RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 1 OF 30

ADNOC GAS

Instrumentation & Control System Numbering Procedure

COMPANY Contract No.

4700022871

JV TJN RUWAIS Contract No

215122C

Document Class

Class 1

Document Category (for Class 1)

Category 2

OPERATING CENTER Contract No.

OPERATING CENTER Doc Ref.

1

IFC - Issued for Construction

18-Dec-2024 E. Hostequin

0A

ICR - Issued for Client Review

30-Sep-2024 E. Hostequin

0

ICR - Issued for Client Review

16-May-2024 E. Hostequin

K. Michineau M. Joshi R. Ikeya R. Biju

K. Michineau M. Joshi R. Ikeya R. Biju

K. Michineau M. Joshi R. Ikeya R. Biju

S. Deilles F. Kiyoshi

S. Deilles F. Kiyoshi

S. Deilles F. Kiyoshi

Rev.

Revision Purpose

Date

Prepared by Checked by Approved by

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 2 OF 30

Contents

Page

Table of Contents

2.0

1.0

2.7

INTRODUCTION … 5 1.1 Project Objective and Location … 5 1.2 Scope of the Document … 5 1.3 Holds List … 5 1.4 References … 6 1.5 Definitions and Abbreviations … 6 INSTRUMENTATION NUMBERING … 7 Instrument Loop Tag Numbering … 7 2.1 2.2 Instrument Tag Numbering … 8 2.3 Analyser Tag Numbering … 9 2.4 Electrical Motors / Heaters … 10 2.5 Safety and Control Interlock … 11 Junction Boxes and Local Panels Numbering … 12 2.6 2.6.1 Field Instrument and F&G Junction Boxes … 12 2.6.2 Field Local Control Panels … 12 2.6.3 Valve Remote Panels … 13 Instrument and F&G Cables Numbering … 14 2.7.1 Single Cables … 14 2.7.2 Power Cables … 14 2.7.3 Junction Box Multicore Cables … 15 2.7.4 Local Control Panel Multicore Cables … 15 Interconnecting Cables between Systems … 16 2.7.5 2.7.6 Drum Identification … 17 2.8 Numbering of Cabinets within Buildings and Equipment Rooms … 18 2.9 Numbering of Other Control & Instrument Equipment within Buildings and Equipment Rooms … 19 2.10 Numbering of Analyser Shelters and Field Enclosures … 20 2.11 Miscellaneous Instrumentation Equipment Identification … 21 2.11.1 Instrument Air Distributors … 21 2.11.2 Junction Box Frame … 21 2.11.3 Air Volume Tank … 21 2.11.4 Sample Connection … 22 3.0 FIRE AND GAS DEVICE TAGGING RULES … 23 3.1 Fire and Gas Device Loop Numbering System … 23 3.2 Fire and Gas Device Tag Numbering System … 23 4.0 ATTACHMENTS … 24 4.1 Attachment 1 – Instrumentation Identification Letters based on ISA 5.1 … 24 4.2 Attachment 2 - Fire & Gas Loop and Device Types … 27 4.3 Attachment 3 - System Types … 28

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 3 OF 30

4.4 Attachment 4 - Signal Types … 28 4.5 Attachment 5 - Instrument Cabinet Types … 29 4.6 Attachment 6 – Other Control & Instrument Equipment Types [HOLD 6] … 29 4.7 Attachment 7 – Assignment rules for serial numbering … 30

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 4 OF 30

Table of Changes compared to previous revision

Paragraph

Modification description

Remarks / Origin

1.4

Reference [4] changed : “Fire and Gas Design Basis” (RLNG-000-HS-DWG-0201) replaced by “Fire and Gas Detection Drawing – Key Plan” (RLNG-000-HS-BOD-0201)

Fire Detection Zones are shown on F&G Detection Drawings.

1.4 & 2.7.6

Specification for Instrumentation and Telecommunication Cables split in two:

• Specification for Instrumentation Cables; • Specification for Telecommunication

Cables.

2.1 & 2.2

Note 1 related to instrumentation connected to F&G system is removed.

Units for Fire Fighting and Fire Gas System instrumentation are 083, 183 or 283.

2.4

Addition of suffixes for HSK selector:

Heater typical

• • •

“L” for Local; “O” for Off; “R” for Remote.

2.5

2.8

2.9

4.1 – Attachment 1

4.6 – Attachment 6

Addition of “KS” for functional identification of DCS or Package sequences.

Addition of a note for numbering of cabinets permanently bolted together and forming a section.

Clarification for numbering of some equipment not related to a specific system. FG replaced by FI. DV added for Deluge Valves. M loop code also used for motors

Addition of missing equipment: LPE, LPF, IRP

Alignment with P&IDs

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 5 OF 30

1.0

INTRODUCTION

1.1

Project Objective and Location

The ADNOC Ruwais LNG Project is a two train, near net-zero electrically driven LNG facility, targeting international markets. The feed gas for the project is supplied from the Habshan Gas Processing Plant via a new export gas pipeline. The plant will have two 4.8 MTPA (nominal capacity) electric driven LNG Trains with associated LNG storage/marine export facilities and utilities.

Figure 1 – Project Context

The ADNOC Ruwais LNG Project foresees the following main components at the facility:

• Onshore LNG Liquefaction facilities for 2 x 4.8 MTPA electrically driven LNG Trains (9.6MTPA

total)

• Common facilities including inlet receiving facilities, LNG storage, BOG handling, flare,

refrigerant storage and support buildings.

• Utilities to support the facilities including import power from the national grid.

• Marine facilities for LNG export and bunkering.

1.2

Scope of the Document

The purpose of this procedure is to provide the principles of identification and numbering of instrumentation and control system items.

This procedure is also applicable to package suppliers and to all other contractors on the Ruwais LNG Project.

1.3

Holds List

HOLD DESCRIPTION

1

2

3

4

5

HOLD cleared

HOLD cleared

HOLD cleared

HOLD cleared

Sampling connection types

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 6 OF 30

HOLD DESCRIPTION

6

7

8

List of equipment will be updated based on selected control systems.

HOLD cleared

HOLD cleared

1.4

References

Equipment and Component Numbering Procedure Geographical Work Breakdown Structures

[1] RLNG-000-PM-PP-2003 [2] RLNG-000-PM-PP-3107 [3] RLNG-000-HS-DWG-0001 Overall Fire Zone Drawing [4] RLNG-000-HS-DWG-0201 [5] RLNG-000-TE-PP-0001 [6] RLNG-000-IC-SP-0741 [7] RLNG-000-TE-SP-0020

Fire and Gas Detection Drawing – Key Plan Telecommunication Numbering Procedure Specification for Instrument Cables Specification for Telecommunication Cables

1.5

Definitions and Abbreviations

COMPANY

CONTRACTOR

EPC ADOC POC YOC CCB DCS ESD FACP F&G FGS FO ICSS IES MMS SIS UCP

ABU DHABI NATIONAL OIL COMPANY (ADNOC) P.J.S.C. TJN Ruwais, Joint Venture of Technip Energies France-Abu Dhabi, JGC Corporation and National Marines Dredging Company (NMDC) Engineering Procurement Construction Abu Dhabi Operating Center - National Marines Dredging Company Paris Operating Center - Technip Energies Yokohama Operating Center - JGC Corporation Central Control Building Distributed Control System Emergency Shutdown Fire Alarm Control Panel Fire and Gas Fire and Gas System Fiber Optic Integrated Control & Safety System Instrument Equipment Shelter Machine Monitoring System Safety Instrumented System Unit Control Panel

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 7 OF 30

2.0

2.1

INSTRUMENTATION NUMBERING

Loop Tag Numbering

The instrument loops shall be identified as follows:

UUU-X-NNNN

Where:

Unit number

UUU

Three digits for Unit Code (Refer to [1])

Hyphen separator

Function Identifier

Hyphen separator

X

Sequential Number

NNNN

Hyphen separator

One letter used to indicate measured/initiation Variable (Refer to Attachment 1 – Instrumentation Identification Letters based on ISA 5.1)

Hyphen separator

Four-digit sequential number used to indicate loop number. The loop sequential number shall be unique, for a given process unit, whatever the measured variable (P, L, T, F, A…). Special Range will be assigned to each package (refer to Attachment 7 – Assignment rules for serial numbering).

Example:

111-F-0011

for flow loop in process unit 111 (LNG train 1 - Precooling and Propane Cycle / C3-MR Compressors / MCHE / Liquefaction Air Coolers).

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 8 OF 30

2.2

Instrument Tag Numbering

The instrument tags shall be identified as follows:

UUU-XXXXXX-NNNN(A(A))

Where:

Unit number

UUU

Three digits for Unit Code (Refer to [1])

Hyphen separator

Function Identifier

XXXXXX

Hyphen separator

Sequential Number

NNNN

Letters when necessary

(A(A))

Up to six letters: • First letter indicates the measured/initiation Variable. • Second up to fifth succeeding letters indicate the

Modifier (Refer to Attachment 1 – Instrumentation Identification Letters based on ISA 5.1)

Four-digit sequential number, indicating the loop number. Special Range will be assigned to each package (refer to Attachment 7 – Assignment rules for serial numbering).

Used for instance for redundant equipment. More often, no suffix digit will be used, otherwise one suffix, rarely two suffixes. “R” suffix will be used for remote electronic indicator.

Examples:

111-FE-0011

for flow element in process unit 111 (related loop number will be 111-F-0011).

111-FT-0011A

for flow transmitter in process unit 111 (related loop number will be 111-F-0011), for large range if applicable.

111-FT-0011B

for flow transmitter in process unit 111 (related loop number will be 111-F-0011), for small range if applicable.

111-LI-0053R

for the remote electronic indicator related to 111-LT-0053 level transmitter.

112-LZT-0021A for 1st level transmitter in 2oo3 voting (related to 112-L-0021) in unit 112.

112-LZT-0021B for 2nd level transmitter in 2oo3 voting (related to 112-L-0021) in unit 112.

112-LZT-0021C for 3rd level transmitter in 2oo3 voting (related to 112-L-0021) in unit 112.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 9 OF 30

2.3

Analyser Tag Numbering

The analyser tags shall be identified as follows:

UUU-AXXX-NNNN(X)

Where:

Unit number

UUU

Three digits for Unit Code (Refer to [1])

Hyphen separator

Function Identifier

AXXX

Hyphen separator

Sequential Number

NNNN

Letters when necessary

(X)

Up to four letters starting with A:

  • AP: Analyser Probe
  • AX: Analyser Sampling System
  • AE: Analyser Element (like pH, conductivity, Chlorine sensor probe located in the sampling system)
  • AT: Analyser Transmitter
  • AI: System Indication/ Measurement
  • Refer also to Attachment 1 – Instrumentation Identification Letters based on ISA 5.1

Four-digit sequential number, indicating the loop number. (refer to Attachment 7 – Assignment rules for serial numbering) Special letter will be assigned for Analyser Sampling System with:

X = A for Sample Pre-Conditioning System X = B for Sample Conditioning System

Examples:

112-AP-0171

for Analyser Probe of 112-AT-0171

112-AX-0171B

for Sample Conditioning System of 112-AT-0171

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 10 OF 30

2.4

Electrical Motors / Heaters

As for instrumentation devices, tags for electrical users are also identified by their loop and function. For all motors and heaters, the loop code (function identifier) is the letter “M”.

The identification of motor/heater instrumentation signals could not follow the equipment name identification. An instrumentation sequential number, different of equipment identification, is assigned to electrical users.

The function identifiers used for electrical motors/heaters, composed of two or three characters, are listed below:

Loop Identifier M M M M M M M M M M M M M M M M M M

Function Identifier

Description

Suffix

HS HS HS HS HS HSK HSM SC XZS XL XL XL II JI SI XL XL XA

Remote Start pushbutton Remote Stop pushbutton Local Start pushbutton Local Stop pushbutton Local Emergency button Local/Off/Remote selection Main/Stand-by selection Speed control set point Trip command Running status Available status Local/Remote Status Current indication Power indication Speed indication Off position Test position MCC Common Alarm

A B C D E L / O / R

A B C

D E

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 11 OF 30

2.5

Safety and Control Interlock

SIS / FGS / UCP Safety Interlocks and DCS / UCP control interlock shall be numbered as follows:

UUU-FF-NNN(A)

Where:

Unit number

UUU

Three digits for Unit Code (Refer to [1])

Hyphen separator

Functional Identification

Hyphen separator

FF

Sequential Number

NNN

Two-letter for Functional identification as follows : • UZ = SIS, Package and F&G safeguarding logic block. • US = DCS or Package control interlock • KS = DCS or Package sequence

Three-digit sequential numbering. Number “001” to be reserved for unit shutdown (ESD-2 level). Special Range will be assigned to each package.

Letters when necessary

Example:

(A)

For example, for redundant equipment

111-UZ-001

for the general shutdown of Process unit 111.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 12 OF 30

2.6

Junction Boxes and Local Panels Numbering

All junction boxes and local control panels shall be clearly identified by means of unique numbers.

2.6.1 Field Instrument and F&G Junction Boxes

The Junction Boxes shall be identified as follows:

AAA-JXYZ-NNN

Where:

AAA

Three characters for Area Code (WBS) (Refer to [2]).

J

X

Y

Z

NNN

Example:

Hyphen separator

“J” to indicate Junction box One-letter code used to indicate the System type code (Refer to Attachment 3 - System Types). One-letter code used to indicate the Signal type code (Refer to Attachment 4 - Signal Types).

“I” for I.S. signals, “N” otherwise

Hyphen separator Three digits used to identify the JB sequence number (from 001 to 999 with 501 to 999 range assigned to Packages).

A11-JEAI-015

for a SIS junction box in A11 area with IS analog signals.

2.6.2 Field Local Control Panels

The field local control panels shall be identified as follows:

AAA-LPX-NNN

Where:

AAA

Three characters for Area Code (WBS) (Refer to [2]).

LP

X

NNN

Example:

Hyphen separator

“LP” to indicate Local Control Panel One-letter code used to indicate the Instrument System type code (Refer to Attachment 3 - System Types). Hyphen separator

Three digits used to identify the Local Control Panel sequence number. Special Range will be assigned to each package (from 001 to 999 with 501 to 999 range assigned to Packages).

A11-LPU-002

for a Package local control panel located in A11 area.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 13 OF 30

2.6.3 Valve Remote Panels

A Valve Remote panel shall be numbered in the same way as the appropriate instrument Tag number and by adding letter “-VRP” in suffix.

Example:

013-ESDV-0004-VRP Valve remote panel of the 013-ESDV-0004.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 14 OF 30

2.7

Instrument and F&G Cables Numbering

2.7.1 Single Cables

The Instrument / F&G field single cables shall be identified in the same way as the appropriate instrument Tag number, without hyphen separators.

Examples:

051PDT0184

Instrument single pair cable running to a junction box (or directly to a Marshalling Cabinet) from differential pressure transmitter 051-PDT-0184.

020TT0362

Instrument single pair cable running to a junction box (or directly to a Marshalling Cabinet) from temperature transmitter 020-TT-0362.

2.7.2 Power Cables

2.7.2.1 Instrument Power Cables

For instruments with a single power feeder cable, the cable shall be numbered in the same way as the appropriate instrument Tag number, without hyphen separators, and by adding letter “P” in suffix.

Example:

042FT0024P

Power cable supplying flowmeter 042-FT-0024.

2.7.2.2 Other Power Cables

Power cables supplying cabinets shall be identified as follows:

BB(B)NN(A)-AQ-NNN-PX

Where:

BB(B)NN(A) Building tag without hyphen (refer to [1])

A

Q

Hyphen separator

One-letter code used to indicate the Instrument System type code (Refer to Attachment 3 - System Types). One-letter code used to indicate cabinet type (Refer to Attachment 5 - Instrument Cabinet Types).

Hyphen separator

NNN

Three-digit number used to identify the Equipment sequence number

Hyphen separator

PX =

• P1 for power cable from UPS A (45’) • P2 for power cable from UPS B (45’) • P3 for power cable from UPS A (8h) • P4 for power cable from UPS A (8h) • PN for power cable from normal power supply

PX

Examples:

OB01-DS-001-P1

for UPS A (45’) power supply cable to DCS system cabinet in CCB.

SS11C-UU-001-PN

for normal power supply cable to a UCP cabinet located in e-house SS11C.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 15 OF 30

2.7.3

Junction Box Multicore Cables

Tag of a junction box multi-core cable shall be the tag of the junction box with “J” replaced with “C”:

AAA-CXYZ-NNN(-S)

Where:

AAA

C

X

Y Z

NNN (-S)

Example:

Three characters for Area Code (Refer to [2]) Hyphen separator “C” to indicate Cable One-letter code used to indicate the Instrument System type code (Refer to Attachment 3 - System Types). One-letter code used to indicate the Signal type (Refer to). “I” for I.S. signals, “N” otherwise Hyphen separator Three digits same as the JB sequence number Tag suffix code. Empty or Hyphen and 1 character

A11-CEAI-015

Intrinsically safe multicore cable from the SIS junction box A11-JEAI-015

2.7.4 Local Control Panel Multicore Cables

The instrument local control panels shall be identified as follows:

AAA-CPX-NNN(-SS)

Where:

AAA

Three characters for Area Code (Refer to [2])

CP

X

Hyphen separator

“CP” to indicate Local Control Panel Cable One-letter code used to indicate the Instrument System type code (Refer to Attachment 3 - System Types) Same code as for the local control panel.

Hyphen separator

NNN

Three digits used to identify the Local Control Panel sequence number

(-SS)

Multicore cable suffix. Empty or up to 2 numbers to identify the different multicore cables connected to the same local control panel.

Example:

A12-CPU-002-1 First multicore cable connected to A12-LPU-002 local panel.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 16 OF 30

2.7.5

Interconnecting Cables between Systems

Cables between cabinets shall be identified as follows:

CY-BB(B)NN(A)AQNNN-BB(B)NN(A)AQNNN-NN(-SS)

Where:

C

Y

Letter “C” for Cable cable

One-letter code used to indicate the Signal type (Refer to Attachment 4

  • Signal Types).

Hyphen separator

BB(B)NN(A)AQNNN

1st cabinet tag number (without hyphens) – Refer to 2.8

Hyphen separator

BB(B)NN(A)AQNNN

2nd cabinet tag number (without hyphens) – Refer to 2.8

NN

(-SS)

Example:

Hyphen separator

Two digits sequential numbers

Multicore cable suffix. Empty or up to 2 numbers for the identification of similar type of cables used in parallel or in series. To be used in particular to discriminate redundant lines A and B.

CF-OB01DS001-OB01ES002-02

for a FO cable between a DCS system cabinet in CCB and a SIS system cabinet in CCB

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 17 OF 30

2.7.6 Drum Identification

Cable drums shall be identified as follows:

SPNN-Cable_Code-NNN

Where:

SPNN

Sub-contractor work package (construction woks). SPNN = • SP03 : LNG Trains • SP04 : LNG Storage Area (excluding LNG Tanks), BOG Compression

& Jetty Topsides

• SP08 : Utilities (Common, Flare, Fire Water and Inlet Facilities) • SP05 : Process Buildings (SS, IES, CCB, JCB) • SP09 : Industrial & Non industrial Buildings • SP07 : LNG Tanks • SP10 : Marine facilities (excluding Jetty Topsides)

Hyphen separator

Cable_Code Cable Code (Refer to [6] and [7])

Hyphen separator

NNN

Three-digit sequence number from 001 to 999

Examples:

SP03-B20P1.5ISWB-003

Drum of 20P-1.5mm2-XLPE-PVC-SWA-PVC (IS) signal cable (fire resistant and buried cable) for LNG Train area.

SP05-J24W-001

Drum of 24-CORE, SWA-PVC Fiber Optic cable (fire resistant and armoured) for installation in CCB.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 18 OF 30

2.8

Numbering of Cabinets within Buildings and Equipment Rooms

Cabinets within CCB, Jetty Control Building, Instrument Equipment Shelters (IES), e-houses… shall be identified as follows:

BB(B)NN(A)-AQ-NNN

Where:

BB(B)NN(A) Building tag without hyphen (refer to [1])

A

Q

Hyphen separator

One-letter code used to indicate the Instrument System type code (Refer to Attachment 3 - System Types). One-letter code used to indicate cabinet type (Refer to Attachment 5 - Instrument Cabinet Types).

Hyphen separator

NNN

Three-digit number used to identify the Equipment sequence number Note: Even if several cabinets are permanently bolted together to form a section, each cabinet shall

have its own tag.

Examples:

OB01-DS-001

for a DCS system cabinet in CCB.

SS11C-UU-001

for a Propane compressor UCP cabinet located in Train 1 Propane Compressor LV E-House.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 19 OF 30

2.9

Numbering of Other Control & Instrument Equipment within Buildings and Equipment Rooms

Equipment (workstations, HMIs…) within CCB, Jetty Control Building, Instrument Equipment Shelters (IES), e-houses… shall be identified as follows:

BB(B)NN(A)-AQQQ-NN(S)

Where:

BB(B)NN(A) Building tag without hyphen (refer to [1])

(A)

QQQ

NN (S)

Hyphen separator One-letter code used to indicate the Instrument System type code (Refer to Attachment 3 - System Types). Empty for some equipment (IRP, FPP…) Three-letter code used to indicate Equipment type (Refer to Attachment 6 – Other Control & Instrument Equipment Types [HOLD 6]). Hyphen separator Two-digit number used to identify the Equipment sequence number Equipment Suffix Code. Empty or 1 character.

Examples:

OB01-DEWS-01

for a DCS engineering workstation in CCB.

OB01-FLPX-01

for a F&G matrix panel in CCB.

SS11C-CEWS-01 for the Propane compressor engineering workstation in Train 1 Propane Compressor

LV E-House.

SS14-IRP-01

for an Interposing Relay Panel in substation SS-14.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 20 OF 30

2.10 Numbering of Analyser Shelters and Field Enclosures

Analyser Shelters shall be identified according to the “Equipment and Component Numbering Procedure” (RLNG-000-PM-PP-2003):

AS-NN

Where:

AS

NN

AS is for Analyser Shelter Hyphen separator Two-digit number used to identify the shelter sequence number

Analyser Field Enclosures shall be identified as follows:

UUU-AC-NN

Where:

UUU

AC

NN

Examples:

Three digits for Unit Code (Refer to [1]) Hyphen separator AC for Analyser Field Enclosure Hyphen separator Two-digit number used to identify the Equipment sequence number

AS-11

for Analyser Shelter in Liquefaction Train 1

A21-AC-01

for Analyser Field Enclosure in Train 2.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 21 OF 30

2.11 Miscellaneous Instrumentation Equipment Identification

2.11.1 Instrument Air Distributors

The instrument air distributors shall be identified as follows:

AAA-IAD-NN

Where:

AAA

Three characters for Area Code (WBS) (Refer to [2]) Hyphen separator

IAD

Three letters used to indicate Instrument Air Distributor

NN

Hyphen separator Two-digit number used to indicate Instrument Air Distributor number. NNN is a sequential number starting at 01

Example:

A14-IAD-01

Air distributor in A14 area.

2.11.2 Junction Box Frame

The Junction box frame shall be identified as follows:

AAA-JBF-NN

Where:

AAA

JBF

NN

Example:

Three characters for Area Code (WBS) (Refer to [2]) Hyphen separator

Three letters used to indicate Junction Box Frame

Hyphen separator Two-digit number used to indicate Instrument Air Distributor number. NNN is a sequential number starting at 01

A12-JBF-01

Junction box frame in A12 area.

2.11.3 Air Volume Tank

The Air volume tank shall be numbered in the same way as the appropriate instrument Tag number and by adding letter “-AVT” in suffix.

Example:

011-BDV-0023-AVT

Air volume tank of the 011-BDV-0023.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 22 OF 30

2.11.4 Sample Connection

The sample connection assemblies shall be identified as follows:

UUU-SPXXY-NNN

Where:

UUU

Three digits for Unit Code (Refer to [1])

Hyphen separator

Two letters “SP” to indicate Sample Connection / Point assembly

Two digits and one letter to identify sampling connection type [HOLD 5]. Starting from 01A. Hyphen separator Three digits number used to indicate Sample assembly number. Unique sequential number starting at 001

SP

XXY

NNN

Example:

111-SP05A-001 for Sample connection type 05A in Process unit 111.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF. RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 23 OF 30

3.0

3.1

FIRE AND GAS DEVICE TAGGING RULES

Fire and Gas Device Loop Numbering System

The Fire and Gas device loops (groups of flame/gas/heat/smoke detectors, MAC, beacons, sounders etc.) shall be identified as follows:

FFFF-Q-NNNN

Where:

FFFF

Q

NNNN

Four characters for Fire Detection Zone, refer to [3] and [4] Hyphen separator “Q” letter code used to identify all Fire and Gas loops. Hyphen separator Four-digit number used to indicate loop number

Example:

02GA-Q-0178

for a Fire and Gas loop in fire detection zone FZ-02-G-A (propane vaporizer equipment in propane liquefaction area, liquefaction train 1).

3.2

Fire and Gas Device Tag Numbering System

Fire and gas devices shall be identified as follows:

FFFF-QXXXXX-NNNN

Where:

FFFF

Q

XXXXX

NNNN

Examples:

Four characters for Fire Detection Zone, refer to [3] and [4] Hyphen separator “Q” letter to identify a F&G device Two up to five-letter code used to indicate the device type (Refer to Attachment 2

  • Fire & Gas Loop and Device Types). Hyphen separator Four-digit number used to indicate loop number

02AA-QGDC-0223 for a Catalytic Hydrogen gas detector in fire detection zone FZ-02-A-A in LNG train 1.

03AA-QGDC-0223 for a Catalytic Hydrogen gas detector in fire detection zone FZ-03-A-A in LNG train 2.

04BA-QFDIR-0698 for a Triple IR Flame detector in fire detection zone FZ-04-B-A in LNG tanks area.

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF.

CONTRACTOR DOC. REF.

RLNG-000-IC-PP-0001

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 24 OF 30

4.0

4.1

Loop Code

A

B

C

D

E

F

G

H

I

J

K

L

ATTACHMENTS

Attachment 1 – Instrumentation Identification Letters based on ISA 5.1

Description

Physical Tag

Soft Tag

Loop Description

Element

Switch

Gauge

Transmitter (1)

Valve

Indication

Control

Switch Point High

Switch Point Low

Alarm / Trip High

Alarm / Trip Low

Analysis

AE, AP

Analysis (Safety)

AZE, AP

Blowdown Valve

HS, ZSC, ZSO

Corrosion, Erosion

Density / Deluge

CE

DE

Emergency Shutdown Valve

ZSC, ZSO

AT

AZT

ZT

CT

DT

ZT

Flow

FE

FS

FI

FT

Totalised Flow

Flow (Safety)

Unclassified

Hand

Current

Power

Time, Schedule

FZE

FZS

HS

FZT

IT

JT

Level

LS

LG

LT

BDV, BDYV (for solenoid)

DV ESDV, ESDYV (for solenoid), ESDY (for positioner) FV, FYV (for solenoid), FY (for positioner)

HV

LV, LYV (for solenoid), LY (for positioner)

AIC

AI

AZI

ZI

CI

DI

ZLO

ZLC

AAH

AZHH

AAL

AZLL

CAH

DAH

DAL

Output

AY

ZI, ESZY

ZLO

ZLC

ZI

FI

FIC

FAH

FAL

FY

FQI

FZI

HI

II

JI

FZSHH

FZSLL

FZHH

FZLL

JIC

IAH

JAH

IAL

JAL

LI

LIC

LSH

LSL

LAH

LAL

LY

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF.

CONTRACTOR DOC. REF.

RLNG-000-IC-PP-0001

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 25 OF 30

Description

Physical Tag

Soft Tag

Loop Code

Loop Description

Element

Switch

Gauge

Level (Safety)

Motor Operated Valve or Motor (refer to 2.4) Unclassified

Unclassified

LZS

ZSC, ZSO

Transmitter (1)

LZT

ZT

Pressure

PSE

PS

PG

PT

Differential Pressure

PDS

PDG

PDT

PZS

PDZS

Pressure (Safety)

Differential Pressure (Safety) Quantity, Fire & Gas Restriction, Remote Operated Valve (2) Speed, Frequency

Speed (Safety)

RO

SE

SZE

Shutdown Valve

ZSC, ZSO

PZT

PDZT

ST

SZT

ZT

M

N

O

P

Q

R

S

Valve

Indication

Control

Switch Point High

Switch Point Low

Alarm / Trip High

Alarm / Trip Low

Output

LZI

ZI

LZSHH

LZSLL

LZHH

LZLL

MVIC

ZLO

ZLC

PI

PIC

PSH

PSL

PAH

PAL

PY

PDI

PDIC

PDSH

PDSL

PDAH

PDAL

PDY

PZI

PDZI

SI

SZI

ZI

TI

PZSHH

PZSLL

PZHH

PZLL

PDZSHH

PDZSLL

PDZHH

PDZLL

SIC

SAH

SZHH

SAL

SZLL

ZLO

ZLC

SY

ZI

TIC

TSH

TSL

TAH

TAL

TY

MOV

PCV, PV, PYV (for solenoid), PY (for positioner) PDV, PDYV (for solenoid) , PDY (for positioner) PSV

ROV

SDV,, SDYV (for solenoid), SDY (for positioner) TCV, TV, TYV (for solenoid),

T

Temperature

TE TW

TS

TG

TT

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF.

CONTRACTOR DOC. REF.

RLNG-000-IC-PP-0001

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 26 OF 30

Description

Physical Tag

Soft Tag

Loop Code

Loop Description

Element

Switch

Gauge

Transmitter (1)

Valve

Indication

Control

Switch Point High

Switch Point Low

Alarm / Trip High

Alarm / Trip Low

Output

Differential Temperature Temperature (Safety) Multivariable Vibration, Mechanical Analysis Vibration, Mechanical Analysis (Safety) Weight, Force, Torque

Weight (Safety)

TZE TW

VE

VZE

TZS

US

VS

VZS

TZT

VT

VZT

On / Off (Valves)

XS, ZSC, ZSO

ZT

Lamp

XL

Intersystem Event, State, Presence Position, Dimension

XS, XZS

ZSO, ZSC

ZT

U

V

W

X

Y

Z

(1)

xI with “R” suffix in tag for remote local indicator separate from transmitter.

(2)

ROV is a Pipeline terminology for an actuated on/off valve.

TY (for positioner)

XV, XYV (for solenoid)

TDI

TZI

UI

VI

VZI

ZI

ZI

TDIC

UIC

TDAH

TZSHH

TZSLL

TZHH

VSH

VSL

UA

VAH

TDAL

TZLL

TDY

VAL

VY

VZHH

VZLL

ZLO

ZLC

ZLO

ZLC

Table 1 - Instrument Types

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF.

RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

4.2

Attachment 2 - Fire & Gas Loop and Device Types

Loop code

Device Type

Description

REVISION: 1

PAGE 27 OF 30

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

Q

QGDC

QGDIR

QGDBT / QGDBR

Hydrogen gas detector – Catalytic bead type

Hydrocarbon gas detector - IR point type

Hydrocarbon Gas detector Open Path / Line of Sight type – Transmitter / Receiver

QGDA

Acoustic gas detector (ultrasonic leak detector)

QGDLO

Low Oxygen Gas Detector

QFDIR

QFDUI

QFDVI

Triple IR Flame detector

UV/IR Flame detector

Video Image Flame Detector (VIFD)

QFDHR

Heat Detector - Rate Of Rise (ROR)

QFDH

QFDLH

QFDOS

QFDBT / QFDBR

QFDHS

QLDRT

QLDFO

QMAC

QFBA

QGBA

QHA

Heat Detector - Fixed

Linear Heat Detector (LHD)

Smoke Detector - Optical Point

Smoke Detector – Open Path / Line of Sight type (LOS) – Transmitter / Receiver

High Sensitivity Smoke Detection (HSSD)

Low Temperature Detector (RTD) for cold spill detection

Fiber Optic Linear Heat Detector / Low Temperature Detector (FO-LHD) for cold spill detection

Manual Alarm Call Point

Fire Beacon (Red)

Gas Beacon (Blue)

F&G Sounder

Table 2 - Fire & Gas Loop and Device Types

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF.

RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

4.3

Attachment 3 - System Types

REVISION: 1

PAGE 28 OF 30

Code

A

C

D

E

F

H

I

M

O

P

U

X

Name AMADAS – Analyzer Management and Data Acquisition System PGC – Process Gas Chromatography

Compressor Control System

DCS – Distribution Control System

SIS – Safety Instrumented System

Fire & Gas Detection System

HVAC – Heating, Ventilation and Air Conditioning

IAMS - Instrument Asset Management System

Machine Monitoring System

OTS – Operating Training System

Power

Package PLC

Miscellaneous Equipment / System

Table 3 - Instrumentation - System Types

4.4

Attachment 4 - Signal Types

Code A C D E F P T R S V X Z

Description Analogue signals Combined (Analogue and Digital signals) Digital signals Ethernet network Fibre Optical Network signals Power Supply (240Vac) Temperature mV signals Temperature RTD signals Serial Communication Signals Voltage vibration signals 24Vdc output signals Safety Network Communication

Table 4 - Instrumentation - Signal Types

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF.

RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

4.5

Attachment 5 - Instrument Cabinet Types

REVISION: 1

PAGE 29 OF 30

Code F N M P S U V X

Description FO Patch Cabinet Network Cabinet Marshalling Cabinet Power Distribution Cabinet System Cabinet UCP/PLC Cabinet Server Cabinet Miscellaneous Cabinet

Table 5 - Instrumentation – Cabinet Types

4.6

Attachment 6 – Other Control & Instrument Equipment Types [HOLD 6]

Code EWS FPP LPE LPF LSD NTS IRP OWS PRN SER

Description Engineering Workstation Fiber Optic Patch Panel SIS Matrix Panel F&G Matrix Panel Large Screen Display Network Time Server Interposing Relay Panel Operator Workstation Printers Servers

Table 6 - Instrumentation – Other Control & Instrument Equipment Types

The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.

RUWAIS LNG PROJECT

Instrumentation & Control System Numbering Procedure

COMPANY DOCUMENT REF.

RLNG-000-IC-PP-0001

CONTRACTOR DOC. REF.

215122C-000-JSD-1500-0001

REVISION: 1

PAGE 30 OF 30

4.7

Attachment 7 – Assignment rules for serial numbering

General principle for sequential numbering of field instruments:

From 0001 1001 2001 3001 4001 5001 6001 7001 8001 9001

To 0999 1999 2999 3999 4999 5999 6999 7999 8999 9999

Assigned to Common Equipment A* Equipment B* Equipment C* Spare Package - Common Package – Equipment A* or 1st main Equipment* Package – Equipment B* or 2nd main Equipment* Package – Equipment C* or 3rd main Equipment* Package - Spare

If there are identical equipment in a process unit, instrument tag numbers associated with these equipment shall have same tag number except for the first digit that will be sequential. For example, air pressure transmitters at Air Compressor A (042-K-001A) outlet and Air Compressor B (042-K- 001B) outlet will be respectively tagged 042-PT-1002 and 042-PT-2002