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 4 OF 8

1.0

INTRODUCTION

The ADNOC Ruwais LNG Project is a two train, near net-zero electrically driven LNG facility, targeting international markets. The feed gas for the project is supplied from the Habshan Gas Processing Plant via a new export gas pipeline. The plant will have two 4.8 MTPA (nominal capacity) electric driven LNG Trains with associated LNG storage/marine export facilities and utilities.

Figure 1 – Project Context

The ADNOC Ruwais LNG Project foresees the following main components at the facility:

 Onshore LNG Liquefaction facilities for 2 x 4.8 MTPA electrically driven LNG Trains (9.6MTPA total)

 Common facilities including inlet receiving facilities, LNG storage, BOG handling, flare, refrigerant

storage and support buildings.

 Utilities to support the facilities including import power from the national grid.

 Marine facilities for LNG export and bunkering.

1.1

Purpose

This instruction covers the procedure for submission of “System EMC Check List”, “Declaration of Conformity for EMC” for the ADNOC Ruwais LNG Project.

1.2

Holds List

To be updated requirement in accordance with EMC assessment.

HOLD

DESCRIPTION

1

2

3

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

4 / 8

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 5 OF 8

2.0

REFERENCES

2.1

Codes and Standards.

IEC 61000

Electromagnetic Compatibility (EMC) – All Parts

2.2

Project Documents.

RLNG-000-EL-BOD-0001

Electrical Design Basis

AGES-GL-02-001

Electrical Engineering Design Guide

3.0

DEFINITIONS

COMPANY

CONTRACTOR

EPC ADOC POC YOC

ABU DHABI NATIONAL OIL COMPANY (ADNOC) P.J.S.C. TJN Ruwais, Joint Venture of Technip Energies France-Abu Dhabi, JGC Corporation and National Marines Dredging Company (NMDC) Engineering Procurement Construction Abu Dhabi Operating Center - National Marines Dredging Company Paris Operating Center - Technip Energies Yokohama Operating Center - JGC Corporation

4.0

GENERAL REQUIREMENT

4.1

Electromagnetic Compatibility (EMC)

EMC levels should be based on the industrial level in accordance with IEC 61000-6-4 for emission and IEC 61000-6-2 for immunity. For other EMC requirement shall be followed each equipment specification and data sheet. Any deviations from the generic industrial standards are to be indicated in the EMC check list.

Vendor shall provide the evidence that the equipment complies with the appropriate EMC requirement such as “System EMC Check List “and “Declaration of Conformity for EMC”.

5.0

ATTACHMENT

Attachment- 1: System EMC Check List

Attachment- 2: Declaration of Conformity for EMC

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

5 / 8

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 6 OF 8

Attachment- 1: System EMC Check List

System list

PO number System description

Location/ WBS

Vendor

XX- YYYY- ZZZ

EMC requirements IEC 61000-6-4 (emission) IEC 61000-6-2 (immunity)

Reference Project Specification doc. reference

Major items containing electrical/electronic equipment

Sl.No Description of

equipment

VSD Electrical motor PLC (Controller)

Compliance Reference

YES NO

Doc no.

Doc no.

Further description

Not applicable

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

6 / 8

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 7 OF 8

Compliance

YES

NO

Attachment- 2: Declaration of Conformity for EMC

DECLARATION OF CONFORMITY

We: Address:

Name of Manufacturer Address of Manufacturer

hereby declare that the system/equipment: Equipment: Model No.: Serial No.:

Description of system/equipment Model name/number Serial number

is in conformity with the applicable requirements of the following standards:

Standard

Title

IEC 61000-6-4 Note 1

IEC 61000-6-2 Note 1

Other standards Note 2

Electromagnetic compatibility (EMC) – Part 6.4: Generic standards – Emission for industrial environments Electromagnetic compatibility (EMC) – Part 6.2: Generic standards – Immunity for industrial environments

In accordance with the following Directive: 2014/30/EU

Electromagnetic Compatibility (EMC) Directive

Applicable conditions

Reference document

Ref. document to be included (e.g. installation manual) Ref. document to be included (e.g. test report) Ref. document to be included (e.g. equipment and/or software settings)

Installation requirements Note 3 Performance criteria Note 4

Other technical documentation Note 5

Date and Place of issue:

Signature:

Name: Position:

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

7 / 8

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

RUWAIS LNG PROJECT

INSTRUCTION TO VENDOR - DECLARATION OF CONFORMITY FOR EMC

COMPANY DOCUMENT REF. CONTRACTOR DOC. REF.

RLNG-000-EL-PP-5003 215122C-000-PP-1600-5003

REVISION: 1

PAGE 8 OF 8

Notes:

  1. Generally, the generic standards for emission and immunity for industrial environments are

applicable.

  1. Product standards with limits and levels equivalent to those of the generic industrial standards may be applied, e.g. for emission in accordance with IEC CISPR 11, class A, group 1. Where deviating levels from the generic standards are used, applicable EMC installation conditions are to be specified to comply with the appropriate EM zones.

In this context, due attention is required for product standards IEC 61800-3 for VSD (Variable Speed Drive) and IEC 62040-2 (Uninterruptible Power Supply), which may specify significantly higher emission levels, and which may require the implementation of an EMC plan.

  1. Any installation requirements with regards to cable lengths, type of cables, cable shielding and segregation,additional filters, earthing arrangement or other EMC installation condition in order to comply with the specified standard(s).

  2. Refer to description of Performance Criteria in IEC 61000-6-2.

  3. Specific settings of equipment such as data rates, inverter switching frequencies etc. may be

applicable to comply with the specified standard(s).

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

8 / 8

J-DMS 29-Aug-2024 UNCONTROLLED WHEN PRINTED

Project: Q-32859 - NMDC - Ruwais Folder: RFQ Files


Loading authentication...