RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 1 OF 158
ADNOC GAS
Specification for Instrumentation Cables
COMPANY Contract No.
4700022871
JV TJN RUWAIS Contract No
215122C
Document Class
Class 2
Document Category (for Class 1)
NA
OPERATING CENTER Contract No.
OPERATING CENTER Doc Ref.
K. Michineau M. Joshi R. Ikeya R. Biju X. Baudribos
K. Michineau M. Joshi R. Ikeya R. Biju
S. Deilles F. Kiyoshi
S. Deilles F. Kiyoshi
1
IFC - Issued for Construction
22-Nov-2024 E. Biedermann
ICR - Issued for Client Review
18-Jun-2024 E. Biedermann
0
Rev.
Revision Purpose
Date
Prepared by Checked by Approved by
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 2 OF 158
Contents
Page
Table of Contents
1.0
INTRODUCTION… 4 1.1 Scope of the Document … 4 1.2 Holds List … 4 1.3 References … 4 1.4 Definitions and Abbreviations … 4 2.0 AMENDMENTS TO ADNOC GENERAL ENGINEERING SPECIFICATION AGES-SP-04-006 … 5 3.0 Appendix … 10 3.1 APPENDIX 1 - AGES-SP-04-006 … 10
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 3 OF 158
Table of Changes compared to previous revision
Paragraph
Modification description
Remarks / Origin
Document Title
Document title changed to “Specification for Instrument cables” , word “Telecommunication” deleted.
Section 1.3 References
Added references :
RLNG-000-TE-SP-0020 - Specification for Telecommunication Cables
RLNG-000-IC-PP-0001 - Instrument & Control System Numbering Procedure
Section 2.0
Changed Spec. reference in title:
AGES-SP-04-006 instead of AGES-SP-04-002
Section 10.4. Fire Resistant Characteristics
Cable Fire resistant test duration changed from 90 minutes to 120 minutes at 830°C temperature.
Amendment to AGES-SP-04-006
Section 11.1 Fiber Optic Cables
Minimum Fibre Count changed from 24 to 6
Added allowed quantity of Fibres (total for one cable) : 6, 12, 24, 36, 48, 72, 96, 144
Amendment to AGES-SP-04-006
APPENDIX 2 – Section A2.1 and Section A2.2
Sections substituted by cable code numbering table specified for RLNG Project.
Amendment to AGES-SP-04-006
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 4 OF 158
1.0
INTRODUCTION
The ADNOC Ruwais LNG Project is a two train, near net-zero electrically driven LNG facility, targeting international markets. The feed gas for the project is supplied from the Habshan Gas Processing Plant via a new export gas pipeline. The plant will have two 4.8 MTPA (nominal capacity) electric driven LNG Trains with associated LNG storage/marine export facilities and utilities.
Figure 1 – Project Context
The ADNOC Ruwais LNG Project foresees the following main components at the facility:
• Onshore LNG Liquefaction facilities for 2 x 4.8 MTPA electrically driven LNG Trains (9.6MTPA
total)
• Common facilities including inlet receiving facilities, LNG storage, BOG handling, flare,
refrigerant storage and support buildings.
• Utilities to support the facilities including import power from the national grid.
• Marine facilities for LNG export and bunkering.
1.1
Scope of the Document
The purpose of this document is to provide a Project specific addendum to the ADNOC Group Engineering Standard AGES-SP-04-006, Instrument and control cables Specification. This document provides an overview of Instrument & Telecommunication cables specification to be applied for the Project.
1.2
Holds List
HOLD
DESCRIPTION
1.3
References
[1] RLNG-000-PM-PP-2002 [2] RLNG-000-IC-SP-0701 [3] RLNG-000-TE-SP-0010 [4] RLNG-000-TE-SP-0020 [5] RLNG-000-IC-PP-0001
Project Basis of Design Specification for Instrument Installation & Design Telecommunications Systems Specification Specification for Telecommunication Cables Instrument & Control System Numbering Procedure
1.4
Definitions and Abbreviations
COMPANY
CONTRACTOR
EPC
ABU DHABI NATIONAL OIL COMPANY (ADNOC) P.J.S.C. TJN Ruwais, Joint Venture of Technip Energies France-Abu Dhabi, JGC Corporation and National Marines Dredging Company (NMDC) Engineering Procurement Construction
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 5 OF 158
ADOC POC YOC
Abu Dhabi Operating center - National Marines Dredging Company Paris Operating Center - Technip Energies Yokohama Operating center - JGC Corporation
2.0
AMENDMENTS TO ADNOC GENERAL ENGINEERING SPECIFICATION AGES-SP-04-006
The following specific amendments and additions shall apply to AGES-SP-04-006, Specification for Instrument Cables.
Instructions contained below such as “Add”, “Substitute”, “Revised”, or “New” shall be interpreted as follows:
• Add: Requirements shall be a continuation of the paragraph in the referenced specification.
• Substitute: The requirement of the referenced specification shall be replaced in its entirety by the
requirements below.
• Revised: The requirement of the referenced specification shall be revised by the specific wording
below.
• New: A new requirement as described below.
10
TECHNICAL REQUIREMENTS
10.2 Cable types and selection criteria
Substitute below chapter:
“(4) Multi-core cables: 2, 3, 4, 7, 11, 19, 27 and 37”
With following:
“(4) Multi-core cables: 2, 4, 10, 20 and 40.”
Substitute below table part:
Signal Type
Cable Type
Conductor Size (Note 1)
Digital Outputs to field devices
1, 2, 10 & 20 Pair
2.5 mm2
24 VDC for Solenoid Valves, Sounder,
Beacon etc.
With following:
Signal Type
Cable Type
Conductor Size (Note 1)
Digital Outputs to field devices
1, 2, 10 & 20 Pair
2.5 mm2
24 VDC for Solenoid Valves, Sounder,
or
Beacon etc.
2, 4, 10, 20 and 40 cores
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 6 OF 158
Substitute below table part:
“All instrument cables used for intrinsic safe I/O, vibration/frequency inputs, milli-volt signals, RTD signals, thermocouple signals, custody measurement signals etc shall be provided with individually and collectively screen with drain wire. All other instrument cables shall be provided with collective screen with drain wire.”
With following:
“All instrument cables used for intrinsic safe I/O, vibration/frequency inputs, milli-volt signals, RTD signals, thermocouple signals, custody measurement signals etc shall be provided with individually and collectively screen with drain wire. All other instrument cables (except core cable type) shall be provided with collective screen with drain wire.”
Substitute below table part:
Applications
Cable Type
Flame Retardant
Fire Resistant
Digital Outputs 24VDC – Solenoid, Beacons, Hooter Digital Outputs 24VDC – Solenoid, Beacons, Hooter
Single Pair Cables 1 Pair
Multi Pair Cables 2, 10 & 20 Pair
A1- Unarmoured A5 – Armoured A10- Armoured Buried A2 – Unarmoured A7 – Armoured A11- Armoured Buried
B1- Unarmoured B5 – Armoured B10- Armoured Buried B2 – Unarmoured B7 – Armoured B11- Armoured Buried
With following:
Applications
Cable Type
Flame Retardant
Fire Resistant
Digital Outputs 24VDC – Solenoid, Beacons, Hooter
Single Pair Cables 1 Pair or 2 cores
A1- Unarmoured A5 – Armoured A10- Armoured Buried G1- Unarmoured G2- Armoured G6 – Armoured
B1- Unarmoured B5 – Armoured B10- Armoured Buried H1 - Unarmoured H2 – Armoured H6 – Armoured
Digital Outputs 24VDC – Solenoid, Beacons, Hooter
Multi Pair Cables 2, 10 & 20 Pair
or
A2 – Unarmoured A7 – Armoured A11- Armoured Buried
B2 – Unarmoured B7 – Armoured B11- Armoured Buried
2, 4, 20 and 40 cores
G3 – Unarmoured G4 – Armoured G5 - Armoured Buried G7 – Armoured
H3- Unarmoured H4- Amoured H5 - Armoured Buried H7 – Armoured
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 7 OF 158
10.3.3 Core Identification
Substitute below table:
Type of Cables
Core 1
Core 2
Core 3
Core 4
Pair
Triad
Quad
With following:
Type of Cables
Pair
Triad
Quad
Black
Black
Black
Core 1 or (+)
Black
Black
Black
10.4. Fire Resistant Characteristics.
Substitute following sentence:
White
White
White
Core 2 or (-)
Red
White
Brown
Red
Red
Blue
Core 3
Core 4
Red
Red
Blue
Fire resistant cables shall pass the tests as defined in IEC 60331-1, 2 & 3. Fire resistant test and mechanical shock test shall be carried out simultaneously with the flame temperature of 830°C and application time of 90 minutes.
With below:
Fire resistant cables shall pass the tests as defined in IEC 60331-1, 2 & 3. Fire resistant test and mechanical shock test shall be carried out simultaneously with the flame temperature of 830°C and application time of 120 minutes.
10.5.2 Drum marking
Substitute article 1 with below:
“All cables shall be supplied and delivered in maximum manufacturing cable drums length, continuous lengths on non-returnable cable drums.”
with:
“All cables shall be supplied and delivered in specified cable drums length by Contractor, continuous lengths on non-returnable cable drums”.
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 8 OF 158
11
TECHNICAL REQUIREMENTS
11.1
Fiber Optic Cables
Substitute below table part:
Sr.No.
Description
Multimode step Index/ Multimode Graded Index
Single Mode Fibre
5
Minimum Fibre Count
24
With following:
Sr.No.
Description
Multimode step Index/ Multimode Graded Index
Single Mode Fibre
5
Minimum Fibre Count
6
Substitute following sentence under aforementioned table :
A minimum of 2 x 24 core Single Mode FO Cable shall be provided for each system, unless otherwise specified by the project requirement.
With below:
Allowed quantity of Fiber cores (total for one cable) : 6, 12, 24, 36, 48, 72, 96, 144
21.2 Deliverables
Add below sentence
“e) Preservation and Installation manual”
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 9 OF 158
APPENDIX 2 - CABLE DESIGNATION
Substitute section A2.1 and A2.2 with below cable code numbering:
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
Specification for Instrumentation Cables
COMPANY DOCUMENT REF. RLNG-000-IC-SP-0741
CONTRACTOR DOC. REF.
215122C-000-JSS-1574-0001
REVISION: 1
PAGE 10 OF 158
SECTION D
A2.7 FIRE RESISTANT CABLE FOR OUTDOOR ABOVE GROUND INSTALLATION
Substitute bullet 6) With below :
“Number of Cores : 4C, 10C, 20C, 40C”
APPENDIX 3 - CONSTRUCTION DETAILS FOR EACH CABLE TYPE
Substitute requirement for “identification” For G3, G4, G5, G7, H3, H4, H5 and H7
With:
“Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 4C, 10C, 20C, 40C Each core printed with a number throughout the cable at equal (150mm) distances.”
3.0
APPENDIX
3.1
APPENDIX 1 - AGES-SP-04-006
The ADNOC Group Engineering Standard AGES-SP-04-006, Specification for Instrument Cables is attached below for reference
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
THE CONTENTS OF THIS DOCUMENT ARE PROPRIETARY AND CONFIDENTIAL.
ADNOC GROUP PROJECTS AND ENGINEERING
INSTRUMENT AND CONTROL CABLES SPECIFICATION
Specification
APPROVED BY:
Abdulmunim Saif Al Kindy
NAME: Abdulmunim Al Kindy TITLE: Executive Director PT&CS EFFECTIVE DATE:
AGES-SP-04-006
GROUP PROJECTS & ENGINEERING / PT&CS DIRECTORATE
CUSTODIAN ADNOC
Group Projects & Engineering / PT&CS Specification applicable to ADNOC & ADNOC Group Companies
REVISION HISTORY
DATE
REV.
NO
1 June 2020
1
PREPARED BY (Designation / Initial) Asadullah Malik / Sr. Engineer, I&C, TE.
REVIEWED BY (Designation / Initial) Ashwani Kumar Kataria/ A/MES,TC- Eng
ENDORSED BY (Designation / Initial) Abdulla Al Shaiba/
ENDORSED BY (Designation / Initial) Zaher Salem/
VP-GPE
SVP-GPE
Reuben Yagambaram/ SPM-GPE
Group Projects & Engineering is the owner of this Specification and responsible for its custody, maintenance and periodic update.
In addition, Group Projects & Engineering is responsible for communication and distribution of any changes to this Specification and its version control.
This specification will be reviewed and updated in case of any changes affecting the activities described in this document.
Document No: AGES-SP-04-006
Rev. No: 1 Page 2 of 148
INTER-RELATIONSHIPS AND STAKEHOLDERS
a) The following are inter-relationships for implementation of this Specification:
i.
ii.
ADNOC Upstream and ADNOC Downstream Directorates and
ADNOC Onshore, ADNOC Offshore, ADNOC Sour Gas, ADNOG Gas Processing. ADNOC LNG, ADNOC Refining, ADNOC Fertilisers, Borouge, Al Dhafra Petroleum, Al Yasat
b) The following are stakeholders for the purpose of this Specification:
ADNOC PT&CS Directorate.
c) This Specification has been approved by the ADNOC PT&CS is to be implemented by each ADNOC Group company included above subject to and in accordance with their Delegation of Authority and other governance-related processes in order to ensure compliance
d) Each ADNOC Group company must establish/nominate a Technical Authority responsible for compliance with
this Specification.
DEFINED TERMS / ABBREVIATIONS / REFERENCES
“ADNOC” means Abu Dhabi National Oil Company.
“ADNOC Group” means ADNOC together with each company in which ADNOC, directly or indirectly, controls fifty percent (50%) or more of the share capital.
“Approving Authority” means the decision-making body or employee with the required authority to approve Policies & Procedures or any changes to it.
“Business Line Directorates” or “BLD” means a directorate of ADNOC which is responsible for one or more Group Companies reporting to, or operating within the same line of business as, such directorate.
“Business Support Directorates and Functions” or “Non- BLD” means all the ADNOC functions and the remaining directorates, which are not ADNOC Business Line Directorates.
“CEO” means chief executive officer.
“Group Company” means any company within the ADNOC Group other than ADNOC.
“Specification” means this Instrument and Control Cables Specification.
CONTROLLED INTRANET COPY
The intranet copy of this document located in the section under Group Policies on One ADNOC is the only controlled document. Copies or extracts of this document, which have been downloaded from the intranet, are uncontrolled copies and cannot be guaranteed to be the latest version.
Document No: AGES-SP-04-006
Rev. No: 1 Page 3 of 148
TABLE OF CONTENTS
THE CONTENTS OF THIS DOCUMENT ARE PROPRIETARY AND CONFIDENTIAL. … 1
GENERAL … 6
1
2
3
PURPOSE … 6
SCOPE … 6
DEFINED TERMS / ABBREVIATIONS / REFERENCES … 7
SECTION A … 10
4
NORMATIVE REFERENCES … 10
INTERNATIONAL CODE(S) AND STANDARDS … 10
5
REFERENCE DOCUMENTS … 15
STANDARD DRAWINGS … 15
OTHER REFERENCES … 15
6
7
8
9
DOCUMENTS PRECEDENCE … 15
SPECIFICATION DEVIATION/CONCESSION CONTROL … 15
PROCESS SAFETY REQUIREMENTS … 16
DESIGN CONSIDERATIONS / MINIMUM DESIGN REQUIREMENTS … 17
OPERATION & DESIGN LIFE … 17
ENVIRONMENTAL REQUIREMENTS … 17
HAZARDOUS AREA PROTECTION … 17
ENGINEERING UNITS … 17
SECTION B … 18
10
TECHNICAL REQUIREMENTS … 18
GENERAL … 18
CABLE TYPES AND SELECTION CRITERIA … 19
CABLE CONSTRUCTION … 21
CABLE PERFORMANCE REQUIREMENTS … 25
MARKING AND TRACEABILITY REQUIREMENTS … 26
11
SPECIAL CABLES … 29
FIBRE OPTIC CABLES … 29
DIRECT BURIAL FIBRE-OPTIC CABLES … 30
SECTION C … 32
12
SCOPE OF SUPPLY … 32
Document No: AGES-SP-04-006
Rev. No: 1 Page 4 of 148
13 QUALITY CONTROL AND ASSURANCE … 32
14 MATERIAL CERTIFICATION … 32
15
INSPECTION & TESTING REQUIREMENTS … 33
INSTRUMENT AND CONTROL CABLES … 33
FIBRE OPTIC CABLES … 35
16
17
18
SUBCONTRACTORS/SUBVENDORS … 36
SPARE PARTS … 36
PACKING, PRESERVATION & SHIPMENT … 36
PACKING AND SHIPPING … 36
PRESERVATION AND STORAGE … 36
19 COMMISSIONING … 37
20
TRAINING … 37
21 DOCUMENTATION/MANUFACTURER DATA RECORDS … 37
GENERAL … 37
DELIVERABLES … 38
22 GUARANTEES & WARRANTY … 38
SECTION D … 39
23 DATA SHEETS … 39
24
STANDARD DRAWINGS … 39
APPENDICES… 40
APPENDIX 1 CABLE DATA SHEETS … 40
APPENDIX 2 CABLE DESIGNATION … 47
APPENDIX 3 CONSTRUCTION DETAILS FOR EACH CABLE TYPE … 58
Document No: AGES-SP-04-006
Rev. No: 1 Page 5 of 148
GENERAL
1 PURPOSE
The purpose of this specification is to define the minimum mandatory technical requirements for design, procurement, manufacturing, installation, testing and packing of Instrument and Control cables.
2 SCOPE
2.1 The scope of this specification is limited to following types of Instrumentation and Control Cables:
- Analogue and Digital Signal Cables
- Thermocouple Extension Cables
- Foundation Fieldbus Cables
- Communication cables (such as RS-232, RS485, Ethernet etc.)
- Optical fibre cables.
2.2 This specification excludes following types of cables:
- Telecommunication cables.
- Co-axial cables.
- 230V AC Power Cables for powering Instruments and Control Equipment
- Earthing Cables
- Submarine Cables
- Proprietary Control System’s cables supplied by ICSS and Mechanical Package Vendors.
2.3 For project specific additional requirements, refer to instrumentation cable requirements stated in
respective project’s Purchase Requisition documentation.
Document No: AGES-SP-04-006
Rev. No: 1 Page 6 of 148
3 DEFINED TERMS / ABBREVIATIONS / REFERENCES
Abbreviations
AL/HDPE/PA
Aluminium / High Density Polyethylene / Polyamide (Nylon)
CSA
EPR
ESD
FAT
FF
FGS
FO
GSWA
GSWB
HOFR
I/O
I.S.
LSZH
Cross Sectional Area
Ethylene Propylene Rubber
Emergency Shutdown System
Factory Acceptance Test
Foundation Fieldbus
Fire and Gas System
Fibre Optic
Galvanised Steel Wire Armour
Galvanised Steel Wire Braid
Heat, Oil and Flame Retardant
Inputs/Outputs
Intrinsically Safe
Low Smoke Zero Halogen
MGT/EPR
Mica Glass Tape Ethylene Propylene Rubber
MGT/XLPE
Mica Glass Tape Cross Linked Polyethylene
PA
PTFE
S95
XLPE
Public Address System
Poly Tetra Fluoro Ethylene
Silicone Rubber
Cross Linked Polyethylene
Document No: AGES-SP-04-006
Rev. No: 1 Page 7 of 148
Technical Definitions
Term
Definition
Armour
Bedding
Metallic wire mesh covering for protection against mechanical damage during cable installation and operation.
Non-metallic layer applied between Armour and Lead Sheath to maintain electric isolation between metallic layers.
Buried
Cables that are required to go underground or laid underground.
Conductor
Metal used to transfer electrical energy from point to point.
Drain wire
Un-insulated wire laid in contact with an electrical screen or an electrical shield which has the specific function of earthing an electrostatic charge by ensuring a low resistive path throughout the length of the cable
Fibre Optics
A technology that transmits information as light pulses along a glass or plastic fibre.
Fillers
Non-conducting components cabled with the insulated conductors or optical fibres to impart roundness, flexibility, tensile strength or a combination of all three to the cable.
Fire Resistance
Ability of an electric cable to continue to operate in a designated manner whilst subjected to a specified flame source for a specified period under specified conditions.
Flame Resistance
The ability of a material not to fuel a flame once the source of heat is removed.
Inner Sheath
Non-metallic cover generally applied under a metallic sheath or armour.
Insulation
Non-conducting electrical isolation material between conductors
Laying Up
Outer Sheath
The cores of cables are laid up with suitable filling elements to form a compact circular assembly. Suitable binder tape(s) may be applied.
Non-metallic cover applied over armour ensuring the protection of the cable from the outside atmosphere.
Quad
A four conductor cable.
Screen/Shield
Earthed metallic layer surrounding a cable which confines the electric field generated by the cable within the cable cores, pair(s), triples(s) or quad(s),
Document No: AGES-SP-04-006
Rev. No: 1 Page 8 of 148
and/or protects the core(s), pair(s), triple(s) or quad(s) from external influence.
Stranded conductor
Conductor consisting of a number of individual wires all which generally have a helical form.
References
ADNOC Group Companies Instrument and Control Cable requirements documents part of Cable
Purchase Order shall be referred for design and supply of equipment.
Document No: AGES-SP-04-006
Rev. No: 1 Page 9 of 148
SECTION A
4 NORMATIVE REFERENCES
International Code(s) and Standards
The following codes and standards, to the extent specified herein, form a part of this specification. When an edition date is not indicated for a code or standard, the latest edition in force at the time of order placement shall apply.
Standard
Description
The International Electrotechnical Commission (IEC)
IEC 60079
IEC 60092
IEC 60092-350
IEC 60092 -352
IEC 60092-360
IEC 60092-376
Explosive Atmospheres. All parts.
Electrical installations in ships, covers power and instrumentation cables to be used on ships and in mobile marine environments.
General construction and test methods of power, control and instrumentation cables for shipboard and offshore applications.
Electrical installations in ships: Choice and installation of electrical cables.
Electrical, mechanical and particular characteristics of insulation and sheathing materials for shipboard and offshore units, power, control, instrumentation and telecommunications cables.
Screened and unscreened cables for control and instrumentation circuits on ships and fixed/mobile offshore units. These cables have extruded solid insulation with a voltage rating of 150/250V.
IEC 60228
Conductors of Insulated cables.
IEC 60304
Standard colours for insulation for low-frequency cables and wires.
IEC 60331
IEC 60332
Tests for Electric Cables under Fire Conditions - Circuit integrity. All series, all parts.
Tests on electric and optical fibre cables under fire conditions. All series, all parts.
IEC 60529
Degrees of protection provided by enclosures (IP Code).
IEC 60584
Thermocouples. All parts.
IEC 60684-2
Flexible Insulating Sleeving Method of Test
Document No: AGES-SP-04-006
Rev. No: 1 Page 10 of 148
IEC 60754
Tests on Gases Evolved during Combustion of Materials from Cables. All parts.
IEC 61784
Industrial communication networks – Fieldbus Profiles. All parts.
IEC 60793
IEC 60794
IEC 60811
IEC 61034
Optical fibres: Measurement methods and test procedures. All parts.
Optical fibre cables: Generic specification. All parts.
Electrical and Optical Fibre Cables - Test Methods for Non-metallic material. All parts.
Measurement of smoke density of cables burning under defined conditions. All parts.
IEC 61158-SER
Digital data communications for measurement and control - Fieldbus for use in industrial control systems – All parts.
IEC 61158-1
IEC 61158-2
Industrial Communication Networks - Fieldbus specifications - Part 1: Overview and guidance for the IEC 61158 and IEC 61784 series.
Industrial Communication Networks - Fieldbus specifications - Part2: Physical Layer Specification and Service Definition.
FF-844 H1
Foundation Fieldbus Type A H1 Cable Test Specification
IEC 61280
IEC 61281-1
Fibre optic communication subsystem basic test procedures. All parts.
Fibre optic communication subsystems. Generic specification.
IEC TR 61282
Fibre optic communication system design guide.
IEC 61315
IEC 62033
IEC TR 62221
Calibration of fibre optic power meters.
Attenuation uniformity in optical fibres.
Optical fibres - Measurement methods - Microbending sensitivity.
IEC TR 62222
Fire performance of communication cables installed in buildings.
IEC TR 63194
Guidance on colour coding of optical fibre cables.
British Standards Institution (BSI)
BS 6004
Electric cables. PVC insulated and PVC sheathed cables for voltages up to and including 300/500 V, for electric power and lighting.
Document No: AGES-SP-04-006
Rev. No: 1 Page 11 of 148
BS 6387
BS 6701
BS 6883
BS 7655
BS 7917
Test method for resistance to fire of cables required to maintain circuit integrity under fire conditions.
Telecommunication equipment and cabling.
Elastomer insulated cables for fixed wiring in ships and on mobile and fixed offshore units. Requirements and test methods.
Specification for insulating and sheathing materials for cables. All parts.
Elastomer insulated fire resistant (limited circuit integrity) cables for fixed wiring in ships and on mobile and fixed offshore units. Requirements and test methods.
European Standards (EN)
EN 10204
Metallic products. Types of inspection documents.
EN 10218
EN 10244-2
EN 10257-1
EN 12548
EN 50173
EN 50200
EN 50288
Steel wire and wire products. General. All parts.
Steel wire and wire products. Non-ferrous metallic coatings on steel wire. Zinc or zinc alloy coatings.
Zinc or zinc alloy coated non-alloy steel wire for armouring either power cables or telecommunication cables. Land cables.
Lead and alloys. Lead alloy ingots for electric cable sheathing and for sleeves.
Information Technology – Generic Cabling Systems.
Method of test for resistance to fire of unprotected small cables for use in Emergency Circuits.
Multi-element metallic cables used in analogue and digital communication and control.
EN 50288-1
Part1: Generic specification.
EN 50288-7
Part7: Sectional specification for instrumentation and control cables.
EN 50289
EN 50290
EN 50290-4
Communication cables. Specifications for test methods. Electrical test methods. General requirements, all series and all parts.
Communication cables. Common design rules and construction. All parts.
Communication cables. General considerations for the use of cables - Guide to use.
EN 50307
Lead and lead alloys. Lead and lead alloy sheaths and sleeves of electric cables.
American Society for Testing and Materials (ASTM) International
Document No: AGES-SP-04-006
Rev. No: 1 Page 12 of 148
ASTM B3-13
Standard Specification for Soft or Annealed Copper Wire.
ASTM B33-10
Standard Specification for Tin-Coated Soft or Annealed Copper Wire for Electrical Purposes.
ASTM D2863-19
Standard Test Method for Measuring the Minimum Oxygen Concentration to Support Candle-Like Combustion of Plastics (Oxygen Index).
Underwriters Laboratories (UL)
UL1581
Reference Standard for Electrical Wires, Cables, and Flexible Cords.
The Institute of Electrical and Electronics Engineers, Inc. (IEEE)
IEEE-802
Standard for local and metropolitan area networks: Overview and architecture - IEEE Computer Society Document.
Engineering Equipment Materials Users Association (EEMUA)
EEMUA 133
Specification for underground armoured cable protected against solvent penetration and corrosive attack.
Electronic Industries Association (EIA)
EIA TIA-455
Standard Test Procedure for Fibre Optic Fibres, Cables, Transducers, Sensors, Connecting and Terminating Devices, and Other Fibre Optic Components.
EIA TIA-492 AAA-A
Detail Specification for 62.5-Micrometer Core Diameter/125-Micrometer Cladding Diameter Class Ia Graded-Index Multimode Optical Fibres.
EIA TIA-492AAA
Detail Specification for Class IVa Dispersion -Unshifted Single-Mode Optical Fibres.
EIA TIA-598
Optical Fibre Colour Coding
International Telecommunications Union (ITU)
ITU-T G650
ITU-T G651
ITU-T G-652
Definition and test methods for the relevant parameters of single mode fibres – Series G.
Characteristics of a 50/125 micrometer multimode graded index optical fibre cable – Series G.
Characteristics of a Single-Mode Optical Fibre Cable Series G: Transmission Systems and Media, Digital Systems and Networks Transmission Media Characteristics - Optical Fibre Cables.
International Organization for Standardization (ISO)
Document No: AGES-SP-04-006
Rev. No: 1 Page 13 of 148
ISO 4589-2
Plastics. Determination of burning behaviour by oxygen index. Ambient- temperature test.
ISO 9001
Quality Management Systems - Requirements.
ISO 9004
Managing for the Sustained Success of an Organization – A Quality Management Approach
ISO 19011
Guidelines for Auditing Management Systems
Document No: AGES-SP-04-006
Rev. No: 1 Page 14 of 148
5 REFERENCE DOCUMENTS
Standard Drawings
Not applicable.
Other References
This specification shall be read in conjunction with respective project specific Cable Purchase Order and its referenced documents and Cable Data Sheets which fully defines project specific requirements.
6 DOCUMENTS PRECEDENCE
The Codes and Standards referred to in this specification shall, unless stated otherwise, be the latest approved issue at the time of Purchase Order placement.
It shall be the VENDOR’S and CONTRACTORS’S responsibility to be, or to become, knowledgeable of the requirements of the referenced Codes and Standards.
The VENDOR/CONTRACTOR shall notify the COMPANY of any apparent conflict between this specification, the related data sheets, the Codes and Standards and any other specifications noted herein.
Resolution and/or interpretation precedence shall be obtained from the COMPANY in writing before proceeding with the design/manufacture.
In case of conflict, the order of document precedence shall be:
- UAE Statutory requirements
- ADNOC Codes of Practice
- Equipment datasheets and drawings
- Project Specifications and standard drawings
- Company Specifications
- National/International Standards
7 SPECIFICATION DEVIATION/CONCESSION CONTROL
Deviations from this specification are only acceptable where the VENDOR has listed in his quotation the requirements he cannot, or does not wish to comply with, and the COMPANY/CONTRACTOR has accepted in writing the deviations before the order is placed.
In the absence of a list of deviations, it will be assumed that the VENDOR complies fully with this specification.
Any technical deviations to the Purchase Order and its attachments including, but not limited to, the Data Sheets and Narrative Specifications shall be sought by the VENDOR only through Concession Request Format. Concession requests require CONTRACTOR’S and COMPANY’S review/approval, prior to the proposed technical changes being implemented. Technical changes implemented prior to COMPANY approval are subject to rejection.
Document No: AGES-SP-04-006
Rev. No: 1 Page 15 of 148
8 PROCESS SAFETY REQUIREMENTS
Sr.No.
Description
1
2
Instrumentation Cables used for ESD and FGS applications and HSE Critical services shall be Fire Resistance in accordance with IEC 60331.
Instrumentation cables used for intrinsic safe applications shall be individually and overall shielded as per IEC 60079-14 Clause 16.2.2.8.
Document No: AGES-SP-04-006
Rev. No: 1 Page 16 of 148
9 DESIGN CONSIDERATIONS / MINIMUM DESIGN REQUIREMENTS
Operation & Design Life
All Instrument and Control cables shall be suitable for continuous operation of 30 years under the environmental conditions at ADNOC facilities.
Environmental Requirements
Refer to Engineering Design Basis of ADNOC Group Company for respective Onshore or Offshore project environmental conditions. conditions. All cables shall be suitably designed for permanent operation under the prevailing environmental conditions specified in purchase order data sheets.
In general, the environment for outdoor installations shall be considered as high temperatures, high humidity, salty, sulphurous, dusty and corrosive. Cables shall be suitable for installation and operation over the full range of ambient temperature and humidity specified in the data sheets and in an environment containing trace amount of H2S, CO2 (sour & corrosive atmosphere) and HC gases.
Cables exposed to direct sunlight (outdoor above ground) shall be manufactured using the best suitable UV stabilizers which enables the long life without stress cracking suited to Middle East Environment Conditions. Cables resistance to UV shall meet requirements of UL 1581 art. 1200.
All indoor systems shall continue to operate in HVAC upset conditions during which the temperature can fall to 0ºC or rise to 60ºC, and the humidity can vary between 5% and 95% non-condensing.
All cables installed indoors shall have Low Smoke Zero Halogen (LSZH) sheath material.
Hazardous Area Protection
Unless otherwise specified, outdoor areas inside process plants shall be considered as hazardous. All cables laid outdoor shall be suitable for hazardous area specified in cable data sheet and shall comply with IEC 60079-11 & 25 requirements.
Engineering Units
Reference shall be made to Project Engineering Design basis for Units of Measurements.
Document No: AGES-SP-04-006
Rev. No: 1 Page 17 of 148
SECTION B
10 TECHNICAL REQUIREMENTS
General
The Instrument and Control cables shall be suitable for process facilities situated at onshore desert and offshore marine locations, operating at high ambient temperatures and H2S/CO2 sour gas corrosive environments.
Cables shall be suitable to install for following laying arrangements:
(a) Outdoor directly buried in the ground
(b) Outdoor concrete trenches with soil backfill
(c) Outdoor on cable trays in the open air exposed to direct sunlight
(d)
Inside building in cable trays, conduits and ducts
All cables shall be heat, oil, soil & UV resistant; non-hygroscopic and gas & vapor tight.
All cables shall be Flame Retardant and comply with IEC 60332-1-1&2 and IEC 60332-3-22, Category A as a minimum.
All cables used for ESD, FGS and safety functions shall be Fire Resistant and comply with IEC 60331-21 .
Onshore and Offshore, Instrument and Control Cables shall be rated for 300/500V i.e. 300 V r.m.s. core to earth and 500 V r.m.s. core to core.
Temperature rating of all cables shall be 90°C under normal operating conditions. For temperature above 90°C, cables shall be customised based on application and intended high temperature requirements.
The Thermocouple extension and compensating cables design shall comply to IEC 60584-3.
The Foundation Fieldbus cables design shall be comply to IEC 61158-2 Type A cables.
All outdoor cables buried in ground, laid in trenches or above ground in cable trays shall be armoured. All cables installed in the plant field areas and all cable runs from the plant areas to the cabinets located inside Instrument Equipment Room shall be considered as outdoor cables.
Indoor cables which are laid within the building between marshalling, system and other panels, should be unarmoured, shall have Low Smoke Zero Halogen (LSZH) sheaths and shall be suitable for installation within cable containment systems like cable trays or ducts. Unarmoured cables shall not be used for outdoor above ground or underground installations.
Mud resistant cables shall be considered for the entire wellhead platform at Offshore and Well pad area.
Document No: AGES-SP-04-006
Rev. No: 1 Page 18 of 148
Cable Types and Selection Criteria
Following types of cables shall be provided based on service and installation requirements:
(1)
Flame Retardant Cables and Fire Resistant Cables
(2) Underground and Above Ground Cables
(3) Armour and Unarmoured Cables
(4)
Intrinsic Safe and Non-intrinsic Safe Cables
(5) Signal Cables (for 4-20 mA, Digital, Frequency, RTD, T/C, FF etc signals)
(6) Control Cables (for solenoid valves, beacons, hooter etc)
(7) Serial Communication Cables
(8)
Fibre Optic Cables
To standardise cable construction, following number cores, pairs, triads and quads shall be used:
(1) Pair cables:
1P, 2P, 10P and 20P.
(2)
Triad cables:
1T, 2T, 10T and 20T
(3) Quad cables:
1Q, 2Q and 10Q,
(4) Multi-core cables: 2, 3, 4, 7, 11, 19, 27 and 37
The selection of cable type and minimum conductor size for various signal types shall be as follows:
Signal Type
Cable Type
Conductor Size (Note 1)
Analogue 4-20 mA, Frequency, Foundation Fieldbus
Digital Inputs- 24 VDC Potential Free contact, Proximity Namur, MCC/Switchgear contacts (Note 2)
Thermocouple inputs
1, 2, 10 & 20 Pair
1 Pair - 1.5 mm2 2, 10 & 20 Pair – 1 mm2
RTD inputs, 3 Wire Transducers, F & G Detectors
1, 2, 10 & 20 Triad 1, 2 & 10 Quad
1 Triad/Quad - 1.5 mm2 2, 10 & 20 Triad/Quad- 1 mm2 or 1.5 mm2 based on voltage drop requirements
Digital Outputs to field devices 24 VDC for Solenoid Valves, Sounder, Beacon etc.
1, 2, 10 & 20 Pair
2.5 mm2
Serial Communication RS485/232/422
1, 2 Pair
1.5 mm2
Document No: AGES-SP-04-006
Rev. No: 1 Page 19 of 148
Note 1: The conductor sizes mentioned above are the minimum requirements. CONTRACTOR shall verify conductor sizes based on cable length, voltage drop and power consumption requirements of instruments.
Note 2: CONTRACTOR shall ensure that signals to/from MCC/Switchgear are isolated from high voltage and their voltage levels are not greater than 24 VDC.
All instrument cables used for intrinsic safe I/O, vibration/frequency inputs, milli-volt signals, RTD signals, thermocouple signals, custody measurement signals etc shall be provided with individually and collectively screen with drain wire. All other instrument cables shall be provided with collective screen with drain wire.
Refer to Appendix 3 for construction details of various Cable Types. Summary of Cable types is as follows:
Applications
Cable Type
Cable Type Reference (A1, B5, C6)
Flame Retardant
Fire Resistant
2 Wire Signals- Analogue, Digital, Pulse, Voltage
2 Wire Signals- Analogue, Digital, Pulse, Voltage
Single Pair Cables 1 Pair
A1- Unarmoured A5 – Armoured A10- Armoured Buried
B1- Unarmoured B5 – Armoured B10- Armoured Buried
Multi Pair Cables 2, 10 & 20 Pair
A2 – Unarmoured A6, A7 – Armoured A11- Armoured Buried
B2 – Unarmoured B6, B7 – Armoured B11- Armoured Buried
3 Wire Signals- RTD, FGS
Single Triad Cables 1 Triad
3 Wire Signals- RTD, FGS
Multi Triad Cables 2, 10, 20 Triad
A3 – Unarmoured A8 – Armoured A12- Armoured Buried
B3 – Unarmoured B8 – Armoured B12- Armoured Buried
A4 – Unarmoured A9 – Armoured A13 – Armoured Buried
B4 – Unarmoured B9, B14 – Armoured B13, B15 – Armoured Buried
Thermocouple Signals
Single Pair T/C Cable 1 Pair
C1, C2, C3 – Unarmoured C4, C5, C6 - Armoured
D1, D2, D3 – Unarmoured D4, D5, D6 - Armoured
Thermocouple Signals
Multi Pair T/C Cable 2, 10, 20 Pair
C7, C8, C9 – Armoured C10, C11, C12 Armoured Buried
D7, D8, D9 – Armoured D10, D11, D12 Armoured Buried
Foundation Fieldbus, RS 485
Single Pair Cables 1 Pair
Foundation Fieldbus, RS 485
Multi Pair Cables 2, 10 & 20 Pair
E1 – Unarmoured E3 – Armoured E5 – Armoured Buried
F1 – Unarmoured F3 – Armoured F5 – Armoured Buried
E2 – Unarmoured E4 – Armoured E6 – Armoured Buried
F2 – Unarmoured F4 – Armoured F6 – Armoured Buried
Document No: AGES-SP-04-006
Rev. No: 1 Page 20 of 148
Applications
Cable Type
Cable Type Reference (A1, B5, C6)
Flame Retardant
Fire Resistant
Communication Cables 4 Wire
Multi Pair Cable 2 Pair
E7 – Unarmoured E8 - Armoured
E7 – Unarmoured E8 - Armoured
Digital Outputs 24VDC – Solenoid, Beacons, Hooter
Single Pair Cables 1 Pair
A1- Unarmoured A5 – Armoured A10- Armoured Buried
B1- Unarmoured B5 – Armoured B10- Armoured Buried
Digital Outputs 24VDC – Solenoid, Beacons, Hooter
Multi Pair Cables 2, 10 & 20 Pair
A2 – Unarmoured A7 – Armoured A11- Armoured Buried
B2 – Unarmoured B7 – Armoured B11- Armoured Buried
Fibre Optic cables Unarmoured
24 fibre, multi-loose tube, single jacket
I1
J1
Fibre Optic cables Armoured
24 fibre, multi-loose tube, double jacket 24 fibre, multi-loose tube, armoured
I2, I3, I4,I5
J2, J3, J4
Cable Construction
Onshore Instrument and Control cable design and construction shall comply with BS EN 50288.
Offshore Instrument and Control cables design and construction shall comply with IEC 60092, BS 6883 and BS 7917.
Refer to Appendix 3 for construction details of each cable type.
10.3.1 Conductors
Conductors, with exception of thermocouple extension and compensating cables, shall be circular and multi-stranded tinned annealed copper wires conforming to IEC60228, Class 2.
Conductors for thermocouple extension and compensating cables shall be solid annealed type (Class 1), material and construction in accordance with IEC 60584-3.
10.3.2 Core Insulation Material
For temperature ratings up to 90°C the cable core insulation material shall be Halogen Free Ethylene Propylene Rubber (EPR) or Cross-Linked Polyethylene (XLPE). For Fire Resistant cables, insulation shall be Halogen Free Ethylene Propylene Rubber with Mica Glass Tape (MGT EPR) or Cross-Linked Polyethylene with Mica Glass Tape (MGT XLPE).
For operating temperature up to 180°C, the Halogen Free Silicone (S95) or equivalent insulation and sheath material cables shall be used. For operating temperature up to 250°C, the insulation material PTFE
Document No: AGES-SP-04-006
Rev. No: 1 Page 21 of 148
or Mica glass with glass fibre braid shall be used. To enhance the heat resistance capacity of the cables suitably treated glass fibre braid shall be applied over insulation and sheath material.
Core insulation shall be extrusion type and shall be applied closely to the conductor. It shall be possible to remove the insulation without damaging the conductor or its metal coating. The average thickness of insulation shall not be less than 0.7 mm. This thickness does not include any separator or organic tape(s) (MGT and/or glass fibre braid) applied over the conductor.
10.3.3 Core Identification
Instrument signal and control cables cores shall be identified by insulation colour as follows:
Type of Cables
Core 1
Core 2
Core 3
Core 4
Pair
Triad
Quad
Black
Black
Black
White
White
White
Red
Red
Blue
For the multi-pair/ triad / quad cables, the pair / triad / quad numbers shall be additionally printed on the insulation of each core.
For multi-core cables containing more than four cores, the cores shall be numbered sequentially, starting with number one (1) printed in a colour contrasting with that of the insulation.
Thermocouple extension/compensation cables cores shall be identified by insulation colour as per IEC 60584-3 as follows:
Description
Thermocouple Type - B
Thermocouple Type – E
Thermocouple Type – J
Thermocouple Type – K
Thermocouple Type – N
Thermocouple Type – R or Type - S
Thermocouple Type - T
Colour
(+) Grey, (-) White
(+) Violet, (-) White
(+) Black, (-) White
(+) Green, (-) White
(+) Pink, (-) White
(+) Orange, (-) White
(+) Brown, (-) White
Multi-pair thermocouple cables shall be identified by having the same ‘pair’ number printed in a contrasting colour on the insulation of each core.
10.3.4 Pair / Triad / Quad formation
Twisted pair/triad/quad cables shall be used for transmission of all instrumentation signals. For Pair / Triad / Quad formation, the cores shall be twisted together in concentric layers with either left hand or right hand lay to form a pair, triad or quad cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 22 of 148
The lay length of a pair, triad or quad shall not exceed 100 mm for conductor size up to 1.5 mm2 nor 150 mm for conductor size 2.5 mm2.
A non-hygroscopic binder tape(s) shall be helically applied (providing 100% coverage with 25% overlap) over each pair, triad or quad.
For cables with individual screens, each pair / triad / quad shall be provided with a laminated electrostatic screening tape applied with the metallic side in electrical contact with a drain wire.
The drain wire shall be 0.5 mm² size minimum and constructed with stranded tinned annealed copper material. Screen shall provide 100% coverage with minimum overlap of 25% of its width.
The laminated electrostatic screening tape shall be of aluminium material bonded to polyester (Mylar Tape) having a minimum thickness of aluminium of 0.008 mm and a minimum thickness of polyester of 0.010 mm.
The individual screens shall be electrically isolated both from each pair / triad / quad and also electrically isolated from the overall screen.
A polyester tape of 0.050 mm nominal thickness shall be applied over the screen with a minimum overlap 20% of its total width, in order for the screen to be insulated from the remaining cable components.
The multi-pairs / triads / quads of the cables shall be assembled in concentric layers using either an uni- directional or reverse lay. Cable fillers shall be solid, non-hygroscopic. They shall fill the cross section such that the transmission of gas and hydrocarbons along the length of the cable, under normal pressure, is not possible.
The overall screen of the cable shall be provided with drain wire and the construction of overall screen shall be similar to the individual screen.
Overall binder tape(s), non-hygroscopic, shall be helically applied similar to individual binder (providing 100% coverage with 25% overlap) over the multi-pair / triad / quad.
10.3.5 Inner Sheath
Inner sheath material shall be Low Smoke Zero Halogen Flame Retardant Compound. Inner sheath shall be suitable for specified service, operating temperatures, site conditions and cable design standard indicated in cable data sheets. Inner sheath shall be extrusion type.
10.3.6 Lead Sheath / Multi-layer Sheath
The lead sheath or multilayer sheath shall provide a barrier against moisture, chemicals, water, solvents, environment and hydrocarbon oil attacks.
All onshore underground buried cables shall be provided with Lead Sheath as a moisture and chemical barrier in accordance with BS EN 50288 and shall comply to EEMUA 133 for lead quality. Alternatively, Aluminum/high density polyethylene/polyamide (AL/HDPE/PA) multi-layer inner sheath can be acceptable subject to COMPANY prior approval. VENDOR shall provide ‘Type Test’ certificates, from a test house acceptable to COMPANY, for AL/HDPE/PA multi-layer inner sheath cables to validate degree of ingress protection against water, organic and non-organic chemicals.
10.3.7 Bedding Layer
The bedding layer shall be provided between lead sheath and armour for underground cables.
The material of construction for the bedding layer shall be same as that of the inner sheath material.
10.3.8 Steel Wire Armour
Armored cable shall have Galvanized Steel Wire Armour under outer sheath.
Document No: AGES-SP-04-006
Rev. No: 1 Page 23 of 148
The galvanized steel wire armour shall comply to requirements of EN 10257-1 and, EN 10218-1.
The coating of steel wire shall comply with the requirements of EN 10244-2.
10.3.9 Outer Sheath
Outer sheath material shall be minimum PVC or better and comply with this specification requirements. Outer sheath shall be Low Smoke Zero Halogen Flame Retardant Compound. Outer sheath shall be suitable for specified service, operating temperature, site conditions and cable design standard indicated in cable data sheets. Outer sheath shall be extrusion type.
Outer sheath shall be anti-vermin impregnated and UV-resistant. Outer sheath shall be heat, oil and flame retardant (HOFR).
Outer sheath material shall be minimum PVC or better and comply with this specification requirements.
The colour of outer sheath shall be as follows:
Description
Outer Sheath Colour
Intrinsically safe cables for Instrument and Control
Non-intrinsically safe cables for Instrument and Control
Non-intrinsically safe cables for FGS.
Blue
Black
Red
Intrinsically safe cables for FGS.
Red with longitudinal blue strip
Non-intrinsically safe Foundation Fieldbus cables
Orange
Intrinsically safe Foundation Fieldbus cables
Orange with longitudinal blue strip
Outer sheath colour for Building Fire Alarm Panel’s cables shall be as per purchase cable data sheets.
Thermocouple cables shall have overall sheath colour in accordance with lEC 60584-3 as follows:
Description
Thermocouple Type - B
Thermocouple Type – E
Thermocouple Type – J
Thermocouple Type – K
Thermocouple Type – R or Type - S
Thermocouple Type - T
Outer Sheath Colour
Blue
Violet
Black
Green
Orange
Brown
Document No: AGES-SP-04-006
Rev. No: 1 Page 24 of 148
Cable Performance requirements
10.4.1 Physical and Mechanical Characteristics.
The physical and mechanical characteristics of the cable core, insulation, screens, sheaths, bedding, filler and armour materials shall be in accordance with the relevant standards that are referred to each type of cables.
10.4.2 Electrical Characteristics.
The electrical characteristics such as resistance, inductance and capacitance of the complete cables shall be in accordance with the relevant standards that are referred to each type of cables.
The electrical parameters such as L/R ratio and Mutual Capacitance for the I.S. cables shall be as per Control Systems VENDOR recommendation based on I.S. circuit design, which shall be specified in the project specific data sheet.
10.4.3 Flame Retardant Characteristics.
Flame retardant cables shall pass the tests as defined in IEC 60332-3-22 Category A (reduced propagation). In addition to above, refer to BS 6883 for Offshore flame retardant cables.
10.4.4 Fire Resistant Characteristics.
Fire resistant cables shall pass the tests as defined in IEC 60331-1, 2 & 3. Fire resistant test and mechanical shock test shall be carried out simultaneously with the flame temperature of 830°C and application time of 90 minutes.
In addition to above, refer to BS7917 for Offshore fire resistant cables.
10.4.5 Smoke Emission Level.
Smoke emission test shall be carried out in accordance with IEC 61034-1 & 2 and the smoke generated shall not result in transmittance value of lower than 60%.
10.4.6 Acid Gas Emission Level
Acid gas emission level test shall be carried out in accordance with IEC 60754-1 requirements. The maximum level of hydrogen chloride (HCl) emission during the combustion of insulation, sheath, bedding and filler materials shall not be greater than 0.5%.
10.4.7 Corrosivity Level
pH and conductivity tests shall be carried out in accordance with IEC 60754-2 requirements.
10.4.8 Fluorine Content Level
Fluorine content test shall be carried out in accordance with IEC 60684-2 requirements.
10.4.9 Oxygen Index.
As a minimum, the oxygen index value for cable shall be greater than 32.
10.4.10 Oil Resistance Characteristics.
Test method and its performance test results for the aboveground cables shall be as per IEC 60811 and Table 9 of IEC 60092-360 respectively.
Test method for the underground cables shall be as per EN 60811 and its performance test results shall be as per EN 50289 and EN 50290.
Document No: AGES-SP-04-006
Rev. No: 1 Page 25 of 148
Refer to BS7655 Section 2.6 for the test requirements and the application details of Offshore / Marine oil- resisting cable, cross-linked elastomeric insulating and sheathing compound types SW1, SW2, SW3 and SW4. Refer to BS7655 Section 1.4 for oil-resisting compound type OR1.
10.4.11 Resistance to Solar Radiation.
Solar radiation (UV rays) resistant of the cables shall be tested in accordance with EN 50289-4-17.
10.4.12 Resistance to Heat Characteristics.
Thermal ageing tests for the cable insulation and sheaths, such as ageing in an air oven and ageing in an air bomb test, shall be carried out in accordance with IEC 60811-401.
10.4.13 Resistance to Water Treeing Characteristics
Cables resistant to water treeing characteristics shall be tested in accordance with the relevant method specified in cable construction standards.
10.4.14 Resistance to Drilling Fluids
Drilling fluids resistant of the cables shall be tested in accordance with IEC 60092-360.
10.4.15 Resistance to Chemicals and Solvents
Cables resistant to Chemicals and solvents test shall be carried out in accordance with the relevant standards that are referred in cable construction standards.
10.4.16 Ozone Resistance Characteristics
Ozone resistance test for insulation and sheath(s) shall be carried out in accordance with IEC 60811-403.
Marking and Traceability Requirements
Cables shall be supplied in continuous drum lengths without any cable or conductor joints.
No negative tolerance on drum length is permissible.
10.5.1 Cable Marking
The outer sheath of cable shall be embossed legibly every one meter along the entire cable length, on two sides, with the following data as a minimum:
(a) Manufacturer Name and year of manufacture
(b) Applicable Cable Standard (EN 50288-7 etc.)
(c)
Flame retardant as per IEC 60332-3 or Fire Resistant as per IEC 60331
(d) Voltage rating (300V/500V etc.)
(e) Cable Type and Designation (construction) or Fibre quantity, size and type
(f)
Cable length (in metres) and sequential length mark
(g) Number of cores (or pairs or fibres) and conductor size (CSA)
(h) Circuit Integrity Class (for Fire Resistant Cables)
The letters and figures on the outer sheath shall consist of upright block characters with a minimum height of 3 mm.
Document No: AGES-SP-04-006
Rev. No: 1 Page 26 of 148
For FO cables, each buffer tube of the outdoor cable shall be a different colour in accordance with VENDOR standard.
The VENDOR shall include the following additional cable information on the cable datasheet for each cable type:
(a) Conductor resistance at 35°C ohms/1000 meters.
(b)
Impedance at 50Hz in ohms/1000 meters.
(c) Mutual capacitance at 50Hz in nanofarads/1000 meters.
(d)
L/R ratio in micro henry/ohm
(e) Weight in Kg/1000 meters.
(f)
Diameter of cable under armour and tolerance.
(g)
Thickness of armour and tolerance.
(h) Bending radius at minimum installation temperature.
(i)
(j)
Minimum installation temperature.
Overall Cable Diameter.
(k) Mutual inductance in millihenry/1000meters.
Refer to Appendix1 for the cable datasheet and Appendix 2 for the cable designation/numbering
requirements.
10.5.2 DRUM MARKING
All cables shall be supplied and delivered in maximum manufacturing cable drums length, continuous lengths on non-returnable cable drums. VENDOR shall specify their standard production length for the selected cable types.
Cable ends shall be sealed and fixed to the drum. Cable drums shall be fitted with battens, fixed around the entire periphery of the drum.
All cable drums shall have their identification number or reference clearly stenciled on the outside of both flanges.
Each cable drum shall be fixed with clear weatherproof identification labels. Labels shall be robust and non- fading. All cable drums labels shall provide the following information as a minimum:
(a) Manufacturer’s name and year of manufacture
(b) Drum identification number (COMPANY and VENDOR’s numbers)
(c)
Purchase order number and project name
(d) Purchase order item number (or Stock code Number as stated in Material Requisition)
(e) Voltage rating
(f)
Number of cores (or pairs or fibres) and conductor size (CSA)
(g) Cable quantity (length)
(h) Cable type and Designation (construction) or Fibre quantity, size and type
(i)
Length of cable on the drum (in metres)
Document No: AGES-SP-04-006
Rev. No: 1 Page 27 of 148
(j)
Total weight of cable and drum (kg)
(k)
Site location
VENDOR shall produce a drum schedule for the scope of supply on each project and shall identify each cable length. All drum lengths shall be continuous. Cable or conductor jointing in any form is unacceptable.
VENDOR shall also identify where multiple cable designations have been applied to a single cable length on the drum and identify each designated cable length to allow for unreel & cable cutting after delivery, where appropriate.
Document No: AGES-SP-04-006
Rev. No: 1 Page 28 of 148
11 SPECIAL CABLES
Fibre Optic Cables
Selection of Fibre Optic (FO) cables and its design shall comply with all parts of IEC 60793, IEC 60794, IEC 61281-1, IEC 61282 and ITU-T G.652.
Fibre optic cable properties and construction shall be as follows:
Sr.No.
Description
Multimode step Index/Multimode Graded Index
Single Mode Fibre
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Core Glass Diameter
6.25/125 or 50/125 micrometer
9 / 125 micrometer
Maximum Attenuation
Minimum Bandwidth
Optical Characteristics
Minimum Fibre Count
Fibre Identification
3.0 dB/Km@850 nm 0.8 dB/Km@1300 nm
400 MHz/Km@850 nm 600 MHz/Km@1300 nm
IEC 60793-210 Type A1b (62.5 micrometer)
0.4 dB/Km@1310 nm 0.25 dB/Km@1550 nm
20 GHz
G.652.D
G.651.1 (50 micrometer)
G.655 NZ-DSF (DWDM System)
24
Colour Coded Fibre Tubes
Fibre Tube
Extruded Tubes, Jelly filled with longitudinal tightness
Minimum Core in a tube
6
Inner Jacket
Black Flame Retardant Polyvinyl Chloride
Fibre Sheath
Non-leaded Hydrocarbon Resistant, Moisture Barrier with Metallic Tape
Bedding
Armour
Rip Cord
Polyvinyl Chloride, Black Colour
Galvanized Steel Wire Armour or Equivalent strength Steel Tape Armour
Yes
Outer Jacket
Black Flame Retardant Polyvinyl Chloride, Black Colour
A minimum of 2 x 24 core Single Mode FO Cable shall be provided for each system, unless otherwise specified by the project requirement.
All FO cables construction shall be based on the ‘Loose Tube’ type. Loose tube cables are characterized by loose fitting, buffer or gel-filled tubes into which the fibres are placed.
Each individual fibre shall be protected by a loosely fitting, colour coded, buffer tube. The tubes shall be extruded from PolyButylene Terephthalate (PBT) or Allied ‘HALAR’ fluoroplastic or an acceptable equivalent. The outside diameter of the buffer tubes shall not exceed 3.0 mm (0.118 inches). The buffer tubes shall be twisted around the central member with a lay which will result in each buffer tube being
Document No: AGES-SP-04-006
Rev. No: 1 Page 29 of 148
approximately two percent longer than the central member. Each buffer tube, as well as the core interstices, shall be flooded with a filling compound to minimize water entry and migration. The compound shall be stable, moisture resistant, non-toxic, electrically non-conducting and compatible with all other cable components.
No fibre splices are allowed in a length of completed cable.
FO Cables shall be given buckle resistance by a glass reinforced plastic (GRP) rod or equivalent, through the center of the cable. An Aramid wrap and/or E-glass yarn and polyester tape around the buffer tubes provides tensile strength.
The inner and outer sheath material shall be LSZH Flame Retardant compound. Wherever required, the FO cable design shall also be fire resistant to IEC 60331.
All outdoor FO cables shall have a twisted steel wire armour in addition to the dual jacketing structure.
The cable shall be designed so that the fibers will not be stressed when the cable is installed with a minimum bending radius of 25 cm.
Fibre Optic Cable shall have fibre colours and buffer tube colours in accordance with EIA/TIA-598.
Direct Burial Fibre-Optic Cables
In addition to the requirements above, fibre-optic cables intended for direct burial shall have a secondary lead sheath, or equivalent multi-layer sheath.
11.2.1 Lead Sheath / Multi-layer Sheath
The lead sheath or multilayer sheath shall provide a barrier against moisture, chemicals, water, solvents, environment and hydrocarbon oil attacks.
All onshore underground buried cables shall be provided with Lead Sheath as a moisture and chemical barrier in accordance with BS EN 50288 and shall comply to EEMUA 133 for lead quality. Alternatively, Aluminum/high density polyethylene/polyamide (AL/HDPE/PA) multi-layer inner sheath can be acceptable subject to COMPANY prior approval. VENDOR shall provide ‘Type Test’ certificates, from a test house acceptable to COMPANY, for AL/HDPE/PA multi-layer inner sheath cables to validate degree of ingress protection against water, organic and non-organic chemicals.
11.2.2 Bedding Layer
The bedding layer shall be provided between lead sheath and armour for underground cables.
The material of construction for the bedding layer shall be same as that of the inner sheath material.
11.2.3 Steel Wire Armour
Armored cable shall have Galvanized Steel Wire Armour under outer sheath.
The galvanized steel wire armour shall comply to requirements of EN 10257-1 and, EN 10218-1.
The coating of steel wire shall comply with the requirements of EN 10244-2.
11.2.4 Outer Sheath
Outer sheath material shall be minimum PVC or better and comply with this specification requirements. Outer sheath shall be Low Smoke Zero Halogen Flame Retardant Compound. Outer sheath shall be
Document No: AGES-SP-04-006
Rev. No: 1 Page 30 of 148
suitable for specified service, operating temperature, site conditions and cable design standard indicated in cable data sheets. Outer sheath shall be extrusion type.
Outer sheath shall be anti-vermin impregnated and UV-resistant. Outer sheath shall be heat, oil and flame retardant (HOFR).
Outer sheath material shall be minimum PVC or better and comply with this specification requirements.
Document No: AGES-SP-04-006
Rev. No: 1 Page 31 of 148
SECTION C
12 SCOPE OF SUPPLY
The VENDOR shall supply Instrument and Control cables in accordance with technical requirements in this specification and project specific Purchase Order documentation.
The VENDOR scope of supply shall include but not be limited to:
- Supply of cables as per types and quantities listed in project purchase order
- Design, fabrication, assembly and testing of cables
- Submission of VENDOR’s Design Specification for cable design, fabrication and testing for
CONTRACTOR/COMPANY approval Inspection and Testing at VENDOR’s work
- Packing & Shipping to site
- Documentation
- Warranty and Guarantee
13 QUALITY CONTROL AND ASSURANCE
Equipment and materials shall only be purchased from Vendors approved by ADNOC Category Management. This approval indicates that the VENDOR has an approved Quality management system and a proven track record in supply of this equipment and material type.
COMPANY/CONTRACTOR reserves the right to inspect materials and workmanship at all stages of manufacture and to witness any or all tests.
VENDOR shall comply to Criticality Rating for Equipment outlined in respective ADNOC Group Company’s Quality System Specifications for requirements of production checks, shop inspection, testing and material certification.
The VENDOR shall provide equipment and material inspection and test reports as per approved Inspection and Test Plan by CONTRACTOR.
14 MATERIAL CERTIFICATION
VENDOR shall provide all material Test Certificates as per Supplier Document Register and Schedule (SDRS) provided in Purchase Order.
Document No: AGES-SP-04-006
Rev. No: 1 Page 32 of 148
15
INSPECTION & TESTING REQUIREMENTS
The VENDOR shall be responsible for workmanship, testing and quality assurance of the material supplied.
All formal testing will be conducted in accordance with written Inspection and Test Plan (ITP) test procedure. The test procedures shall be furnished by the VENDOR to the CONTRACTORS at least two months prior to the associated test for approval.
Instrument and Control Cables
All the cables shall be subjected to routine tests and the test records/reports shall be submitted for CONTRACTOR/COMPANY review.
The test requirements, types of tests and test procedures shall be specified in the Inspection and Test Plan (ITP), submitted and agreed with the COMPANY.
COMPANY, CONTRACTOR and/or assigned Third Party Inspector for the specific project shall witness the inspection and tests as per approved project specific Inspection and Test Plan (ITP) and QA/QC procedure. The COMPANY shall be informed of testing schedule with an advance notice as per project specific contract requirements.
The inspection and acceptance of reports and certificates shall in no way release VENDOR from final guarantee with regard to materials, workmanship and performance of the material inspected.
The VENDOR shall be responsible for inspection and quality assurance of the materials and standard of workmanship furnished. Testing and inspection will be carried out and witnessed by the CONTRACTOR and COMPANY representatives at various stages as the equipment is manufactured and assembled, at locations as detailed below:
(1) Shop Inspection: Conducted at the manufacturing facility of VENDOR
(2)
Factory Acceptance Test: Conducted at the manufacturing facility of VENDOR
(3) Site Delivery Acceptance Test and Inspection: Conducted at the job site.
Each formal acceptance test shall be signed by VENDOR, CONTRACTOR and COMPANY representatives at the successful completion of the test(s).
Inspection and Testing shall be performed only when all the technical documents from the VENDOR are reviewed and approved by COMPANY. Before commencement of any test, copies of all relevant drawings, certificates and specifications shall be made available to the COMPANY.
Provision of suitable test gear and accessories, if any, for the test shall be the responsibility of the VENDOR.
All the punch points highlighted during Factory Acceptance Test (FAT) shall be cleared in agreement with COMPANY.
Material shall be dispatched only after obtaining dispatch clearance from the CONTRACTOR/COMPANY. All the necessary documents including FAT punch points clearance report and material test certificates shall be submitted to CONTRACTOR/COMPANY, while requesting the dispatch clearance.
Document No: AGES-SP-04-006
Rev. No: 1 Page 33 of 148
During the FAT, the following tests are to be carried out at VENDOR works for witness by representatives of COMPANY, CONTRACTOR and Third-Party Inspector.
Below (S) means ‘Sample Test during FAT (samples taken from drum)’ and (D) means ‘Drum Test for the complete length of cable in the drum’.
(a) Dimensions and Tolerances Check (S & D)
(b) Voltage test (S)
(c) Continuity test (D)
(d)
(e)
(f)
Insulation resistance test (S & D)
Flame Retardant test (S)
Fire with mechanical shock resistant test (S)
(g)
Fire tests including pH & Conductivity, Fluorine content, Acid gas emission test (S)
(h) Oxygen index test (S)
(i)
(j)
Bending test (S)
Conductor resistance test. including drain wire (S & D)
(k)
Electrical Characteristics L/R ratio & Capacitance (S)
(l)
Resistant to Fire with water spray test (S)
(m) Thermal Ageing test (S)
(n) Smoke Density test (S)
(o) Ozone Resistance Test (S)
(p) Oil Resistant Test (S)
(q) UV resistant Test S)
(r)
Drilling Fluid Resistance test (S)
(s) High Temperature Test (for siliconee insulated cables) (S)
(t) Watering Treeing Test (S)
(u) Galvanizing Test (Dipping Test) (S)
(v) Mechanical Tests including impact resistance test (S)
Where there are no standard test procedures available in the referenced IEC / BS standards for some specific tests, test procedures and methods shall be developed by VENDOR and agreed with COMPANY.
Details such as cable diameter shall be submitted to the COMPANY during the course of manufacture to enable designing and/or selection of the cable gland.
After testing, the ends of the cable shall be sealed with approved caps to prevent the ingress of moisture.
The test reports shall contain as a minimum:
(a)
(b)
The anticipated (theoretical) values.
The tolerances permitted.
Document No: AGES-SP-04-006
Rev. No: 1 Page 34 of 148
(c)
The results of the measurements, including any intermediate value, which has caused a temporary rejection.
(d) Explanation of any calculations.
Fibre Optic Cables
Tests shall be carried out on all fibre optic cables according to EIA TIA-455 to verify attenuation and bandwidth specifications at the manufacturer’s premises.
Routine tests and sample tests shall be carried out on all cables produced and shall be in accordance with IEC 60793, IEC 60794 and IEC 61280.
The routine type tests shall include the following:
(a) OTDR measurements
(b) End to end attenuation
(c) Macrobending loss
(d) Chromatic dispersion
(e) Stress corrosion susceptibility
(f)
(g)
(h)
(i)
Bandwidth
Tensile strength
Fibre proof tests
Fibre geometry
Additional tests shall be carried out to verify the FO cable properties including the following:
(a)
(b)
(c)
Fire resistance test to IEC 60331 and EN 50200 for fire resistant cables.
Flame retardant test IEC 60332 for flame retardant cables.
Bending test for all cables.
(d) Cable Bending Radius (IEC 60794-1-2-E11 and -E6).
(e)
Tensile Force (IEC 60794-1-2-E1).
(f)
Torsion Strength (IEC 60794-1-2-E7).
(g) Crush Resistance (IEC 60794-1-2-E3).
(h)
Impact Resistance (IEC 60794-1-2-E4).
(i)
Kink Resistance (IEC 60794-1-2-E10).
(j) Water Penetration (IEC 60794-1-2-F5).
The FAT will include the inspection, testing and acceptance of Fibre Optic Cables as per EIA/TIA and ITU standards. In particular, the attenuation test shall be done on 100% fibres.
At the satisfactory conclusion of the FAT, a factory Certificate of Acceptance shall be provided by the VENDOR for signature by COMPANY and CONTRACTOR.
Document No: AGES-SP-04-006
Rev. No: 1 Page 35 of 148
At the satisfactory conclusion of the Site Acceptance Test (SAT), a Provisional Acceptance Certificate shall be prepared by CONTRACTOR. Along with all test reports and certificates, a Certificate of Provisional Site Acceptance, which COMPANY shall review and approve.
16 SUBCONTRACTORS/SUBVENDORS
The VENDOR shall assume unit responsibility and overall guarantee for the equipment package and associated materials.
The VENDOR shall transmit all relevant purchase order documents including specifications to his SUBCONTRACTORS.
It is the VENDOR’S responsibility to enforce all Purchase Order and Specification requirements on his SUBCONTRACTORS.
The VENDOR shall submit all relevant SUBCONTRACTOR drawings and engineering data to the CONTRACTOR.
The VENDOR shall obtain and transmit all SUBCONTRACTORS warranties to the CONTRACTOR/COMPANY, in addition to the system warranty.
17 SPARE PARTS
Not Applicable.
18 PACKING, PRESERVATION & SHIPMENT
Packing and Shipping
Preparation for shipment shall be in accordance with purchase order Preservation and Export Packing requirements. VENDOR shall be solely responsible for the adequacy of the preparation for shipment provisions with respect to materials and application, and to provide equipment at the destination in ex-works condition when handled by commercial carriers. Adequate protection shall be provided to prevent mechanical damage and atmospheric corrosion in transit and at the jobsite. Preparation for shipment and packing will be subject to inspection and rejection by COMPANY’S/CONTRACTOR’S inspectors. All costs occasioned by such rejection shall be to the account of the VENDOR. Cables shall be export quality packed to prevent damage during transit, lifting, or unloading. Pieces of equipment and spare parts shall be identified by item number and service and marked with CONTRACTOR’S order number, tag number, and weight, both inside and outside of each individual package or container. A bill of material shall be enclosed in each package or container of parts. One complete set of the installation, operation, and maintenance instructions shall be packed in the boxes or crates with equipment. This is in addition to the number called for in the Purchase Order.
All kinds of regulatory / non-regulatory approvals and procedures required for shipping shall be in the scope of CONTRACTOR / VENDOR.
Preservation and Storage
Cables shall be protected to withstand ocean transit and extended period of storage at the jobsite for a minimum period of 18 months. Cables shall be protected to safeguard against all adverse environments, such as humidity, moisture, rain, dust, dirt, sand, mud, salt air, salt spray, and seawater. All cables shall be preserved, and export packed in accordance with project specifications.
Document No: AGES-SP-04-006
Rev. No: 1 Page 36 of 148
Adequate protection shall be provided to prevent mechanical damage and atmospheric corrosion in transit and at the worksite. The cable drums shall be lagged or covered with suitable material, to provide physical protection during transit, ordinary storage and handling operations.
The ends of Control and Instrument cables shall be properly sealed for transport by sea and for storage under desert conditions. Cable ends shall be fitted with heat shrink end cap to prevent entry to moisture inside the cable.
The VENDOR shall provide preservation plan to protect and ensure the integrity of equipment and materials during the period that starts when the equipment and materials is prepared for the first shipment from the point of origin and ends at the completion of project commissioning and start-up. The plan shall identify protective measures to be implemented during each phase of the project, inclusive of ambient conditions. The completion plan shall be submitted to COMPANY for review and comment no later than 90 days prior to the first shipment of equipment and materials from the factory.
Preparation for shipment and packing will be subject to inspection and rejection by COMPANY inspectors.
19 COMMISSIONING
Not Applicable.
20 TRAINING
Not Applicable.
21 DOCUMENTATION/MANUFACTURER DATA RECORDS
GENERAL
VENDOR shall submit the type and quantity of drawings and documentation for COMPANY/CONTRACTOR authorization or information as per Supplier Document Register and Schedule (SDRS) provided in Purchase Order.
The VENDOR shall provide all standard and project-specific documentation and material data sheets. This information shall provide complete documentation for the cables in sufficient detail to permit supply, installation, proof testing, maintenance and replacement of the control and instrumentation cables.
Mutual Agreement on document list and documents issue dates shall be an integral part of Purchase Order.
Comments made by COMPANY/CONTRACTOR on drawing submittal shall not relieve VENDOR of any responsibility in meeting the requirements of this specification. Such comments shall not be construed as permission to deviate from requirements of the Purchase Order unless specific and mutual agreement is reached and confirmed in writing.
All drawings, documents, information, correspondence, test reports, operating and maintenance instructions and like items shall be in the English language.
All documents and drawings issued by the VENDOR shall be produced in an electronic format compatible with Microsoft Office computer software. Documentation shall also be provided in Native format, in order to allow company to update during operational upgrade and future projects. VENDOR shall provide final documentation on DVD-ROM with search and retrieval capabilities.
All drawings and datasheets shall be prepared and submitted in accordance with recognized standards. Every effort shall be made to minimize the total number of drawings and datasheets prepared by use of common drawings or datasheets, where practicable without loss of clarity.
Each drawing or datasheet shall be provided with a block in the bottom right-hand corner incorporating the following information:
Document No: AGES-SP-04-006
Rev. No: 1 Page 37 of 148
(a) Official trade name of the VENDOR.
(b) VENDOR’S drawing or material reference number.
(c) Drawing title giving the description of contents whereby the drawing can be identified.
(d) A symbol or letter indicating the latest issue or revision.
(e) PO number and item tag numbers.
Revisions to drawing or datasheet shall be identified with symbols adjacent to the alterations, a brief description in tabular form of each revision shall be given, and if applicable, the authority and date of the revision shall be listed. The term “Latest Revision” shall not be used.
DELIVERABLES
The VENDOR and CONTRACTOR shall supply complete final cable documentation, which shall include but not limited to the following:
(a)
Technical Data Sheets & Specifications
(b) Material Test Certificates
(c) Dimensional Details
(d)
Installation Test Certificates
22 GUARANTEES & WARRANTY
VENDOR shall provide warranty support for a period of two years following cable installation and plant commissioning at site. Warranty shall apply to defective material workmanship and cable failures. The cost of diagnostics and/or correction of any warranty items shall be borne by the VENDOR.
The VENDOR shall guarantee that supplied cables last till design life for 30 years.
Document No: AGES-SP-04-006
Rev. No: 1 Page 38 of 148
SECTION D
23 DATA SHEETS
Refer following Appendices in Section E for cable data sheet, numbering method and construction requirements:
Appendix 1: CABLE DATASHEET
Appendix 2: CABLE DESIGNATION
Appendix 3: TYPICAL CONSTRUCTION DETAILS FOR CABLES
24 STANDARD DRAWINGS
Not applicable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 39 of 148
APPENDICES
APPENDIX 1 CABLE DATA SHEETS
CONTROL/INSTRUMENTATION CABLE
The cable details listed below, items 1 to 71 including the tick-boxes & the data values, shall be provided/submitted by the VENDOR on a datasheet for each cable.
- Cable Type (Code and Designation):
-
Cable Quantity required (metres): ………………………………3. Manufacturer: ………
-
Purchase Order Number and Date: ……………………………………………….
dd/mm/yyyy
-
Installation:
Aboveground
Underground
Indoor
Marine
- Manufacturing Standard
IEC 60092
BS EN 50288
BS 6883
BS 7917
- Cable characteristic:
Flame Retardant
Fire Resistant
High Temperature
- Intrinsic Safety requirement:
IS
NIS
- Application Requirement: …………………………………………………………………………………………
(Analog, RTD, Thermocouple, Vibration, Speed, Digital Input, Digital Output, SOV, F&G, ESD, Comms, Other – please specify)
- Rated Voltage (Uo/U):
300V/500V
Other(…….)
- CSA of Conductor:
1.0mm²
1.5mm²
2.5mm²
Other (
)
- Conductor Class:
Class 1 (solid)
Class 2 (stranded)
- Conductor Insulation Material Halogen Free Flame Retardant as per IEC 60092, BS EN 50290:
EPR
XLPE
MGT EPR
MGT XLPE
Other __________________
XL SILICONE RUBBER (S95)
MGT XL SILICONE RUBBER (S95)
- Conductor Insulation Material Halogen Free Flame Retardant BS 6883 & BS 7917:
GP4
GP 5
GP6
GP7
Other ___________________
-
Conductor Formation:
Cores (…….)
Pair
Triad
Quad
Document No: AGES-SP-04-006
Rev. No: 1 Page 40 of 148
16. Core Colours / Identification:
Black, White
Black, White, Red
Black, White, Red, Blue
Other……………………..
-
Thickness of insulation: ______ mm
-
Lay length (Number of twists per Metre): _____
-
Screen/Foil:
Individual
Overall
Individual & Overall
N/A
20. Screen material: Other……….
Aluminium bonded to polyester (Mylar) tape Braid
-
Drain wire and size: …………………………………………………………………….
-
Inner Sheath material as per IEC 60092, BS EN 50290:
Halogen Free Flame Retardant Compound Other…….
-
Inner Sheath material Halogen Free Flame Retardant Compound (BS 6883-5.3 or BS 7917-5.3):
SW2
Other……………
-
Thickness of inner sheath: …………………. 25. Inner Sheath colour: …………………………
-
Mechanical Protection:
Unarmoured
GSWB
GSWA
Foil
GSW Diameter……..……
- Bedding material:
Rubber, Type SHF2
HFFR Compound
Other………………….
28. Moisture and Chemical barrier:
Lead sheath
AL/HDPE/PA Multi-layer Sheath N/A
-
Thickness of lead sheath………………………. sheath………………
-
Thickness of multi-layer
-
Outer Sheath material as per IEC 60092, BS EN 50290:
Halogen Free Flame Retardant Compound Other………….
-
Outer Sheath material Halogen Free Flame Retardant Compound (BS 6883-4.2 or BS 7917-4.2):
SW2
Other……………………
-
Thickness of outer sheath: …………………. 34. Outer Sheath colour: ………………………
-
Halogen Emission (EN 50267-1&2):
0.5%
5%
Document No: AGES-SP-04-006
Rev. No: 1 Page 41 of 148
36. Special Requirements: …………………………………………………………………………………………… (Excessive Sunlight, Resistance to Chemicals, Corrosive Environment, High Temperature)
-
Thermocouple Tolerance Class:
Class 1
Class 2
N/A
-
Total Cable Length (metres): ………………………………………………………..
-
Drum Length (metres): ……………………………………………………………….
-
Cable Weight (Kg/Km): ……………
-
Cable and Drum combined Weight (Kg): ……………
-
Conductor Max Temperature:
Normal operation………….°C Fault Condition…………….°C.
-
Cable Min. Installation Temperature: ……………………………°C
-
Bending Radius (mm) at minimum install temperature: …………………….……mm at …….…°C.
-
Cable Diameter (mm) and Tolerances:
-
Under Armour……………………………………..
- Material & Thickness:
-
Insulation ……………………………………………
-
Over Armour……………………………………….
-
Overall………………………………………………
-
Bedding……………………………………………..
-
Sheath…….…………………………………………
-
Armour……………………………………………….
-
Others………………………………………………..
-
Recommended Gland type and size: ……………………………………………………………….
-
Resistance Max. at 90°C (Ohm/Km): …………………..
-
Reactance (Ohm/Km): ………………
-
Inductance Max. up to 1 KHz (mH/Km): …………………………………………
-
Impedance Max. @ 90°C & 60 Hz (Ohm/Km): ………………………………….
-
Conductor Loop Resistance per Km @ 35°C: …………………… @ 60°C: ……………………….
-
Max. Loop Self Inductance per Km up to 1 Khz (mH): ………………………….
-
Max. L/R ratio (μH/Ω): …………………………………………………………………
-
Max. Mutual Capacitance (μF/Km): …………………………………………………
-
Max. Capacitance Core to Earth (μF/Km): ……………… Core to Core (μF/m): …………………..
-
Voltage Drop (per amp per Km): ……………………………………………………
Document No: AGES-SP-04-006
Rev. No: 1 Page 42 of 148
58. Short Circuit Rating (kA) at 250°C / sec. duration: ………………………………
-
Smoke Emission level: …………………………………… ………………………….
-
Corrosive and Acid Gas Emission level: ………………………………………….
-
pH and Conductivity levels: ………………………………………………………….
-
Fluorine content level: …………………………………………………………………
-
Oxygen Index value: ……………………………………………………………………
-
Oil resistance characteristics:
-
Ozone resistance characteristics:
-
Resistance to high temperature:
-
Resistant to chemicals & solvents:
-
Resistant to rodent & fauna attack:
-
Resistant to mechanical damage:
-
Resistant to water treeing:
-
Resistant to drilling fluids:
-
Resistant to soil salinity:
-
Resistant to saline water ingress:
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Document No: AGES-SP-04-006
Rev. No: 1 Page 43 of 148
FIBRE-OPTIC CABLES
The Fibre Optic cable details listed below, items 1 to 48 including the tick-boxes & the data values,
shall be provided/submitted by the VENDOR on a datasheet for each Fibre Optic cable.
- Cable Type (Code and Designation):
………………………………………………………………………………
-
Cable Quantity required (metres): ………………………………3. Manufacturer: ………
-
Purchase Order Number and Date: ……………………………………………….
dd/mm/yyyy
-
Installation:
Aboveground
Underground
Indoor
Marine
- Standard References:
IEC60793
IEC60794
IEC62181
IEC61282
ITU-T G.651.1
ITU-T G.652
ITU-T G.655
- Cable characteristic:
Flame Retardant
Fire Resistant
-
Cable Temperature Range: Storage -…..…°C to +…..…°C, Operating -….….°C to +…….°C
-
Application Requirement: …………………………………………………………………………………………
(Comms Backbone, Data trunk, Direct Burial, Cable tray or Duct installation, Automation, Subsystem,
Other)
- Mode/Fibre Type:
OM1
OM2
OM3
OM4
OS2
- Optical Performance: Bandwidth………..…MHz@ 850 nm
Attenuation………….…dB/km
Optical Performance: Bandwidth………..…MHz@ 1300 nm
Attenuation………….…dB/km
Optical Performance: Bandwidth………..…MHz@ ……. nm
Attenuation………….…dB/km
Optical Performance: Bandwidth…………..…GHz Attenuation………….…dB/km@..................nm
12. Core (Fibre) diameter: …………….…/………………… micrometer
- Strength Member Material: Central………………………. Overall……………………………..
(GRP rod, Fibreglass, E-glass, E-glass and Aramid Yarn, Aramid Yarn)
-
Buffer Tube Material: ………………………………………………………………………………..
-
Fibre bundle Formation:
No. of Fibre Cores ……..……. No. of Buffer Tubes……………
- Fibre bundle Wrap / Binder material: …………………………………………………………….
(Water blocking tape, Water swellable tape, Water blocking E-glass yarn, Aramid yarn and polyester tape)
Document No: AGES-SP-04-006
Rev. No: 1 Page 44 of 148
17. Inner Jacket Material:
Halogen Free Flame Retardant Compound
Other………….
18. Thickness of inner jacket: …………………. 19. Inner jacket
colour: …………………………
- Mechanical Protection:
Unarmoured
Corrugated Steel Tape
Aluminium Tape
Polyester Tape
GSWA
E-glass & Aramid Yarn
Aramid Yarn
Other…………….
-
Outer Jacket Material:
Halogen Free Flame Retardant Compound Other………….
-
Thickness of outer jacket: ………………….
-
Outer Jacket colour: …………………………
(Orange, Aqua, Yellow, Black)
- Halogen Emission (EN 50267-1&2):
0.5%
5%
-
Special Requirements: …………………………………………………………………………………………… (Excessive Sunlight, Resistance to Chemicals, Corrosive Environment, High Temperature)
-
Total FO Cable Length (metres): ………………………………………………………..
-
Drum Length (metres): ……………………………………………………………….
-
Cable Weight (Kg/Km): ……………
-
Cable and Drum combined Weight (Kg): ……………
-
Cable Min and Max. Installation Temperature: ………………°C Min
…..……………°C Max
- Minimum Bending Radius at minimum install temperature: ……………… x O.D.
at …….………….°C.
-
FO Cable Outside Diameter (O.D.): ……………… mm
-
Max Installation Load:
……………… N (or equivalent ……………….. Lbs)
- Crush Resistance (EIA-455-41):
……………… N/cm
- Impact Resistance (EIA-455-25):
………………
impacts at ……………….N-m
- Cyclic Flexing (EIA-455-104):
……………… cycles
Document No: AGES-SP-04-006
Rev. No: 1 Page 45 of 148
36. Smoke Emission level: …………………………………… ………………………….
-
Corrosive and Acid Gas Emission level: ………………………………………….
-
pH and Conductivity levels: ………………………………………………………….
-
Fluorine content level: …………………………………………………………………
-
Oxygen Index value: ……………………………………………………………………
-
Oil resistance characteristics:
-
Ozone resistance characteristics:
-
Resistance to high temperature:
-
Resistant to chemicals & solvents:
-
Resistant to rodent & fauna attack:
-
Resistant to mechanical damage:
-
Resistant to water treeing:
-
Resistant to drilling fluids:
-
Resistant to soil salinity:
-
Resistant to saline water ingress:
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
Yes
No
No
No
No
No
No
No
No
No
No
Document No: AGES-SP-04-006
Rev. No: 1 Page 46 of 148
APPENDIX 2 CABLE DESIGNATION
CABLE FOR OUTDOOR ABOVE GROUND INSTALLATION
Instrument and Control cables (Analogue and Digital Signals) - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for above ground outdoor installation shall be identified with the following designation:
LSZH
1
2
3
4
5
6
7
Colour
For example LSZH/MGT XLPE/IS & OS/LZSH/GSWA/LZSH/5P/1.5 mm²/Black
- Core Insulation
XLPE
MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Silicone Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
- Screen OS IS & OS
Inner Jacket
LZSH
- Armour
Overall Screen Individual and Overall Screen
Flame Retardant Low Smoke Zero Halogen Compound
GSWA
Galvanised Steel Wire Armour
- Outer Jacket
LZSH
Flame Retardant Low Smoke Zero Halogen Compound
- Number of Cores or Pairs or Triads or Quads
2C, 4C, 7C, 11C, 19C, 27C, 37C, 1P, 1T, 1Q 2P, 2T, 2Q 10P, 10T, 10Q 20P, 20T
- Cross Sectional Area of each Conductor
1.0 mm2, 1.5mm² or 2.5mm² or state the alternative size
Outer jacket colour shall be as per application.
Use the “–“ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner jacket and/or without armour.
Document No: AGES-SP-04-006
Rev. No: 1 Page 47 of 148
CABLE SUITABLE FOR DIRECT BURIAL OR OUTDOOR USE
Instrument and Control cables (Analogue and Digital Signals) - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for underground or outdoor installation shall be identified with the following designation:
LSZH
1
2
3
4
5
6
7
8
9
Colour
For example LSZH/MGT XLPE/IS & OS/LZSH/MLS/LSZH/GSWA/LZSH/2T/2.5 mm²/Black
- Core Insulation
XLPE MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Silicone Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
- Screen OS IS & OS
Overall Screen Individual and Overall Screen
Inner Jacket
LZSH
EPR
SHF2
Flame Retardant Low Smoke Zero Halogen Compound equivalent EPR, LSZH. equivalent Siliconee Rubber, LSZH.
Inner Sheath (Moisture & Chemical Barrier) LS MLS
Lead Sheath Multi-Layer Sheath (AL/HDPE/PE)
-
Bedding LZSH
-
Armour
GSWA
- Outer Jacket
LZSH EPR SHF2
Flame Retardant Low Smoke Zero Halogen Compound
Galvanised Steel Wire Armour
Flame Retardant Low Smoke Zero Halogen Compound equivalent EPR, LSZH. equivalent Siliconee Rubber, LSZH.
- Number of Cores or Pairs or Triads or Quads
2C, 3C, 4C, 7C, 11C, 19C, 27C, 37C, 1P, 1T, 1Q 2P, 2T, 2Q 10P, 10T, 10Q 20P, 20T
Document No: AGES-SP-04-006
Rev. No: 1 Page 48 of 148
9) CSA of each Conductor
1.0 mm2, 1.5mm² or 2.5mm² or state the alternative size
Outer jacket colour shall be as per application.
Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner sheath and without bedding material.
Document No: AGES-SP-04-006
Rev. No: 1 Page 49 of 148
THERMOCOUPLE EXTENSION CABLE FOR OUTDOOR ABOVE GROUND INSTALLATION
Thermocouple Extension cables - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for above ground outdoor installation shall be identified with the following designation:
LSZH
1
2
3
4
5
6
7
Type
For example LSZH/MGT XLPE/IS & OS/LZSH/GSWA/LZSH/5P/1.5 mm²/Type K
- Core Insulation
XLPE
MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Silicone Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
- Screen OS IS & OS
Inner Jacket
LZSH
- Armour
Overall Screen Individual and Overall Screen
Flame Retardant Low Smoke Zero Halogen Compound
GSWA
Galvanised Steel Wire Armour
- Outer Jacket
LZSH
- Number of Pairs
Flame Retardant Low Smoke Zero Halogen Compound
1P, 2P, 10P, 20P
- CSA of each Conductor
1.0 mm2, 1.5mm² or state the alternative size
State the Thermocouple Type; Type B, E, J, K, N, R, S or Type T.
Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner jacket and/or without armour.
Document No: AGES-SP-04-006
Rev. No: 1 Page 50 of 148
THERMOCOUPLE EXTENSION CABLE SUITABLE FOR DIRECT BURIAL
Thermocouple Extension cables - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for underground or outdoor installation shall be identified with the following designation;
LSZH
1
2
3
4
5
6
7
8
9
Type
For example LSZH/MGT XLPE/IS & OS/LZSH/MLS/LSZH/GSWA/LZSH/2P/1.5 mm²/Type K
- Core Insulation
XLPE
MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Siliconee Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
- Screen OS IS & OS
Overall Screen Individual and Overall Screen
Inner Jacket
LZSH
EPR
SHF2
Flame Retardant Low Smoke Zero Halogen Compound equivalent EPR, LSZH. equivalent Siliconee Rubber, LSZH.
Inner Sheath (Moisture & Chemical Barrier) LS MLS
Lead Sheath Multi-Layer Sheath (AL/HDPE/PE)
-
Bedding LZSH
-
Armour
GSWA
- Outer Jacket
LZSH EPR SHF2
Flame Retardant Low Smoke Zero Halogen Compound
Galvanised Steel Wire Armour
Flame Retardant Low Smoke Zero Halogen Compound equivalent EPR, LSZH. equivalent Silicone Rubber, LSZH.
- Number of Pairs
1P, 2P, 10P, 20P
- CSA of each Conductor
1.0 mm2, 1.5mm² or 2.5mm² or state the alternative size
State the Thermocouple Type; Type B, E, J, K, N, R, S or Type T. Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner sheath and without bedding material.
Document No: AGES-SP-04-006
Rev. No: 1 Page 51 of 148
FIELDBUS CABLE FOR OUTDOOR ABOVE GROUND INSTALLATION
Foundation Fieldbus cables - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for above ground outdoor installation shall be identified with the following designation:
LSZH
1
2
3
4
5
6
7
Colour
For example LSZH/XLPE/IS & OS/LZSH/GSWA/LZSH/2P/1.5 mm²/Orange
- Core Insulation
XLPE
MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Silicone Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
- Foil Screen
OS IS & OS
Overall Foil Screen Individual Foil and Overall Foil Screen
Each foil screen is an aluminium tape plastic coated on one surface, with the metal surface in contact with a drain wire.
Inner Jacket
LZSH
BRAID
- Armour
Flame Retardant Low Smoke Zero Halogen Compound Tinned copper braid in continuous contact with a drain wire.
GSWA
Galvanised Steel Wire Armour
- Outer Jacket
LZSH
Flame Retardant Low Smoke Zero Halogen Compound
- Number of Cores or Pairs
1P, 2P, 5P, 10P, 20P
- CSA of each Conductor
1.0mm², 1.5 mm2 or state the alternative size.
Outer jacket colour shall be as per application.
Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner jacket and/or without armour.
Document No: AGES-SP-04-006
Rev. No: 1 Page 52 of 148
FIELDBUS CABLE SUITABLE FOR DIRECT BURIAL
Foundation Fieldbus cables - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for underground or outdoor installation shall be identified with the following designation:
LSZH
1
2
3
4
5
6
7
8
9
Colour
For example LSZH/MGT XLPE/IS & OS/LZSH/MLS/LSZH/GSWA/LZSH/2P/1.5 mm²/Orange
- Core Insulation
XLPE
MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Silicone Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
- Screen OS IS & OS
Overall Foil Screen Individual Foil and Overall Foil Screen
Each foil screen is an aluminium tape plastic coated on one surface, with the metal surface in contact with a drain wire.
Inner Jacket
LZSH
BRAID
Flame Retardant Low Smoke Zero Halogen Compound Tinned copper braid in continuous contact with a drain wire.
Inner Sheath (Moisture & Chemical Barrier) LS MLS
Lead Sheath Multi-Layer Sheath (AL/HDPE/PE)
-
Bedding LZSH
-
Armour
GSWA
- Outer Jacket
LZSH EPR SHF2
Flame Retardant Low Smoke Zero Halogen Compound
Galvanised Steel Wire Armour.
Flame Retardant Low Smoke Zero Halogen Compound equivalent EPR, LSZH. equivalent Silicone Rubber, LSZH.
- Number of Cores or Pairs
1P, 2P, 10P, 20P
- CSA of each Conductor
1.0mm² , 1.5 mm2 or state the alternative size.
Outer jacket colour shall be as per application. Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner sheath and without bedding material.
Document No: AGES-SP-04-006
Rev. No: 1 Page 53 of 148
FIRE RESISTANT CABLE FOR OUTDOOR ABOVE GROUND INSTALLATION
Control cables - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for above ground outdoor installation shall be identified with the following designation:
LSZH
1
2
3
4
5
6
7
Colour
For example LSZH/XLPE/OS/LZSH/GSWA/LZSH/12C/2.5 mm²/Black
- Core Insulation
XLPE
MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Silicone Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
Cores should be laid up with extruded Flame Retardant LSZH Compound filler for up to 5 cores. For 6 cores or more a wrapping of polyester tape is required.
- Screen OS IS & OS
Inner Jacket
LZSH
- Armour
Overall Screen Individual and Overall Screen
Flame Retardant Low Smoke Zero Halogen Compound
GSWA
Galvanised Steel Wire Armour
- Outer Jacket
LZSH
- Number of Cores
Flame Retardant Low Smoke Zero Halogen Compound
2C, 3C, 4C, 7C, 11C, 19C, 27C, 37C
- CSA of each Conductor
2.5mm² minimum or state the alternative size.
Outer jacket colour shall be as per application.
Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner jacket and/or without armour.
Document No: AGES-SP-04-006
Rev. No: 1 Page 54 of 148
FIRE RESISTANT CABLE SUITABLE FOR DIRECT BURIAL
Control cables - Low Smoke Zero Halogen Flame Retardant or Fire Resistant cable types, used for underground outdoor installation shall be identified with the following designation:
LSZH
1
2
3
4
5
6
7
8
9
Colour
for example LSZH/MGT XLPE/IS & OS/LZSH/MLS/LSZH/GSWA/LZSH/7C/2.5 mm²/Black
- Core Insulation
XLPE MGT XLPE - EPR
MGT EPR -
S95
MGT S95
Flame retardant Cross (X) Linked Polyethylene Mica impregnated glass tape beneath extruded layer of XLPE Ethylene Propylene Rubber Mica impregnated glass tape beneath extruded layer of EPR Cross linked Silicone Rubber with treated glass fibre braid Mica impregnated glass tape beneath extruded layer of S95
Cores should be laid up with extruded Flame Retardant LSZH Compound filler for up to 5 cores. For 6 cores or more a wrapping of polyester tape is required.
- Screen OS IS & OS
Inner Jacket
LZSH
Overall Screen Individual and Overall Screen
Flame Retardant Low Smoke Zero Halogen Compound
Inner Sheath (Moisture & Chemical Barrier) LS MLS
Lead Sheath Multi-Layer Sheath (AL/HDPE/PE)
-
Bedding LZSH
-
Armour
GSWA
- Outer Jacket
LZSH EPR SHF2
Flame Retardant Low Smoke Zero Halogen Compound
Galvanised Steel Wire Armour.
Flame Retardant Low Smoke Zero Halogen Compound equivalent EPR, LSZH. equivalent Silicone Rubber, LSZH.
- Number of Cores
2C, 3C, 4C, 7C, 11C, 19C, 27C, 37C
- CSA of each Conductor
2.5mm² minimum or state the alternative size.
Outer jacket colour shall be as per application. Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner jacket and/or without armour.
Document No: AGES-SP-04-006
Rev. No: 1 Page 55 of 148
FIBRE OPTIC CABLE FOR OUTDOOR ABOVE GROUND INSTALLATION
Fibre Optic cables:
LSZH
1
2
3
4
5
6
7
8
Colour
for example LSZH/SMF OS2/PBT 6/Tape/AT/LSZH1/GSWA/LZSH/24//Black
- Fibre Type and Glass Fibre Grade Code
SMF- MMF- OM1- OM2-
Single mode glass fibres Multi-mode glass fibres Grade 1, 62.5/125µm mutli-mode Grade 2, 50/125µm mutli-mode
OM3- Grade 3, 50/125µm mutli-mode OM4- Grade 4, 50/125µm mutli-mode OS2- Grade S, single-mode
- Buffer Tubes and quantity of fibres per tube PolyButylene Terephthalate Halar Fluoroplastic equivalent to PBT or HF materials
PBT HF Other
Minimum 6 fibres per buffer tube. Each extruded buffer tube with a moisture resistant gel filling
compound.
Multiple buffer tubes are to be twisted around a dielectric material rod provided for central strength together with a filler core where required, flame retardant, LSZH.
- Separator / Inner Sheath
Foil Tape
LSZH
Aramid yarn for strength and aluminium foil core wrapping or separator Water blocking E-glass yarn and polyester tape together with Aramid strength members and a Rip cord. Flame Retardant Low Smoke Zero Halogen Compound sheath.
- Armour Tape
AT PT CST
Inner Jacket
LZSH1
LSZH2
Rip
- Armour
Aluminium Tape armour and a Rip cord Polyester Tape armour and a Rip cord Corrugated Steel Tape armour and a Rip cord
Flame Retardant Low Smoke Zero Halogen Compound Flame Retardant LSZH Compound together with Aramid strength members and a
cord.
GSWA CST
Galvanised Steel Wire Armour. Corrugated Steel Tape armour and a Rip cord.
- Outer Jacket
LZSH EPR SHF2
Flame Retardant Low Smoke Zero Halogen Compound equivalent EPR, LSZH. equivalent Silicone Rubber, LSZH.
Document No: AGES-SP-04-006
Rev. No: 1 Page 56 of 148
8) Number of Fibres (total)
6, 12, 24, 36, 48, 72, 96, 144
Outer jacket colour shall be as per application.
Fibres and Buffer Tubes shall be colour coded in accordance with EIA/TIA-598.
A printed legend shall be provided on the outer jacket of the FO cable at equal distances to identify the quantity and types of glass fibres within the cable.
Use the “ – “ (dash symbol) to indicate when the designation parameter is not applicable, as necessary for cables types without inner jacket and/or without armour.
Document No: AGES-SP-04-006
Rev. No: 1 Page 57 of 148
APPENDIX 3 CONSTRUCTION DETAILS FOR EACH CABLE TYPE
(A1) Single pair, collective screen, unarmoured, flame retardant. (XLPE/Coll Scr/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm2 min for analogue & digital signals. 2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White.
Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 58 of 148
123456
(A2) Multi-pair, Collective Screen, unarmoured, flame retardant. (XLPE/Coll Scr /LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.0 mm2 min for analogue & digital signals.
2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White. Each core printed with pair number throughout the cable at equal distances.
- Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound , LSZH. Colour: Black.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 59 of 148
123456
(A3) Single-triad, collective screen, unarmoured, flame retardant. (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm2 min for RTD, Winding Temperature & Vibration signals.
Identification
Black, Red & White.
- Insulation
CABLE:
Flame retardant material as per data sheet.
- Fillers
Flame retardant moisture resistant material , LSZH.
Cores are twisted together and covered with:
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: For the cables utilized for Vibration Signals Total capacitance of (core to core) + (core to screen) shall be less than 200nf/km.2.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 60 of 148
12345
(A4) Multi- triad, individual & collective screen, unarmoured, flame retardant. (XLPE/Ind & Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductor s
Identification
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet.
Black, Red & White. Each core printed with triad number through out the cable at equal distances.
- Insulation
Flame retardant material as per data sheet.
CABLE:
- Fillers
Flame retardant moisture resistant material , LSZH.
Cores are twisted into triads – each triad covered with:
- Ind screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Fillers
Flame retardant moisture resistant material , LSZH.
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: For the cables utilized for Vibration Signals Total capacitance of (core to core) + (core to screen) shall be less than 200nf/km.2. Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 61 of 148
1245673
(A5) Single-pair, collective screen, armoured, flame retardant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Identification
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm² min for analogue & digital signals. 2.5 mm2 for Solenoids, beacons, hooters Black and White.
Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape.
Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound, LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 62 of 148
1234567
(A6) Multi-pair, individual & collective screen, armoured, flame retardant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.0 mm2 min for analogue & digital signals.
Identification
Black and White. Each core printed with pair number throughout the cable at equal distances.
Insulation
Flame retardant material as per data sheet.
CABLE:
Ind screen tape.
Cores are twisted together and covered with:
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar
Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Binder Tape
PETP tape 50% overlap.
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound, LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 63 of 148
12456783
(A7) Multi-pair, collective screen, armoured, flame retardant. (XLPE/ Coll Scr/ SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for Digital (24VDC or Namur) signals.
2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White. Each core printed with pair number throughout the cable at equal distances.
Insulation
Flame retardant material as per data sheet .
CABLE:
Cores are twisted together and covered with:
- Binder Tape
PETP tape 50% overlap
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound , LSZH. Colour: Black.
- Armour
- Outer jacket
Galvanized steel wire Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 64 of 148
1234567
(A8) Single-triad, collective screen, armoured, flame retardant. (XLPE/Coll Scr/ SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm2 min for RTD, Winding Temperature & Vibration signals.
Identification
Black, Red & White.
- Insulation
CABLE:
Flame retardant material as per data sheet.
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound.
Colour: Black
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: For the cables utilized for Vibration Signals Total capacitance of (core to core)2 + (core to screen) shall be less than 200nf/km.2.
Document No: AGES-SP-04-006
Rev. No: 1 Page 65 of 148
1234567
(A9) Multi- triad, individual & collective screen, armoured, flame retardant. (XLPE/Ind & Coll Scr/ SWA/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductor s
Identification
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for Winding Temperature & Vibration Instrument signals.
Black, Red & White. Each core printed with triad number through out the cable at equal distances.
- Insulation
Flame retardant material as per data sheet .
CABLE:
- Ind screen
Cores are twisted together and covered with:
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Binder Tape
PETP tape 50% overlap.
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound.
Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: For the cables utilized for Vibration Signals Total capacitance of (core to core)2 + (core to screen) shall be less than 200nf/km.2.
Document No: AGES-SP-04-006
Rev. No: 1 Page 66 of 148
12456783
(A10) Single-pair, collective screen, armoured, external buried, flame retardant. (XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm² min for analogue & digital signals. 2.5 mm2 for Solenoids, beacons, hooters
Identification Black and White.
Insulation
Flame retardant material as per data sheet.
CABLE:
-
Fillers
-
Cable screen
Inner jacket
Inner Sheath
Cores are twisted together and covered with:
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound , LSZH. Colour: Black.
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound , LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 67 of 148
123456789
(A11) Multi-pair, individual & collective screen, armoured, external buried, flame retardant. (XLPE/Ind & Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Identification
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.0 mm2 for analogue & digital signals. Black and White.
Each core printed with pair number throughout the cable at equal distances.
Insulation
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant material as per data sheet.
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
-
Fillers
-
Coll screen
Inner jacket
Inner Sheath
-
Bedding
-
Armour
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 68 of 148
1256710114389
(A12) Single-triad, collective screen, armoured, external buried, flame retardant. (XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Identification
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm² min for analogue & digital signals. Black, Red and White.
Insulation
Flame retardant material as per data sheet.
CABLE:
-
Fillers
-
Cable screen
Inner jacket
Inner Sheath
Cores are twisted together and covered with:
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound , LSZH. Colour: Black.
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 69 of 148
345678912
(A13) Multi-triad, individual & collective screen, armoured, external buried, flame retardant. (XLPE/Ind & Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductor s
Identification
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for Winding Temperature & Vibration Instrument signals. Black, Red & White. Each core printed with triad number through out the cable at equal distances.
- Insulation Cores are twisted into triads – each triad covered with:
- Fillers
Flame retardant material as per data sheet.
Flame retardant moisture resistant material , LSZH.
- Ind screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
Triads twisted into multi-triads - Triads twisted (10 to 14 twists/m) together are covered with:
- Fillers
Flame retardant moisture resistant material, LSZH.
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
-
Inner Sheath
-
Bedding
-
Armour
-
Outer jacket
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire. Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 70 of 148
1256710114389
(B1) Single pair, collective screen, unarmoured, fire resistant. (Mica/XLPE/Coll Scr/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm2 min for Analogue or Digital signals (inside building) and ESD, F&G
and PA applications. 2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White.
Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Binder Tape
PETP tape 50% overlap.
- Cable screen
One tinned copper 0.50 mm min solid drain wire and aluminium backed (overall) Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Outer jacket Flame retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 71 of 148
123456
(B2) Multi-pair, Collective Screen, unarmoured, fire resistant. (Mica/XLPE/Coll Scr /LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.0 mm2 for Analogue or Digital signals (inside building) and ESD, F&G and
PA applications. 2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White. Each core printed with pair number throughout the cable at equal distances.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs - Pairs twisted (10 to 14 twists/m) together are covered with:
- Binder Tape
PETP tape 50% overlap.
- Cable Screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Outer jacket Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 72 of 148
123456
(B3) Single-triad, collective screen, non-armoured, fire resistant. (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm2 for RTD, Vibration signals etc for ESD and FGS applications.
Identification
Black, Red & White.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: For the cables utilized for Vibration Signals Total capacitance of (core to core) + (core to screen) shall be less than 200nf/km.2.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 73 of 148
12345
(B4) Multi- triad, individual & collective screen, unarmoured, fire resistant. (Mica/XLPE/Ind & Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor s
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for RTD, F&G Detector & Vibration Signals etc for ESD, F&G and PA applications.
Identification
Black, Red & White. Each core printed with triad number through out the cable at equal distances.
- Insulation linked
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into triads – each triad covered with: 3. Fillers
Flame retardant moisture resistant material , LSZH.
- Ind screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
Cores are twisted into triads - Triads twisted (10 to 14 twists/m) together are covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 74 of 148
1245673
(B5) Single-pair, collective screen, armoured, fire resistant.
(Mica/XLPE/Coll Scr/SWA/LSHF)
Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C Size 1.5 mm2 min for Analogue and Digital signals and ESD, F&G and PA
applications. 2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White.
- Insulation
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross linked polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Binder tape :
PETP tape 50% overlap.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Inner jacket
Flame retardant Low Smoke Zero Halogen compound , or equivalent EPR or equivalent S95 Rubber, LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 75 of 148
1234567
(B6) Multi-pair, individual & collective screen, armoured, fire resistant. (Mica/XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for Analogue signals for ESD, F&G and PA applications.
Identification Black and White.
Each core printed with pair number throughout the cable at equal distances.
- Insulation
CABLE:
- Ind screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross linked polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
One tinned copper 0.50 mm² min drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Insulating Tapes
Glass - Silk and polyester.
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Inner jacket
Flame retardant Low Smoke Zero Halogen compound. Colour: Black
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 76 of 148
12456783
(B7) Multi-pair, collective screen, armoured, fire resistant. (Mica/XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.0 mm2 for Analogue and Digital I/O of ESD, F&G and PA applications. 2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White. Each core printed with pair number throughout the cable at equal distances.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs - Pairs twisted (10 to 14 twists/m) together are covered with:
- Binder tape
PETP tape 50% overlap.backed
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed (overall) Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Inner jacket Flame retardant Low Smoke Zero Halogen compound.
Colour: Black
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331
Document No: AGES-SP-04-006
Rev. No: 1 Page 77 of 148
1234567
(B8) Single-triad, collective screen, armoured, fire resistant. (Mica/XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C Size: 1.5 mm2 min for RTD, F&G Detector & Vibration signals to ESD, F&G and PA applications.
Identification
Black, Red and White.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
-
Binder tape : PETP tape 50% overlap.backed
-
Cable screen One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape.
Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Inner jacket Flame retardant Low Smoke Zero Halogen compound.
Colour: Black
-
Armour Galvanized steel wire.
-
Outer jacket
Flame Retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 78 of 148
1234567
(B9) Multi- triad, individual & collective screen, armoured, fire resistant. (Mica/XLPE/Ind & Coll Scr/ SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor s
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for RTD, Winding Temperature, F&G Detector & Vibration signals and ESD, F&G and PA applications.
Identification
Black, Red & White. Each core printed with triad number through out the cable at equal distances.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into triads - Triads twisted (10 to 14 twists/m) together are covered with:
- Ind screen
One tinned copper 0.50 mm² min drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Insulating Tape
Glass - Silk and polyester.
- Coll screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 79 of 148
12456783
(B10) Single-pair, collective screen, armoured, external buried, fire resistant. (XLPE/Coll Scr/IS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm² min for analogue & digital signals and ESD, F&G and PA applications. 2.5 mm2 for Solenoids, beacons, hooters
Identification
Black and White.
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with: Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket Flame retardant Low Smoke Zero Halogen Compound
Inner Sheath
Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 80 of 148
123456789
(B11) Multi-pair, individual & collective screen, armoured, external buried, fire resistant. (XLPE/Ind & Coll Scr/IS/SWA/LSHF). Voltage Rating: 300/500V.
CORE:
- Conductors
Identification
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for analogue & digital signals and ESD, F&G and PA applications. Black and White.
Each core printed with pair number throughout the cable at equal distances.
2.
Insulation linked
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
-
Fillers
-
Coll screen
Inner jacket
Inner Sheath
-
Bedding
-
Armour
-
Outer jacket
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire. Flame Retardant Low Smoke Zero Halogen Compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 81 of 148
1256710114389
(B12) Single-triad, collective screen, armoured, external buried, fire resistant. (XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Identification
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Inner jacket
Inner Sheath
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm² min for RTD, F&G Detectors wired to ESD, FGS. Black, Red and White.
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 82 of 148
345678912
(B13) Multi-triad, individual & collective screen, armoured, external buried, fire resistant. (XLPE/Ind & Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductor s
Identification
-
Insulation linked
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for RTD, Vibration Instrument signals to ESD, FGS. Black, Red & White. Each core printed with triad number through out the cable at equal distances. Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into triads – each triad covered with: 3. Fillers 4. Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
-
Fillers
-
Coll screen
-
Inner jacket
-
Inner Sheath
-
Bedding
-
Armour
-
Outer jacket
.
Triads twisted into multi-triads - Triads twisted (10 to 14 twists/m) together are covered with:
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2. Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black. Galvanized steel wire. Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 83 of 148
1256710114389
(B14) Multi-triad, collective screen, armoured, fire resistant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductor s
Identification
-
Insulation linked
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for 3 wire Fire and Gas Detectors. Black, Red & White. Each core printed with triad number through out the cable at equal distances.
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into triads – each triad covered with: 3.
Fillers/Tape
Flame retardant moisture resistant material , LSZH.
CABLE:
- Fillers/Tape
- Coll screen
Triads twisted into multi-triads - Triads twisted (10 to 14 twists/m) together are covered with:
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 84 of 148
12456783
(B15) Multi-triad, collective screen, armoured, external buried, fire resistant. (XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductor s
Identification
-
Insulation linked
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: As per data sheet for 3 wire Fire and Gas Detectors. Black, Red & White. Each core printed with triad number through out the cable at equal distances. Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into triads – each triad covered with: 3. Fillers/Tape
Flame retardant moisture resistant material , LSZH.
CABLE:
-
Fillers/Tape
-
Coll screen
Inner jacket
Inner Sheath
- Bedding
Triads twisted into multi-triads - Triads twisted (10 to 14 twists/m) together are covered with:
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound LSZH. Colour: Black.
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
- Outer jacket
Galvanized steel wire. Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 85 of 148
12456910378
(C1) Single pair Thermocouple Extension, Type B, collective screen, unarmoured, flame retardant (Mica/XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Grey Negative Core: White
Insulation
Flame retardant material as per data sheet .
CABLE:
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 86 of 148
12345
(C2) Single pair Thermocouple Extension, Type K, collective screen, unarmoured, flame retardant (Mica/XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Green Negative Core: White
Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material.
- Cable screen
One tinned copper 0.50 mm² min drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 87 of 148
12345
(C3) Single pair Thermocouple Extension, Type T, collective screen, unarmoured, flame retardant (Mica/XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Brown Negative Core: White
Insulation
Flame retardant material as per data sheet .
CABLE:
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 88 of 148
12345
(C4) Single pair Thermocouple Extension, Type B, collective screen, armoured, flame retardant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Grey Negative Core: White
Insulation
Flame retardant material as per data sheet.
CABLE:
-
Fillers
-
Cable screen
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 89 of 148
1234567
(C5) Single pair Thermocouple Extension, Type K, collective screen, armoured, flame retardant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Green Negative Core: White
Insulation
Flame retardant material as per data sheet.
CABLE:
-
Fillers
-
Cable screen
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 90 of 148
1234567
(C6) Single pair Thermocouple Extension, Type T, collective screen, armoured, flame retardant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Brown Negative Core: White
Insulation
Flame retardant material as per data sheet.
CABLE:
-
Fillers
-
Cable screen
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 91 of 148
1234567
(C7) Multi-pair Thermocouple Extension, Type B, individual & collective screen, armoured, flame retardant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Grey Negative Core: White.
Identification
Insulation
Flame retardant material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
- Fillers
- Coll screen
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 92 of 148
125678943
(C8) Multi-pair Thermocouple Extension, Type K, individual & collective screen, armoured, flame retardant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Green Negative Core: White.
Identification
Insulation
Flame retardant material as per data sheet.
- Fillers
Ind screen
CABLE:
- Fillers
- Coll screen
Cores are twisted into pairs – each pair covered with: Flame retardant moisture resistant material One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material . One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 93 of 148
125678943
(C9) Multi-pair Thermocouple Extension, Type T, individual & collective screen, armoured, flame retardant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Brown Negative Core: White.
Identification
Insulation
Flame retardant material as per data sheet.
- Fillers
Ind screen
CABLE:
- Fillers
- Coll screen
Cores are twisted into pairs – each pair covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 94 of 148
125678943
(C10) Multi-pair Thermocouple Extension, Type B, individual & collective screen, armoured, external buried, flame retardant. (XLPE/Ind & Coll Scr/IS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Grey Negative Core: White.
Identification
Insulation
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant material as per data sheet.
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
- Fillers
- Coll screen
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
Inner Sheath
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 95 of 148
1256710114389
(C11) Multi-pair Thermocouple Extension, Type K, individual & collective screen, armoured, external buried, flame retardant. (XLPE/Ind & Coll Scr/IS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Green Negative Core: White.
Identification
Insulation
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant material as per data sheet.
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
- Fillers
- Coll screen
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
Inner Sheath
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 96 of 148
1256710114389
(C12) Multi-pair Thermocouple Extension, Type T, individual & collective screen, armoured, external buried, flame retardant. (XLPE/Ind & Coll Scr/IS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C.
Identification
Positive Core: Brown Negative Core: White.
Insulation
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant material as per data sheet.
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
- Fillers
- Coll screen
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
Inner Sheath
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 97 of 148
1256710114389
(D1) Single pair Thermocouple Extension, Type B, collective screen, unarmoured, fire resistant. (Mica/XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Grey Negative Core: White
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 98 of 148
12345
(D2) Single pair Thermocouple Extension, Type K, collective screen, unarmoured, fire resistant. (Mica/XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Green Negative Core: White
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 99 of 148
12345
(D3) Single pair Thermocouple Extension, Type T, collective screen, unarmoured, fire resistant. (Mica/XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Brown Negative Core: White
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Flame retardant moisture resistant material .
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 100 of 148
12345
(D4) Single pair Thermocouple Extension, Type B, collective screen, armoured, fire resistant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Grey Negative Core: White
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
- Armour
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 101 of 148
1234567
(D5) Single pair Thermocouple Extension, Type K, collective screen, armoured, fire resistant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Green Negative Core: White
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 102 of 148
1234567
(D6) Single pair Thermocouple Extension, Type T, collective screen, armoured, fire resistant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.5 mm² min Negative: Alumel Wire, Solid, Size: 1.5 mm² min Temperature rating 105°C.
Identification
Positive Core: Brown Negative Core: White
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Flame retardant moisture resistant material , LSZH.
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
- Armour
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 103 of 148
1234567
(D7) Multi-pair Thermocouple Extension, Type B, individual & collective screen, armoured, fire resistant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C.
Identification
Positive Core: Grey Negative Core: White.
Insulation linked
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
- Fillers
- Coll screen
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
- Armour
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 104 of 148
125678943
(D8) Multi-pair Thermocouple Extension, Type K, individual & collective screen, armoured, fire resistant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C.
Identification
Positive Core: Green. Negative Core: White.
Insulation linked
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
- Fillers
- Coll screen
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
- Armour
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 105 of 148
125678943
(D9) Multi-pair Thermocouple Extension, Type T, individual & collective screen, armoured, fire resistant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C.
Identification
Positive Core: Brown. Negative Core: White.
Insulation linked
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
- Fillers
- Coll screen
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
- Armour
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 106 of 148
125678943
(D10) Multi-pair Thermocouple Extension, Type B, individual & collective screen, armoured, external buried, fire resistant. (XLPE/Ind & Coll Scr/IS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type B Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Grey Negative Core: White. Mica impregnated glass tape beneath extruded layer of flame retardant cross
Identification
Insulation linked
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
-
Fillers
-
Coll screen
Inner jacket
Inner Sheath
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
-
Outer jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire. Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 107 of 148
1256710114389
(D11) Multi-pair Thermocouple Extension, Type K, individual & collective screen, armoured, external buried, fire resistant. (XLPE/Ind & Coll Scr/IS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type K Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Green Negative Core: White. Mica impregnated glass tape beneath extruded layer of flame retardant cross
Identification
Insulation linked
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
-
Fillers
-
Coll screen
Inner jacket
Inner Sheath
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are c overed with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
-
Outer jacket
Flame retardant Low Smoke Zero Halogen Compound Colour: Black. Galvanized steel wire. Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 108 of 148
1256710114389
(D12) Multi-pair Thermocouple Extension, Type T, individual & collective screen, armoured, external buried, fire resistant. (XLPE/Ind & Coll Scr/IS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductor Type T Positive: Chromel Wire, Solid, Size: 1.0 mm² min Negative: Alumel Wire, Solid, Size: 1.0 mm² min Temperature rating 105°C. Positive Core: Brown Negative Core: White. Mica impregnated glass tape beneath extruded layer of flame retardant cross
Identification
Insulation linked
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted into pairs – each pair covered with: 3. Fillers 4.
Ind screen
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
CABLE:
-
Fillers
-
Coll screen
Inner jacket
Inner Sheath
Pairs are twisted into multi-pairs - Pairs twisted (10 to 14 twists/m) together are covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
-
Outer jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black. Galvanized steel wire. Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 109 of 148
1256710114389
(E1) Communication, 2 wire applications, Single-pair, foil shield and braid, unarmoured, flame retardant. (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2. Temperature rating 90°C Size 1.5 mm2 min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Insulation
Flame retardant material as per data sheet.
CABLE:
- Foil
Cores are twisted together and covered with:
Overall foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Braid
Tinned copper wire braid in continuous contact with the tinned copper drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
(E2) Communication, 2wire applications, Multi-pair, foil shield, unarmoured, flame retardant. (XLPE/Ind & Coll Scr/LSHF)
Document No: AGES-SP-04-006
Rev. No: 1 Page 110 of 148
12345
Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2 and Foundation Fieldbus Cable Specification FF-844 H1. Temperature rating 90°C. Size: 1.0 mm² min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-). Each core printed with pair number throughout the cable at equal distances.
Insulation
Flame retardant material as per data sheet.
CABLE:
Ind Foil
Cores are twisted together and covered with:
Individual foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Coll Foil
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire .
- Outer jacket
Flame Retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 111 of 148
12453
(E3) Communication, 2wire applications, Single-pair, foil shield, armoured, flame retardant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Type A according to IEC 61158-2. Temperature rating 90°C Size 1.5 mm2 min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
- Insulation
Flame retardant material as per data sheet.
CABLE:
- Coll Foil
Cores are twisted together and covered with:
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Inner jacket
Flame retardant Low Smoke Zero Halogen Compound.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 112 of 148
123456
(E4) Communication, 2wire applications, Multi-pair, foil shield, armoured, flame retardant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-22 and Foundation Fieldbus Cable Specification FF-844 H1. Temperature rating 90°C. Size: 1.0 mm² min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-). Each core printed with pair number throughout the cable at equal distances.
Insulation
Flame retardant material as per data sheet.
CABLE:
Ind Foil
Cores are twisted together and covered with:
Individual foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Coll Foil
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 113 of 148
1243567
(E5) Communication, 2wire applications, Single-pair, foil shield, armoured, external buried, flame retardant. (XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 1.5 mm² min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Insulation
Flame retardant material as per data sheet.
CABLE:
- Coll Foil
Cores are twisted together and covered with:
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers and PETP binder tape.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
Inner Sheath
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 114 of 148
12367845
(E6) Communication, 2-wire applications, Multi-pair, foil shield, armoured, external buried, flame retardant. (XLPE/Ind & Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228 and Foundation Fieldbus Cable Specification FF-844 H1. Temperature rating 90°C. Size: 1.0 mm² min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Each core printed with pair number throughout the cable at equal distances.
2.
Insulation
Flame retardant material as per data sheet.
CABLE:
Ind Foil
Cores are twisted into pairs – each pair covered with:
Individual foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Coll Foil
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
Inner Sheath
- Bedding
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 115 of 148
124378956
(E7) RS232/422/485 Communication, 4wire applications, overall screen, unarmoured, flame retardant. (XLPE/OS/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
2Pair, Stranded annealed copper. Circular section, TypeA according to IEC 61158-
2
Temperature rating 90°C. Size: 1.5 mm² min for 4-wire serial communications.
Identification
Pair1 - White/Blue stripe and Blue/White stripe Pair2 - White/Orange stripe and Orange/White stripe.
Insulation
Flame retardant material as per data sheet .
CABLE:
Cores are twisted together and covered with:
- Coll Foil
Overall foil shield with one tinned copper drain wire .
- Braid
Tinned copper braid in continuous contact with the tinned copper drain wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 116 of 148
12453
(E8) RS232/422/485 Communication, 4wire applications, overall screen, armoured, flame retardant. (XLPE/OS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
2Pair, Stranded annealed copper, Circular section, Type A as per IEC 61158-2. Temperature rating 90°C. Size: 1.5 mm² min for 4-wire serial communications.
Identification
Pair1 - White/Blue stripe and Blue/White stripe Pair2 - White/Orange stripe and Orange/White stripe.
Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are twisted together and covered with:
- Coll Foil
Overall foil shield with one tinned copper drain wire .
- Braid
Tinned copper braid in continuous contact with the tinned copper drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound , LSZH. Colour: Black.
- Armour
Galvanized steel wire (see note).
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
(F1) Communication, 2wire applications, Single-pair, foil shield and braid, unarmoured, fire resistant. (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
Document No: AGES-SP-04-006
Rev. No: 1 Page 117 of 148
1245673
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2. Temperature rating 90°C Size 1.5 mm2 min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Coll Foil
Overall foil (aluminium tape plastic coated on one surface) shield with metal surface in contact with one tinned copper drain wire .
- Braid
Tinned copper wire braid in continuous contact with the tinned copper drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 118 of 148
12345
(F2) Communication, 2wire applications, Multi-pair, foil shield and braid, unarmoured, fire resistant. (XLPE/Ind & Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2 and Foundation Fieldbus Cable Specification FF-844 H1. Temperature rating 90°C. Size: 1.0 mm² min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-). Each core printed with pair number throughout the cable at equal distances.
Insulation
Mica impregnated glass tape beneath extruded layer of flame retardant cross linked Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
CABLE:
Ind Foil
Cores are twisted together and covered with:
Individual foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Coll Foil
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire .
- Braid
Tinned copper wire braid in continuous contact with the tinned copper drain wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 119 of 148
124635
(F3) Communication, 2wire applications, Single-pair, foil shield, armoured, fire resistant. (XLPE/Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2. Temperature rating 90°C Size 1.5 mm2 min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Coll Foil
Overall foil (aluminium tape plastic coated on one surface) shield with metal surface in contact with one tinned copper drain wire .
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound , LSZH Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 120 of 148
123456
(F4) Communication, 2wire applications, Multi-pair, foil shield, armoured, fire resistant. (XLPE/Ind & Coll Scr/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2 and Foundation Fieldbus Cable Specification FF-844 H1. Temperature rating 90°C Size 1.0 mm2 min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Insulation linked
CABLE:
Ind Foil
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
Individual foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Coll Foil
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire .
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 121 of 148
1243567
(F5) Communication, 2wire applications, Single-pair, foil shield, armoured, external buried, fire resistant. (XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2. Temperature rating 90°C Size 1.5 mm2 min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Insulation linked
CABLE:
- Coll Foil
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers and PETP binder tape.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
Inner Sheath
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 122 of 148
12367845
(F6) Communication, 2wire applications, Multi-pair, foil shield, armoured, external buried, fire resistant. (XLPE/Ind & Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Type A according to IEC 61158-2 and Foundation Fieldbus Cable Specification FF-844 H1. Temperature rating 90°C Size 1.0 mm2 min for `Foundation Fieldbus’ and RS-485 signals.
Identification
Orange (+) and Blue (-).
Insulation linked
CABLE:
Ind Foil
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
Individual foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire . Together with Flame retardant moisture resistant material fillers.
- Coll Foil
Collective foil (aluminium foil, polyester tape coated on one surface) shield with metal surface in contact with one tinned copper drain wire .
Inner jacket
Inner Sheath
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
-
Outer jacket
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black. Galvanized steel wire. Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 123 of 148
124378956
(F7) RS232/422/485 Communication, 4wire applications, overall screen, unarmoured, fire resistant. (XLPE/OS/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductors
2Pair, Stranded annealed copper. Circular section, TypeA according to IEC 61158-
Temperature rating 90°C. Size: 1.5 mm² min for 4-wire serial communications.
Identification
Pair1 - White/Blue stripe and Blue/White stripe Pair2 - White/Orange stripe and Orange/White stripe.
Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Coll Foil
Overall foil shield with one tinned copper drain wire.
- Braid
Tinned copper braid in continuous contact with the tinned copper drain wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 124 of 148
12453
(F8) RS232/422/485 Communication, 4wire applications, overall screen, armoured, fire resistant. (XLPE/OS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
-
Conductors
2Pair, Stranded annealed copper. Circular section, TypeA according to IEC 61158-
Temperature rating 90°C. Size: 1.5 mm² min for 4-wire serial communications.
Identification
Pair1 - White/Blue stripe and Blue/White stripe Pair2 - White/Orange stripe and Orange/White stripe.
Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Coll Foil
Overall foil shield with one tinned copper drain wire.
- Braid
Tinned copper braid in continuous contact with the tinned copper drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire (see note).
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 125 of 148
1245673
(G1) Two core, Collective Screen, unarmoured, flame retardant (Control Cable). (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red and Black.
- Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
(G2) Two core, armoured, flame retardant (Control Cable). (XLPE/SWA/ LSHF) Voltage Rating: 300/500V
Document No: AGES-SP-04-006
Rev. No: 1 Page 126 of 148
12345
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red and Black.
- Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are covered with:
- Fillers
Flame retardant Low Smoke Zero Halogen Compound.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’.
(G3) Multi-core, Collective Screen, unarmoured, flame retardant (Control Cable). (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
Document No: AGES-SP-04-006
Rev. No: 1 Page 127 of 148
12345612345
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
- Insulation
Flame retardant material as per data sheet.
CABLE:
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 128 of 148
(G4) Multi - core, armoured, flame retardant (Control Cable). (XLPE/SWA/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
- Insulation
Flame retardant material as per data sheet.
CABLE:
- Fillers
Cores are covered with:
Cores laid up with extruded PVC filler for 5 cores. For 6 cores or more wrapping of polyester tape.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 129 of 148
123456
(G5) Multi-core, collective screen, armoured, external buried, flame retardant (Control Cable). (XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
Insulation
Flame retardant material as per data sheet.
CABLE:
-
Fillers
-
Cable screen
Inner jacket
Inner Sheath
Cores are twisted together and covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
- Bedding
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’
Document No: AGES-SP-04-006
Rev. No: 1 Page 130 of 148
123456789
(G6) Two core, Collective Screen, armoured, flame retardant (Control Cable). (XLPE/Coll Scr/SWA/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red and Black.
- Insulation
Flame retardant material as per data sheet.
CABLE:
- Fillers
Halogen
Cores are covered with:
Cores laid up with extruded PVC filler or Flame retardant Low Smoke Zero
Compound ,LSZH.
- Cable Screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’.
(G7) Multi-core, Collective Screen, armoured, flame retardant (Control Cable). (XLPE/Coll Scr/SWA/ LSHF) Voltage Rating: 300/500V
Document No: AGES-SP-04-006
Rev. No: 1 Page 131 of 148
1234567
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
- Insulation
Flame retardant material as per data sheet.
CABLE:
- Fillers
Halogen
Cores are twisted together and covered with:
Cores laid up with extruded PVC filler or Flame retardant Low Smoke Zero
Compound ,LSZH.
- Cable Screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’.
.
Document No: AGES-SP-04-006
Rev. No: 1 Page 132 of 148
1234567
(H1) Two core, Collective Screen, unarmoured, fire resistant (Control Cable). (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red and Black.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame Retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 133 of 148
12345
(H2) Two core, armoured, fire resistant (Control Cable). (Mica/XLPE/SWA/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for Fire and Gas (Sounder/Beacon), Digital Output & Solenoid signals and ESD, F&G and PA applications.
Identification
Red and Black.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound or equivalent EPR or equivalent S95 Rubber, LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 134 of 148
123456
(H3) Multi-core, Collective Screen, unarmoured, fire resistant (Control Cable). (XLPE/Coll Scr/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals.
Identification
Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
- Cable screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Note: This cable type shall be only utilized for indoor application where the cable is installed and fully routed within the same building.
Document No: AGES-SP-04-006
Rev. No: 1 Page 135 of 148
12345
(H4) Multi-core, armoured, fire resistant (Control Cable). (Mica/XLPE/SWA/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for Fire and Gas (Sounder/Beacon), Digital Output & Solenoid signals and ESD, F&G and PA applications.
Identification
Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Fillers
Flame retardant moisture resistant material , LSZH.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound or equivalent EPR or equivalent S95 Rubber, LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
.
Document No: AGES-SP-04-006
Rev. No: 1 Page 136 of 148
123456
(H5) Multi-core, collective screen, armoured, external buried, fire resistant (Control Cable).
(XLPE/Coll Scr/LS/SWA/LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Identification
Insulation linked
CABLE:
-
Fillers
-
Cable screen
Inner jacket
Inner Sheath
Stranded annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm² min for control signals, Fire and Gas (Sounder/Beacon), Digital Output & Solenoid signals and ESD, F&G and PA applications. Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with: Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire. Flame retardant Low Smoke Zero Halogen Compound or equivalent EPR or equivalent S95 Rubber, LSZH. Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black. Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
Document No: AGES-SP-04-006
Rev. No: 1 Page 137 of 148
123456789
(H6) Two core, Collective Screen, armoured, fire resistant (Control Cable). (Mica/XLPE/Coll Scr/SWA/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for Fire and Gas (Sounder/Beacon), Digital Output & Solenoid signals and ESD, F&G and PA applications.
Identification
Red and Black.
- Insulation linked
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
CABLE:
Cores are covered with:
-
Fillers
-
Cable shield
Inner jacket
Flame retardant moisture resistant material , LSZH. One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire
Flame retardant Low Smoke Zero Halogen Compound or equivalent EPR or equivalent S95 Rubber, LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire Resistant to IEC 60331.
.
Document No: AGES-SP-04-006
Rev. No: 1 Page 138 of 148
1234567
(H7) Multi-core, Collective Screen, armoured, fire resistant (Control Cable). (XLPE/Coll Scr/SWA/ LSHF) Voltage Rating: 300/500V
CORE:
- Conductors
Standed annealed copper. Circular section, Class 2 according to IEC 60228. Temperature rating 90°C. Size: 2.5 mm2 min for control signals, Digital Output & Solenoid signals and ESD, F&G and PA applications.
Identification
Red, Black, Brown, Blue for 4 cores. White with Black core numbers for 7, 12, 19, 25 and 37 cores. Each core printed with a number throughout the cable at equal (150mm) distances.
- Insulation linked
CABLE:
Mica impregnated glass tape beneath extruded layer of flame retardant cross
Polyethylene (XLPE) or equivalent Ethylene Propylene Rubber (EPR) or equivalent Silicone Rubber (S95) or material as per data sheet.
Cores are twisted together and covered with:
- Fillers
Flame retardant Low Smoke Zero Halogen Compound ,LSZH.
- Cable Screen
One tinned copper 0.50 mm² min solid drain wire and aluminium backed Mylar tape. Tape shall be helically wrapped with 25% overlap. Aluminium tape shall be in continuous contact with the drain wire.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound ,LSZH. Colour: Black.
- Armour
Galvanized steel wire.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame retardant to IEC 60332.Pt.3.Cat`A’.
Document No: AGES-SP-04-006
Rev. No: 1 Page 139 of 148
1234567
(I1) Fibre Optic cable (24Fibres), flame retardant, indoor.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Minimum 6 fibres per buffer tube.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
- Buffer tubes
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded tube with a moisture resistant gel filling compound. Multiple buffer tubes are twisted around a GRP (or equivalent dielectric material) rod provided for central strength and a filler core, flame retardant LSZH.
Tube Identification Colour Coded in accordance with EIA/TIA-598. Tube colours shall not be repeated. Each tube shall be a solid colour and be marked with a number.
CABLE:
- Separator
Water blocking E-glass yarn and polyester tape, together with Aramid strength members and a Rip cord.
- Armour Tape
Aluminium or Polyester or Corrugated steel tape armour and a Rip cord.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 140 of 148
12345
(I2) Fibre Optic cable (24Fibres), flame retardant, outdoor.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Minimum 6 fibres per buffer tube.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
- Buffer tubes
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded tube with a moisture resistant gel filling compound. Multiple buffer tubes are twisted around a GRP (or equivalent dielectric material) rod provided for central strength and a filler core, flame retardant LSZH.
Tube Identification Colour Coded in accordance with EIA/TIA-598. Tube colours shall not be repeated. Each tube shall be a solid colour and be marked with a number.
CABLE:
- Separator
Water blocking E-glass yarn or Aramid yarn and polyester tape.
- Armour Tape
Aluminium or Polyester or Corrugated steel tape armour and a Rip cord.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound) Together with Aramid strength members and a Rip cord. Colour: Black.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 141 of 148
123456
(I3) Fibre Optic cable (24Fibres), flame retardant, outdoor, armoured.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Minimum 6 fibres per buffer tube.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
- Buffer tubes
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded tube with a moisture resistant gel filling compound. Multiple buffer tubes are twisted around a GRP (or equivalent dielectric material) rod provided for central strength and a filler core, flame retardant LSZH.
Tube Identification Colour Coded in accordance with EIA/TIA-598. Tube colours shall not be repeated. Each tube shall be a solid colour and be marked with a number.
CABLE:
- Separator
Water blocking E-glass yarn or Aramid yarn and polyester tape.
- Armour Tape
Aluminium or Polyester or Corrugated steel tape armour and a Rip cord.
- Inner jacket
Flame retardant Low Smoke Zero Halogen Compound , LSZH Colour: Black.
- Armour
Galvanised Steel Wire Armour or equivalent steel tape armour and a Rip cord.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 142 of 148
1234567
(I4) Fibre Optic cable (2 up to 24Fibres), flame retardant, indoor or outdoor, armoured.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Maximum of 24 individual fibres. Temperature rating 70°C.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded loose tube with a moisture resistant gel filling compound. Flame retardant LSZH.
- Uni-Tube
CABLE:
- Separator
Water blocking E-glass yarn or Aramid yarn and polyester tape.
- Armour Tape
Aluminium or Corrugated steel tape armour and a Rip cord.
- Outer jacket
Flame retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 143 of 148
12345
(I5) Fibre Optic cable (2 up to 24Fibres), armoured, external buried, flame retardant.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Minimum 6 fibres per buffer tube.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
- Buffer tubes
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded tube with a moisture resistant gel filling compound. Multiple buffer tubes are twisted around a GRP (or equivalent dielectric material) rod provided for central strength and a filler core, flame retardant LSZH.
Tube Identification Colour Coded in accordance with EIA/TIA-598. Tube colours shall not be repeated. Each tube shall be a solid colour and be marked with a number.
CABLE:
- Separator
Water blocking E-glass yarn or Aramid yarn and polyester tape.
- Armour Tape
Aluminium or Polyester or Corrugated steel tape armour and a Rip cord.
Inner jacket
Inner Sheath
Flame retardant Low Smoke Zero Halogen Compound , LSZH Colour: Black. Lead Sheath (or Lead pipe). A multi-layered Inner Sheath (AL/HDPE/PA instead of lead sheath) will be considered if the multi-layer sheath provides the same protection as a lead sheath for hydrocarbons, chemical and solvents, saline water ingress and vermin protection, as per BS 50288-7 section 4.18.2.
-
Bedding
-
Armour
-
Outer jacket
. Flame retardant Low Smoke Zero Halogen Compound. Colour: Black Galvanised Steel Wire Armour or equivalent steel tape armour and a Rip cord. Flame retardant Low Smoke Zero Halogen compound
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 144 of 148
123456789
(J1) Fibre Optic cable (24Fibres), fire resistant, indoor.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Minimum 6 fibres per buffer tube.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
- Buffer tubes
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded tube with a moisture resistant gel filling compound. Multiple buffer tubes are twisted around a GRP (or equivalent dielectric material) rod provided for central strength and a filler core, flame retardant LSZH.
Tube Identification Colour Coded in accordance with EIA/TIA-598. Tube colours shall not be repeated. Each tube shall be a solid colour and be marked with a number.
CABLE:
- Separator
Water blocking E-glass yarn and polyester tape, together with Aramid strength members and a Rip cord.
- Armour Tape
Aluminium or Polyester or Corrugated steel tape armour and a Rip cord.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 145 of 148
12345
(J2) Fibre Optic cable (24Fibres), fire resistant, outdoor.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Minimum 6 fibres per buffer tube.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
- Buffer tubes
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded tube with a moisture resistant gel filling compound. Multiple buffer tubes are twisted around a GRP (or equivalent dielectric material) rod provided for central strength and a filler core, flame retardant LSZH.
Tube Identification Colour Coded in accordance with EIA/TIA-598. Tube colours shall not be repeated. Each tube shall be a solid colour and be marked with a number.
CABLE:
- Separator
Water blocking E-glass yarn or Aramid yarn and polyester tape.
- Armour Tape
Aluminium or Polyester or Corrugated steel tape armour and a Rip cord.
Inner jacket
Flame retardant Low Smoke Zero Halogen Compound) Together with Aramid strength members and a Rip cord. Colour: Black.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire resistant to IEC 60331 . Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 146 of 148
123456
(J3) Fibre Optic cable (24Fibres), fire resistant, outdoor, armoured.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Minimum 6 fibres per buffer tube.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
- Buffer tubes
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded tube with a moisture resistant gel filling compound. Multiple buffer tubes are twisted around a GRP (or equivalent dielectric material) rod provided for central strength and a filler core, flame retardant LSZH.
Tube Identification Colour Coded in accordance with EIA/TIA-598. Tube colours shall not be repeated. Each tube shall be a solid colour and be marked with a number.
CABLE:
- Separator
Water blocking E-glass yarn or Aramid yarn and polyester tape.
- Armour Tape
Aluminium or Polyester or Corrugated steel tape armour and a Rip cord.
Inner jacket
- Armour
Flame retardant Low Smoke Zero Halogen Compound or equivalent EPR or equivalent S95 Rubber, LSZH to IEC 60332. Pt.3. Cat`A’. Fire resistant to IEC 60331. Together with Aramid strength members and a Rip cord. Colour: Black. Galvanised Steel Wire Armour or equivalent steel tape armour and a Rip cord.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire resistant to IEC 60331.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 147 of 148
1234567
(J4) Fibre Optic cable (2 up to 24Fibres), fire resistant, indoor or outdoor, armoured.
CORE:
- Fibres
Single mode fibre or Multimode fibres, to suit the glass type needed for the application. Maximum of 24 individual fibres. Temperature rating 70°C.
Fibre Identification Colour Coded in accordance with EIA/TIA-598. Fibre colours shall not be repeated.
1st group of 12 fibres are solid colours. 2nd group of 12 fibres are solid colours with a stripe.
Flame retardant PolyButylene Terephthalate (PBT) or Halar Fluoroplastic or equivalent extruded loose tube with a moisture resistant gel filling compound. Flame retardant LSZH.
- Uni-Tube
CABLE:
- Separator
Water blocking E-glass yarn or Aramid yarn and polyester tape.
- Armour Tape
Aluminium or Corrugated steel tape armour and a Rip cord.
- Outer jacket
Flame retardant Low Smoke Zero Halogen Compound.
Entire cable assembly shall be Flame Retardant to IEC 60332. Pt.3. Cat`A’ and Fire resistant to IEC 60331.
Colour Coded in accordance with EIA/TIA-598 with a printed legend on the outer jacket of the cable at equal distances to identify the quantity and types of glass fibres within the cable.
Document No: AGES-SP-04-006
Rev. No: 1 Page 148 of 148
12345