Infinity

Not logged in
Home

❯

Reference Examples

❯

Q 32859 NMDC Ruwais

❯

RFQ Files

❯

RLNG 000 HS SP 0006_0

RUWAIS LNG PROJECT

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

COMPANY Document Ref

CONTRACTOR Document Ref

RLNG-000-HS-SP-0006

215122C-000-SP-1900-0006

ADNOC GAS

REVISION : 0

PAGE 1 of 7

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

COMPANY Contract No.

TJN RUWAIS Contract No.

4700022871

215122C

Document Class

Document Category (for Class 1)

2

N/A

OPERATING CENTER Contract No.

OPERATING CENTER Doc Ref.

215122C-000-PDS-1900-0001

0

ICR – Issued for Client Review

16-Apr-25

DGO / D. Yokanathan

V. Evans/ K. Nitta / D. Shah

S. Deilles / K. Fujii

Rev.

Revision Purpose

Date

Prepared by

Checked by

Approved by

DOCUMENT REVISIONS

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

Page 1/7

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

Project Name Client Location

Ruwais LNG Project ADNOC GAS Ruwais, UAE

CPY Doc. No. Requisition No. Document No.

RLNG-000-HS-SP-0006 RLNG-000-HS-R-8851 215122C-000-SP-1900-0006

2

Page Issue Revision

of

7 ICR 0

.

v e R

Standard / Document Number

REFERENCES

Standard / Document Title

ANSI/ISEA Z358.1

American National Standard for Emergency Eyewash and Shower Equipment

AGES-SP-03-001

Escape, Evacuation, Rescue & Life Saving Appliances (EER & LSA) Specification

AGES-SP-03-002

Active Fire Protection System Specification (Part 4)

RLNG-000-PM-BOD-2002

Project Basis of Design

RLNG-000-PM-SP-2002

Site and Utility Data

RLNG-000-PR-BOD-0003

Utility Design Basis

RLNG-000-HS-PP-0001

Design HSE Philosophy

RLNG-000-EL-BOD-0001

Electrical Design Basis

RLNG-000-HS-PP-0301

Hazardous Area Classification Philosophy

RLNG-000-PI-SP-1022

Specification for Piping Material Classes

RLNG-000-PT-SP-0001

Project Specification for Protective Coating of Equipment, Piping & Structures

REVISIONS AND HOLDS

Revision

Description of Changes

0

Not applicable - New document

HOLD

HOLDS

Description

1

Line numbers on the P&IDs for some of the Safety Shower and Eye Wash units to be confirmed later.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

Page 2/7

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

Project Name Client Location

Ruwais LNG Project ADNOC GAS Ruwais, UAE

CPY Doc. No. Requisition No. Document No.

RLNG-000-HS-SP-0006 RLNG-000-HS-R-8851 215122C-000-SP-1900-0006

3

Page Issue Revision

of

7 ICR 0

. v e R

S. No.

General Notes

Environmental Conditions are defined in Project Basis of Design (Doc. No. RLNG-000-PM-BOD-2002). The design of all the outdoor equipment shall address the below normal operating conditions, in particular • High UV radiation levels • High ambient temperature • Marine and Saliferous environment • Dust and sand environment • High humidity and corrosive environment. The requirements of these conditions shall be fully compensated for, both in the design and in the construction materials of equipment. All equipment with associated accessories shall be designed for a period of 30 years in line with Project Basis of Design (Doc. No. RLNG-000-PM-BOD-2002) when maintained in accordance with manuals supplied by the VENDOR.

Each Safety Shower & Eye Wash Unit shall be provided with a dedicated overhead tank, which will be fed from plant potable water supply header.

Safety Shower & Eye Wash Units are placed in the areas which are exposed to direct sunlight. Hence, Safety shower and eye wash unit should be insulated and require a cabinet.

Safety Shower & Eye Wash Unit shall be fitted with a flow switch which is activated when the shower is being used and will raise an alarm in the control room.

Safety Shower & Eye Wash Unit shall be designed in such a way that it shall be possible to operate both Safety Shower and Eye Wash at the same time.

Both Safety shower and Eye wash must be designed such that once opened, the valves remain open without the continuous pressure or action from the operator until intentionally closed.

Painting shall be performed in accordance with ‘Project Specification for Protective Coating of Equipment, Piping & Structures’ (Doc. No. RLNG-000-PT-SP-0001). Supply water filling rate for a unit shall not exceed 10 m3/h, otherwise a restriction orifice shall be supplied by the Vendor to limit the flow.

Operating Instructions (with pictogram) shall be provided in Arabic & English.

Manufacturer’s test certificates/compliance certificate shall be furnished by the Vendor.

Vendor shall submit manufacturing, test, inspection, and welding procedures for CONTRACTOR’s approval prior to manufacturing.

The use of refurbished and re-use of metallic materials is prohibited.

Vendor shall perform Tests and / or inspections under the Vendor’s own quality control. The Quality plan and Inspection and Test Plan shall be submitted to CONTRACTOR for review.

Any deviation from the requirements mentioned in this specification shall be duly informed and shall be approved by CONTRACTOR/ COMPANY.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

Page 3/7

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

Project Name Client Location

Ruwais LNG Project ADNOC GAS Ruwais, UAE

CPY Doc. No. Requisition No. Document No.

RLNG-000-HS-SP-0006 RLNG-000-HS-R-8851 215122C-000-SP-1900-0006

4

Page Issue Revision

of

7 ICR 0

.

v e R

GENERAL

Type of unit

Manufacturer

Model No.

Design Code

Installation Location

Operating Mechanism

Safety Shower and Eye Wash unit (cabinet type) with dedicated Overhead tank and Chiller unit. Refer to TYPICAL ARRANGEMENT DRAWING in Sheet 6.

Vendor To Advise

Vendor To Advise

ANSI/ISEA Z358.1

Outdoor

Pull Rod for Safety Shower / Foot Pedal for Eye Wash

Insulation of the Pipes and Tanks

Yes ; Cold Insulation

Cabinet

Yes ; covered on three sides and around the tank

AMBIENT & DESIGN CONDITIONS

Ambient Temperature

Design Temperature

Humidity

Atmosphere

°C

°C

%

Minimum

Maximum

4.1

4

3

51.2

87

100

Marine, Saliferous, Dust and Sand

SERVICE CONDITIONS

Operation (Continuous or Intermittent)

Service

Safety Shower Capacity

litre / min

Eye Wash Capacity

litre / min

Operation Time of Safety Shower & Eye Wash

minutes

Required temperature of the flushing water

°C

Potable Water

Intermittent

76.0

11.4

15

26.0

Required pressure of the flushing water

barg

As per ANSI/ISEA Z358.1

POTABLE WATER SUPPLY CONDITIONS

Minimum

Normal

Maximum

Potable Water Supply Temperature

°C

Potable Water Supply Pressure

barg

Mechanical Design Temperature

°C

Mechanical Design Pressure

barg

16

2.0

25

3.0

4 / 87

9.8

Potable Water Supply Line Insulation

Yes ; Cold Insulation

38

4.5

POTABLE WATER SUPPLY CONNECTION

Potable Water Supply Line Connection Size

inch

1

Potable Water Supply Line Connection Type

ASME B16.5, #150, Raised Face Flange

Potable Water Supply Line Material

SS316/316L

OVERHEAD TANK

Overhead Tank capacity

litre

Drain line

Overflow line

CHILLER UNIT

Required temperature of the chilled water

Operating Limits

°C

°C

Nominal Cooling Duty

kW

Power supply

V / Ph / Hz

Control Panel IP Classification

Power Consumption

kW

1400 (minimum)

Yes ; with ball valve closed

Yes

0 to 60

26

Vendor To Advise

415 / 3 Phase / 50

IP66

Vendor To Advise

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

Page 4/7

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

Project Name Client Location

Ruwais LNG Project ADNOC GAS Ruwais, UAE

CPY Doc. No. Requisition No. Document No.

RLNG-000-HS-SP-0006 RLNG-000-HS-R-8851 215122C-000-SP-1900-0006

5

Page Issue Revision

of

7 ICR 0

. v e R

ACCESSORIES AND OTHER REQUIREMENTS

Audible Alarm / Visual Alarm

Flow Switch for Activation Alarm

Explosion Rating

Junction Box

Scald Valve

Light inside the Cabinet

Water Level Indicator for the Tank

Temperature Gauge for the Tank

Water Level Switch

Overflow nozzle

Drain Sump and Grating

Tag & Name Plate

Safety Sign with name

Fixation Materials / Anchor Bolt / Nut

Gasket / Bolt / Nut at the potable water supply tie-in

Inspection Hatch

Lifting lugs

Protective Painting

Shower Head

Eye Wash

Eye Wash Dust Cap

NO

YES

YES; Zone 1, IIB, T3

YES NO; Scalding protection is provided by means of temperature controlled chiller unit. Additional scald valve is not required. YES; Zone 1, IIB, T3

YES

YES

NO

YES

YES; with 6” outlet (Bell & Spigot joint) connected to GRE pipe (AC network)

Yes, in SS316

YES; As per ISO 7010 with English and Arabic Text

YES; To be supplied by vendor

YES; To be supplied by vendor

YES

YES YES, as per Manufacturer’s Standard suitable for the ambient conditions mentioned in Sheet 4.

MATERIAL

SS316

SS316

Manufacturer’s Standard

Pipe

As per Piping Class N104, Stainless Steel S-40S

Corrosion Allowance mm.

0

Valve

Tank

As per Piping Class N104, Ball Valve (SS316)

Medium density PE with GRP jacket and Polyurethane insulation

Accessories (Pull Rod / Foot Pedal / Spring etc.)

Cabinet

Cabinet Frame and Legs

Drain Sump

Drain Sump Grating and Frame

SS316

GRP

Galvanized Mild Steel

GRP

Galvanized Mild Steel

DIMENSIONS & WEIGHT

Dimensions (LxWxH)

Weight

Vendor To Advise

Vendor To Advise

TESTS & APPROVAL

Hydrostatic Test

Performance Test

Approval

Vendor Standard

As per ANSI/ISEA Z358.1

ANSI/ISEA Z358.1

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

Page 5/7

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

Project Name Client Location

Ruwais LNG Project ADNOC GAS Ruwais, UAE

CPY Doc. No. Requisition No. Document No.

RLNG-000-HS-SP-0006 RLNG-000-HS-R-8851 215122C-000-SP-1900-0006

6

of

Page Issue Revision

7 ICR 0

. v e R

TYPICAL SCHEMATIC OF SAFETY SHOWER & EYEWASH UNIT

TYPICAL ARRANGEMENT OF DRAIN SUMP AND OUTLET CONNECTION

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

Page 6/7

Technical Specification & Process Data Sheet - Safety Shower & Eye Wash

Project Name Client Location

Ruwais LNG Project ADNOC GAS Ruwais, UAE

CPY Doc. No. Requisition No. Document No.

RLNG-000-HS-SP-0006 RLNG-000-HS-R-8851 215122C-000-SP-1900-0006

7

of

Page Issue Revision

7 ICR 0

. v e R

QUANTITY AND TAG NUMBERS OF SAFETY SHOWER AND EYE WASH UNITS

TAG NO.

P&ID No.

Rev.

Line No.

INLET FACILITIES AREA

010-SS-501

010-SS-502

010-SS-503

LNG STORAGE TANK AREA

RLNG-000-PR-PID-5007

020-SS-001

RLNG-000-PR-PID-8005

REFRIGERANT STORAGE AREA

035-SS-501

035-SS-502

035-SS-503

035-SS-504

035-SS-505

CHILLED WATER UNIT AREA

044-SS-501

044-SS-502

BOG COMPRESSION AREA

060-SS-001

060-SS-002

UTILITY & POTABLE WATER AREA

076-SS-501

076-SS-502

FIRE WATER SYSTEM AREA

RLNG-000-PR-PID-5007

RLNG-000-PR-PID-5008

RLNG-000-PR-PID-8005

RLNG-000-PR-PID-5008

077-SS-501

RLNG-000-PR-PID-5008

SANITARY SEWER / SEWAGE TREATMENT AREA

079-SS-501

079-SS-502

LIQUEFACTION TRAIN 1

111-SS-101

111-SS-102

111-SS-103

111-SS-104

111-SS-105

LIQUEFACTION TRAIN 2

211-SS-101

211-SS-102

211-SS-103

211-SS-104

211-SS-105

Notes:

RLNG-000-PR-PID-5008

RLNG-101-PR-PID-0611

RLNG-201-PR-PID-0611

Total No. of Units = 28

0

0

0

0

0

0

0

0

0

0

2”-010-PW-XXXX-N104-C

2”-010-PW-XXXX-N104-C

2”-010-PW-XXXX-N104-C

2”-020-PW-XXXX-N104-C

2”-035-PW-XXXX-N104-C

2”-035-PW-XXXX-N104-C

2”-035-PW-XXXX-N104-C

2”-035-PW-XXXX-N104-C

2”-035-PW-XXXX-N104-C

2”-044-PW-XXXX-N104-C

2”-044-PW-XXXX-N104-C

2”-060-PW-XXXX-N104-C

2”-060-PW-XXXX-N104-C

2”-076-PW-XXXX-N104-C

2”-076-PW-XXXX-N104-C

2”-077-PW-XXXX-N104-C

2”-079-PW-XXXX-N104-C

2”-079-PW-XXXX-N104-C

2”-101-PW-0201-N104-C

2”-101-PW-0202-N104-C

2”-101-PW-0203-N104-C

2”-101-PW-0204-N104-C

2”-101-PW-0205-N104-C

2”-201-PW-0201-N104-C

2”-201-PW-0202-N104-C

2”-201-PW-0203-N104-C

2”-201-PW-0204-N104-C

2”-201-PW-0205-N104-C

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

Page 7/7

Project: Q-32859 - NMDC - Ruwais Folder: RFQ Files