RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 1 OF 38
ADNOC GAS
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY Contract No.
4700022871
JV TJN RUWAIS Contract No
215122C
Document Class
Class 1
Document Category (for Class 1)
Category 2
OPERATING CENTER Contract No.
OPERATING CENTER Doc Ref.
0D
0C
0B
0A
0
ICR – Issued for Client Review
06-Feb-25 C. Thai, G. Rao
B. Schott
S. Deilles
ICR – Issued for Client Review
14-Nov-24 C. Thai, G. Rao
B. Schott
S. Deilles
ICR – Issued for Client Review
17-Jun-24
B. Schott
A de Vandière S. Deilles
ICR – Issued for Client Review
30-Apr-24
B. Schott
A de Vandière S. Deilles
ICR – Issued for Client Review
04-Apr-24
B. Schott
S. Deilles C. Louanchi
Rev.
Revision Purpose
Date
Prepared by
Checked by
Approved by
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 2 OF 38
Table of Contents
Contents
Page
1.0 INTRODUCTION … 4 1.1 Scope of the Document … 4 1.2 Holds List … 4 1.3 References … 5 1.4 Definitions and Abbreviations … 5 2.0 EQUIPMENT NUMBERING … 6 2.1 Main Equipment … 6 2.2 Auxiliary Equipment … 7 3.0 ELECTRICAL EQUIPMENT NUMBERING … 8 3.1 Electrical Equipment In buildings … 8 3.2 Electrical Equipment In field … 8 3.2.1 Motor Equipment’s … 9 3.2.2 Lighting & small power … 9 3.3 Electrical Cables … 10 3.4 Cathodic protection … 11 3.5 Cable Trays / Trenches and Earth Pit … 12 INSTRUMENTATION NUMBERING … 13 4.0 5.0 FIRE AND GAS TAGGING RULES … 15 6.0 TELECOMMUNICATION AND SECURITY NUMBERING … 17 7.0 PROCESS & PIPING LINE NUMBERING … 20 8.0 PIPING CLASSES … 20 9.0 PIPING SPECIALTIES AND MANUAL VALVE … 21 9.1 PIPING SPECIALTIES … 21 9.2 MANUAL VALVE … 21 9.3 EQUIPMENT NOZZLE… 22 9.4 Utility Station … 22 10.0 TECHNICAL BUILDINGS, INDUSTRIAL AND NON-INDUSTRIAL BUILDINGS … 23 11.0 INSULATION … 23 12.0 HVAC EQUIPMENT IDENTIFICATION … 24 13.0 CIVIL ASSET NUMBERING … 25 14.0 MARINE … 27 15.0 FIRE FIGHTING AND SAFETY EQUIPMENT NUMBERING … 29 16.0 Attachments … 30 16.1 Attachment 1 - Unit Numbering … 30 16.2 Attachment 2 - Service - Fluid Codes … 32 16.3 Attachment 3 - Equipment Code identification … 33 16.4 Attachment 4 - Electrical Equipment Type Code … 34 16.5 Attachment 5 - Electrical - Voltage Code … 35 16.6 Attachment 6 - Piping Specialty … 36 16.7 Attachment 7 - HVAC - EQUIPMENT TYPE PREFIX … 37 16.8 Attachment 8 - HVAC - EQUIPMENT TYPE MODIFIER … 37 16.9 Attachment 9 – Manual Valve Type Code … 38
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 3 OF 38
Table of Changes compared to previous revision (for Procedures and Job Specifications only)
Paragraph
Modification description
Remarks / Origin
2.2
3.1
3.5
5.0
9.2
9.4
12
16.1
16.2
16.3
16.7
16.8
16.9
Section updated with Example
Description in table updated
Section added
Section updated Example
Section updated
Section added
Description in Section updated
Unit Desc Updated
Description in table updated
Table updated
Table updated
Table updated
Table updated
13, 14
Cross references updated
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 4 OF 38
1.0
INTRODUCTION
The ADNOC Ruwais LNG Project is a two train, near net-zero electrically driven LNG facility, targeting international markets. The feed gas for the project is supplied from the Habshan Gas Processing Plant via a new export gas pipeline. The plant will have two 4.8 MTPA (nominal capacity) electric driven LNG Trains with associated LNG storage/marine export facilities and utilities.
Figure 1 – Project Context
The ADNOC Ruwais LNG Project foresees the following main components at the facility:
• Onshore LNG Liquefaction facilities for 2 x 4.8 MTPA electrically driven LNG Trains (9.6MTPA
total)
• Common facilities including inlet receiving facilities, LNG storage, BOG handling, flare,
refrigerant storage and support buildings.
• Utilities to support the facilities including import power from the national grid.
• Marine facilities for LNG export and bunkering.
1.1
Scope of the Document
This document aims to establish a unified tagging system for the Ruwais LNG plant including jetty.
1.2
Holds List
HOLD
DESCRIPTION
1
2
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 5 OF 38
1.3
References
[1] TE-PR-064 Procedure of Tagging Of Assets [2] RLNG-000-IC-PP-0001 (215122C-000-JSD-1500-0001) I&C System numbering procedure [3] RLNG-000-TE-PP-0001 (215122C-000-JSD-1530-0001) Telecommunication numbering
procedure
[4] RLNG-000-PI-RP-1021 (FEED ref: 359665-0809-070-SP-1300-001 / CTR ref: 215122C-000-
JSD-1300-1021) Specification for Piping Material Service Classes Index
[5] RLNG-000-PI-RP-1022 (FEED ref: 359665-0809-070-SP-1300-002 / CTR ref: 215122C-000-
JSD-1300-1022) Specification for Piping Material Classes
[6] RLNG-000-IL-SP-0001 (FEED ref: 359665-0809-070-SP-9999-011 / CTR ref: 215122C-000-
JSD-2200-0001) Specification for Thermal and Acoustic Insulation
[7] RLNG-000-IL-SP-0002 (CTR ref: 215122C-000-JSD-2250-0001) Specification for PFP/CSP
Material for Piping and Equipment
[8] RLNG-000-PM-PP-3107 (215122C-000-PP-3107) Geographical Work breakdown Structure [9] RLNG-000-PM-NM-0001 (215122C-000-NM-0001) Equipment List [10] RNLG-000-CV-NM-0001 (215122C-000-NM-2000-0001) Buildings List [11] RLNG-000-HS-DWG-0001 Overall Fire Zone Drawing [12] RLNG-000-HS-BOD-0201 Fire and Gas Design Basis
1.4
Definitions and Abbreviations
COMPANY
CONTRACTOR
EPC ADOC POC YOC
ABU DHABI NATIONAL OIL COMPANY (ADNOC) P.J.S.C. TJN Ruwais, Joint Venture of Technip Energies France-Abu Dhabi, JGC Corporation and National Marines Dredging Company (NMDC) Engineering Procurement Construction Abu Dhabi Operating center - National Marines Dredging Company Paris Operating Center - Technip Energies Yokohama Operating center - JGC Corporation
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 6 OF 38
2.0
EQUIPMENT NUMBERING
2.1
Main Equipment
The Process Equipment Numbering shall be:
Unit number Hyphen separator Equip. code identification Hyphen separator
UUU
X(X)
Sequential Number
NNN
Suffix Code
(A)
Refer to Attachment 1 - Unit Numbering
Refer to Attachment 3 - Equipment Code identification
3 digits. Wherever necessary, the sequential numbering can be adapted to ease the readability. For instance, in the liquefaction unit:
- Feed Gas Path - Sequential number in “000”
- MR Path - Sequential number in “100”
- Propane Path - Sequential number in “200” A, B, C, D, …etc.
Example:
111-E-005 Main Cryogenic heat exchanger, in unit 111
111-V-101 HP MR Separator, vessel from Unit 111
111-K-101 LP MR Compressor, from Unit 111
111-E-105 LP MR Compressor Aftercooler, from Unit 111
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 7 OF 38
2.2
Auxiliary Equipment
The auxiliary numbering will apply only to the equipment that are, on PIDs, within a rectangle identified as “by VENDOR”. The main equipment is numbered as “Process Equipment”. The other equipment, in the rectangle and supplied by the Vendor, will have an “Auxiliary Numbering”. The Auxiliaries of Process Equipment Numbering shall be:
Full Parent Tag Hyphen separator Equip. code identification Sequential Number
UUU-X(X)-NNN(A)
Refer to 2.1 - Main Equipment
X(X)(X)
MM
Refer to Attachment 3 - Equipment Code identification 2 digits
For instance, for the compressors:
111-K-101
LP MR Compressor (parent tag)
111-K-101-Z05
LP MR Compressor Lube Oil Skid
111-K-101-E02
LP MR Compressor Lube Oil Cooler
111-K-101-Z03
LP MR Compressor Dry Gas Seal System
One application for instance: Cooler bays and fans/fan motors
111-E-105 (former 11K-31-E1) LP MR Compressor Aftercooler
Induced Draft Air Cooler 1
-
Bay 111-E-105-B09
for 09th Bay
-
Fan 111-E-105-B09-FA2 for 2nd Fan in Bay 09
-
Fan 111-E-105-B09-FAM2 for 2nd Fan motor in Bay 09
Compressor Lube oil Cooler
060-K-001A-E01 Compressor Lube oil Cooler 1
060-K-001A-E01-FA01 Compressor Lube oil Cooler 1 Fan 1
060-K-001A-E01-FAM01 Compressor Lube oil Cooler 1 Fan 1 Motor
All equipment tags are listed in: [9] - RLNG-000-PM-NM-0001 (215122C-000-NM-0001) Equipment List
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 8 OF 38
3.0
ELECTRICAL EQUIPMENT NUMBERING
3.1
Electrical Equipment In buildings
The numbering shall be:
Building Tag
BB(B)NN(A)
Hyphen separator
Electrical Equipment Code
Hyphen separator
Voltage Code
Hyphen separator Sequential Number Letters when necessary (e.g redundant equipment)
Examples:
YYYY
Z
NNN
(A)
Building tag without hyphen, Refer to section 10.0 TECHNICAL BUILDINGS, INDUSTRIAL AND NON- INDUSTRIAL BUILDINGS.
Refer to Attachment 4 - Electrical Equipment Type Code
The voltage code refers to the voltage of the higher rated electrical equipment. Refer to Attachment 5 - Electrical - Voltage Code.
3 digits
- SS11A-ASD-C-001
Adjustable Speed Drive in E-house SS-11A
- SS11B-SWG-C-001
13.8kV switchgear in E-house SS-11B
- SS11C-MCC-F-001
Motor Control Center (690/415 LV Switchgear) in E-house SS-11C
3.2
Electrical Equipment In field
The numbering shall be:
Unit number
Hyphen separator
Electrical Equipment Code
Hyphen separator Sequential Number Letters when necessary (e.g redundant equipment)
Examples:
UUU
Refer to Attachment 1 - Unit Numbering
YYYY
NNN
(A)
Refer to Attachment 4 - Electrical Equipment Type Code
3 digits
111-LP-001 First lighting panel in unit 111
111-WO-007 Seventh Welding Outlet in unit 111
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 9 OF 38
3.2.1 Motor Equipment’s
Main Equipment tag in Field
Hyphen separator
Electrical Equipment Code
Sequential Number
Letters when necessary (e.g redundant equipment)
Examples:
UUU-X(X)- NNN(A)
Refer to 2.1 - Main Equipment where XX = PM for Pump motor from Attachment 3 - Equipment Code identification
YYYY
(NN)
Refer to Attachment 4 - Electrical Equipment Type Code 2 digits - optional where there is more than one auxiliary equipment
(A)
Alphabet
120-PM-101A-LCS
Control station for motor 120-PM-101A
120-PM-101A-JB
Power JB for motor 120-PM-101A
120-PM-101A-SH01
First Space heater for motor 120-PM-101A
120-PM-101A-SH02 Second Space heater for motor 120-PM-101A
3.2.2 Lighting & small power
Main Electrical Equipment tag in Field Hyphen separator Circuit Number Hyphen separator
UUU-YYYY- NNN(A)
MM
Refer to 3.2 Electrical Equipment In field
2 digits, Sequential
Electrical Equipment Code
Sequential Number
YYYY
NN
Refer to Attachment 4 - Electrical Equipment Type Code 2 digits
Examples:
120-LDB-001-02-LF03 Lighting fixtures from lighting distribution board 120-LDB-001 (3rd light from 2nd circuit)
120-LDB-001-02-JB03 lighting panel 120-LDB-001)
Intermediate Lighting junction box (3rd light JB from 2nd circuit of
120-SDB-001-05-SO04 Socket Outlet from small power distribution board 120-SDB-001 (4th socket outlet from 5th circuit)
120-SDB-001-05-JB04 4th socket outlet JB from 5th circuit of small power distribution board 120-SDB-001
120-SDB-001-03-MJB02 2nd Junction box 3 phases from 3rd circuit of small power distribution board 120-SDB-001
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 10 OF 38
3.3
Electrical Cables
Main Electrical Equipment tag in Field
UUU-YYYY- NNN(A)
Refer to 3.2 Electrical Equipment In field
or (depending on the case)
In building Hyphen separator Cable Service Code Sequential Number
Phase Identification Nb
BB(B)-NN(A)- YYYY-Z-NNN(A)
Refer to 3.1 Electrical Equipment In buildings
X NN
(ZZ)
One letter from table below 2 digits
(L1, L2, L3 for single core cables)
Where X stands for:
Cable Service Code Description
P
C
A
F
E
Power
Control
Analogue Measurement (CT, RTD, …)
Fibre Optic
Earthing cable
Note: Cable identification refers to end user equipment.
Examples:
-
Power cable: 120-PM-001A-P01
-
Control cable: 120-PM-001A-C01
-
Single core cable 1st phase: SST1-TR-C-001A-P01L1
-
Single core cable 2nd phase: SST1-TR-C-001A-P01L2
-
Single core cable 3rd phase: SST1-TR-C-001A-P01L3
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 11 OF 38
3.4
Cathodic protection
Main Electrical Equipment tag in Field
UUU-YYYY- NNN(A)
Refer to 3.2 Electrical Equipment In field
Where YYYY = TRU for Transformer Rectifier Unit
or (depending on the case)
In building
Hyphen separator Cathodic Electrical Equipment Code Sequential Number
BB(B)-NN(A)- YYYY-Z-NNN(A)
Refer to 3.1 Electrical Equipment In buildings
YY(Y)
NNN
2 to 3 characters, refer to the table below
3 digits, Sequential Number
YY(Y) stands for: Cathodic Electrical Equipment Code
CODE
DESCRIPTION
AJB
Anode Junction Box
AN
CA
NJB
PC
PJB
RE
SP
Anode
Cathodic protection
Negative Junction Box
Polarization Coupon
Positive Junction Box
Reference Electrode
Surge Protector
TRU
Transformer Rectifier Unit
TS
Test Station
Cables will be tagged as per section 3.3 Electrical Cables.
Example: Parent tag shall either be a :
-
Transformer Rectifier Unit (TRU) or
-
Test Station
In the case of: Transformer Rectifier Unit (TRU) : for instance 112-TRU-001
- For Anode JB:
112-TRU-001-AJB003
- For Negative JB:
112-TRU-001-NJB03
- For Positive JB:
112-TRU-001-PJB03
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 12 OF 38
3.5
Cable Trays / Trenches and Earth Pit
Cable Trays / Trenches:
WBS Hyphen separator
Discipline indicator Routing Type indicator
Type of Signal Cable
Hyphen separator Sequential Number
AAA
D V
(Y)
NNN
D - Discipline Indicator:
I: ICST
E: Electrical
V - Routing Type indicator:
U: Under Ground Routing
A: Above Ground Routing
Three Character WBS area code
Discipline indicator (I- ICST, E- Electrical) Routing Type (AG or UG routing) Refer below list Y (optional, applicable for ICST routing): type of signals, Refer below list
3 digit
Y - Type of Signal: Y (applicable for ICST routing): type of signals cable
L: LV
F: FO
I: IS
N: NIS
P: PAGA
Example:
C00-EA-001 Electrical cable tray above ground
C13-IAF-001 Instrument Cable tray above ground for FOC
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 13 OF 38
Earth Pit:
Unit number Hyphen separator Earth Pit type indicator Hyphen separator
Sequential Number Deep well indicator
AAA
XXX
NNN (D)
Three-digits for Unit Code
Earth Pit type indicator Refer Below
3 digit Deep well indicator, one character
Earth Pit type indicator values
EEP - Electrical Earth Pit
IEP – Instrumentation Earth Pit
LEP – Lightning Earth Pit
Example:
111-EEP-001 Earth Pit in LNG Liquefaction unit
4.0
INSTRUMENTATION NUMBERING
This numbering is developed in a dedicated procedure - refer to [2] RLNG-000-IC-PP-0001 (215122C- 000-JSD-1500-0001) I&C System numbering procedure. Below is summary from the document. Full details to be referred from RLNG-000-IC-PP-0001 (215122C-000-JSD-1500-0001) I&C System numbering procedure.
Loop Tag Numbering
Unit number Hyphen separator
Function Identifier
Hyphen separator
UUU
X
Sequential Number
NNNN
Three-digits for Unit Code
One letter used to indicate measured/initiation Variable (Refer to Attachment 1 – Instrumentation Identification Letters based on ISA 5.1
Four-digit sequential number used to indicate loop number. The loop sequential number shall be unique, for a given process unit, whatever the measured variable (P, L, T, F, A…).
111-F-0011 for flow loop in process unit 111(LNG train 1 - Precooling and Propane Cycle / C3-MR Compressors / MCHE / Liquefaction Air Coolers).
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 14 OF 38
Instrument Tag Numbering
Unit number Hyphen separator
UUU
Three-digits for Unit Code
Up to Six-digits.
Function Identifier
XXXXXX
First letter indicates the measured/initiation Variable.
Hyphen separator Sequential Number
NNNN
Letters when necessary
(A(A))
Second up to fifth succeeding letters indicate the Modifier
Four-digit sequential number, indicating the loop number. Used for instance for redundant equipment. More often, no suffix digit will be used, otherwise one suffix, rarely two suffixes. “R” suffix will be used for remote electronic indicator.
Examples:
111-FE-0011
for flow element in process unit 111 (related loop number will be 111-F-0011).
111-FT-0011A for flow transmitter in process unit 111 (related loop number will be 111-F-0011), for large range if applicable
Safety and Control Interlock
SIS / FGS / UCP Safety Interlocks and DCS / UCP control interlock shall be numbered as follows:
Unit number Hyphen separator
Function Identifier
Hyphen separator
UUU
FF
Three-digits for Unit Code
Two-letter for Functional identification as follows : UZ = SIS, Package and F&G safeguarding logic block. US = DCS or Package control interlock KS = DCS or Package sequence
Sequential Number
NNN
Letters when necessary
(A)
Three-digit sequential numbering. Number “001” to be reserved for unit shutdown (ESD-2 level). e.g redundant equipment
Example:
111-UZ-001
for 1st Safety Interlock related to Process unit 111
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 15 OF 38
5.0
FIRE AND GAS TAGGING RULES
This numbering is developed in a dedicated procedure. - refer to [2] RLNG-000-IC-PP-0001 (215122C- 000-JSD-1500-0001) I&C System numbering procedure. Below is summary from the document. Full details to be referred from RLNG-000-IC-PP-0001 (215122C-000-JSD-1500-0001) I&C System numbering procedure.
Fire and Gas Device Loop Numbering System
The Fire and Gas device loops (groups of flame/gas/heat/smoke detectors, MAC, beacons, sounders etc.) shall be identified as follows:
Fire Zone Hyphen separator Function Identifier Hyphen separator Sequential Number
Example:
FFFF
Q
NNNN
Four characters for Fire Detection Zone
“Q” letter to identify a F&G loop
Four-digit sequential number, indicating the loop number.
02GA-Q-0178 for a Fire and Gas loop in fire detection zone FZ-02-G-A (propane vaporizer equipment in propane liquefaction area, liquefaction train 1).
Fire and Gas Device Tag Numbering System
Fire and gas devices shall be identified as follows:
Fire Zone Hyphen separator Function Identifier Modifier indicate the device type Hyphen separator Sequential Number
Examples:
FFFF
Q
Four characters for Fire Zone
“Q” letter to identify a F&G device
XXXXX
Two up to five-letter code used to indicate the device type
NNNN
Four-digit sequential number, indicating the loop number.
02AA-QGDC-0223 for a Catalytic Hydrogen gas detector in fire detection zone FZ-02-A-A in LNG train 1.
03AA-QGDC-0223 for a Catalytic Hydrogen gas detector in fire detection zone FZ-03-A-A in LNG train 2.
04BA-QFDIR-0698 for a Triple IR Flame detector in fire detection zone FZ-04-B-A in LNG tanks area.
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 16 OF 38
Instrument and F&G Cables Numbering
Single Cables
The Instrument / F&G field single cables shall be identified in the same way as the appropriate instrument
Tag number, without hyphen separators.
Examples:
051PDT0184 Instrument single pair cable running to a junction box (or directly to a Marshalling
Cabinet) from differential pressure transmitter 051-PDT-0184.
020TT0362
Instrument single pair cable running to a junction box (or directly to a Marshalling Cabinet) from temperature transmitter 020-TT-0362.
Power Cables
Instrument Power Cables
For instruments with a single power feeder cable, the cable shall be numbered in the same way as the
appropriate instrument Tag number, without hyphen separators, and by adding letter “P” in suffix.
Example:
042FT0024P Power cable supplying flowmeter 042-FT-0024.
Other Power Cables
Power cables supplying cabinets shall be identified as follows:
BB(B)NN(A Hyphen separator
BB(B)NN(A
Building tag without hyphen
A
Q
Hyphen separator
Sequential Number
FF
NNN
Power Cable Source Type indicator
PX
Examples:
One-letter code used to indicate the Instrument System type code One-letter code used to indicate cabinet type
Three-digit number used to identify the Equipment sequence number
PX = • P1 for power cable from UPS A (45’) • P2 for power cable from UPS B (45’) • P3 for power cable from UPS A (8h) • P4 for power cable from UPS A (8h) • PN for power cable from normal power supply
OB01-DS-001-P1 for UPS A (45’) power supply cable to DCS system cabinet in CCB.
SS11C-UU-001-PN for normal power supply cable to a UCP cabinet located in e-house SS11C.
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 17 OF 38
Sample Connection
The sample connection assemblies shall be identified as follows
Unit number Hyphen separator
Function Identifier
sampling connection type Hyphen separator
Sequential Number
Example:
UUU
SP
XXY
NNN
Three-digits for Unit Code
Two letters “SP” to indicate Sample Connection / Point assembly Two digits and one letter to identify sampling connection type. Starting from 01A
Three digits number used to indicate Sample assembly number. Unique sequential number starting at 001
111-SP05A-001 for Sample connection type 05A in Process unit 111.
6.0
TELECOMMUNICATION AND SECURITY NUMBERING
[13] This numbering is developed in a dedicated procedure - refer to [3] - RLNG-000-TE-PP-0001
(215122C-000-JSD-1530-0001) Telecommunication numbering procedure
Field Device/Enclosure Numbering
Field device and enclosure numbering shall be identified as follows:
Area Code
Hyphen separator
System/Sub System
Equipment Hyphen separator
AAA
XXXX
YYYY
Sequential Number
NNNN
Letter when necessary
(W)
Examples:
Three characters for Area Code (WBS): Refer to reference document RLNG-000-PM-PP-3107 “Geographical Work Breakdown Structure” [3] – Paragraph 3.1 ATTACHMENT 1: List of Geographical Work Breakdown System codes Hyphen separator 3 or 4 letters used to indicate Telecom System or Telecom Sub System 3 or 4 letters used to indicate the equipment Type Hyphen separator Four-digit sequential number used to indicate equipment sequential number Used for instance for redundant equipment: e.g. to differentiate PAGA System A equipment from PAGA System B equipment
A11-PCTVCAM-0002
for the second Process CCTV camera in A11 area
A11-SCTVCAM-0001
for the first Security CCTV camera in A11 area
A12-PAGASPE-0003A for the third PAGA speaker A in A12 area
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 18 OF 38
Building device and enclosure
Building tag
BBBBB
Hyphen separator
System/Sub System
Equipment Hyphen separator
Sequential Number
XXXX
YYYY
NNNN
Letter when necessary
(W)
Building tag without hyphen - Refer to reference document RLNG-000-CV-NM-0001 Building List Summary – Appendix 1 (Building List) Hyphen separator 3 or 4 letters used to indicate Telecom System or Telecom Sub System 3 or 4 letters used to indicate the equipment Type Hyphen separator Four-digit sequential number used to indicate equipment sequential number Used for instance for redundant equipment: e.g. to differentiate PAGA System A equipment from PAGA System B equipment
Examples:
IES11-PAGACAB-0001A
for the PAGA system A cabinet in IES11.
CCB01-FOCSCAB-0001A for the FOCS A FOPP cabinet in CCB.
CCB01-BLANCSW-0002
for the BLAN core switch in CCB (in LAN cabinet)
TELECOMMUNICATION CABLE NUMBERING Below is Tagging Format of Telecom Cable. For More additional please refer Section 3 of RLNG-000- TE-PP-0001
Equipment Cable Numbering
Cable type
C(C)
• C for Copper signal cable
• P for Power cable
• EC for Ethernet Copper cable
• FO for Optical cable
• K for Composite cable
Hyphen separator
• Hyphen separator
Equipment tag
AAAXXXXYYYYNNNN(W)
Equipment tag without hyphen
BBBBBXXXXYYYYNNNN(W)
Hyphen separator
Hyphen separator
Sequential Number
(ZZ)
Optional: to be used when one telecom equipment is connected to more than one cable of same type
From 1 to 2 digits
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 19 OF 38
Examples:
K-A11PCTVCAM0002
for the composite cable of A11-PCTVCAM-0002 camera
K-A11SCTVCAM0001
for the composite cable of A11-SCTVCAM-0001 camera
C-A12PAGASPE0003A for the copper cable of A12-PAGASPE-0003A speaker
C-CCB01PACSCRD0001 for the copper signal cable of CCB01-PACSCRD-0001 card reader
Cable between Cabinets/Enclosures
Cable type
C(C)
Hyphen separator
• C for copper signal cable
• P for power cable
• EC for Ethernet Copper cable
• FO for optical cable
• K for composite cable
• Hyphen separator
Cabinet/enclosure tags
BBBBBXXXXYYYYNNNN(W)- BBBBBXXXXYYYYNNNN(W)
From/to cabinet/enclosure tags without hyphen
OR
BBBBBXXXXYYYYNNNN(W)- XXXXYYYYNNNN(W)
Hyphen separator
Sequential Number
(ZZ)
Hyphen separator
Optional when from/to cabinet/enclosure having more than one cables of the same type
From 1 to 2 digits
Note : for cable connected between cabinets located within the same building (BBBBB is not repeated)
Examples:
FO-CCB01FOCSCAB0001A-IES11FOCSCAB0001A
FO-IES11PAGACAB0001A-FOCSCAB0001A
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 20 OF 38
7.0
PROCESS & PIPING LINE NUMBERING
The numbering appearing on P&IDs shall be:
Linesize
linesize
Hyphen separator
in inches. The fractions will be written: 1.5”, or 0.5”, for better readability.
Unit number
UUU
3 digits, Refer to Attachment 1 - Unit Numbering
Hyphen separator
Service / fluid
Hyphen separator
FF
2 characters, Refer to Attachment 2 - Service - Fluid Codes
Sequential number
SSSS
4 digits
Hyphen separator
Pipe class
PPPP(P)
Up to 5 characters, refer to section - Insulation thickness is not part of line tag. PIPING CLASSES.
Hyphen separator
Insulation type
NNN
3 characters
Line Sequence number range for each Operating Center:
Each operating Center will work with in below allocated range,
POC 0001 to 2999
POC - Vendor 3001 to 3999
JGC 5001 to 6999
JGC - Vendor 7001 to 7999
ADOC 8001 to 8999
ADOC - Vendor 9001 to 9599
Example:
20”-111-N2-1511-A206N-AHD - 20” line of Nitrogen
4”-076-PW-6402-F10AN-C - 4” line of Potable Water
Insulation thickness:
Insulation thickness is indicated on the line list.
Insulation thickness is not part of line tag.
8.0
PIPING CLASSES
Piping classes will be as per:
359665-0809-070-SP-1300-002 - Specification for Piping Material Classes - revision 0 as stated in ADR- 002
Should some additional piping classes need to be developed for the Project, if one piping class is created from another “close” one, the new created piping class might have 1 additional character (5 characters instead of 4), to keep traceability / readability to the initial one.
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 21 OF 38
9.0
PIPING SPECIALTIES AND MANUAL VALVE
9.1
PIPING SPECIALTIES
They shall be numbered:
Unit Number
Separator
Item Identifier
Separator
Sequence Number
Suffix Code
Example:
UUU
Refer to Attachment 1 - Unit Numbering
XXX
Refer to Attachment 6 - Piping Specialty
NNN
(A)
3 digits
A, B,C,D,…etc.
111-SPS-001 Strainer in unit 111
111-SPH-001 Hose connection in Unit 111
9.2
MANUAL VALVE
Manual Valves shown on P&IDs will be tagged. Instrumentation root valves which are not detailed on PIDs (but shown on typical arrangement only) will not be tagged
Unit Number
Separator
Item Identifier
Separator
UUU
Refer to Attachment 1 - Unit Numbering
XXX
Refer to 16.9Attachment 9 – Manual Valve Type Code
Sequence Number
NNNN
4 digits
Manual Valve Sequence number range for each Operating Center:
Each operating Center will work with in below allocated range, Vendor will be allocated tags by the Contractor
POC 0001 to 2999
POC - Vendor 3001 to 3999
JGC 5001 to 6999
JGC - Vendor 7001 to 7999
ADOC 8001 to 8999
ADOC - Vendor 9001 to 9599
Example:
111-GLV-0001 Globe Valve in unit 111
111-BFV-0001 Butterfly Valve in unit 111
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 22 OF 38
9.3
EQUIPMENT NOZZLE
Process nozzles are tagged as NX
-
N constant
-
with X as a number incremented.
Resulting in N1, N2, N3… N10.
Instrument nozzles are tagged as MYZ
-
with M a letter indicating the parameter measured,
-
Y a number incremented.
-
And Z as optional letters A and B for bound instruments (such as differential pressure or level
transmitters).
Resulting in P1, P2, P3, T1, T2, L1A and L1B, P4A and P4B etc.
Mechanical Nozzles are tagged as MK
-
M is constant
-
K is a number incremented.
X, Y and K increments are independent from each other.
9.4
Utility Station
Unit Number
Separator
Item Identifier
Separator
UUU
Refer to Attachment 1 - Unit Numbering
XX
“US” Code indicating Utility station
Sequence Number
NNN
3 digits
Example:
111-US-001 Utility Station in unit 111
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 23 OF 38
10.0
TECHNICAL BUILDINGS, INDUSTRIAL AND NON-INDUSTRIAL BUILDINGS
Building Type
BB(B)
Two to three characters from the table below
Hyphen separator
Sequential Number
Suffix Code
NN
(A)
Two numerical characters
One letter as necessary
Where BB(B) stands for:
SS
MB
OB
CCB
JCB
AS
IES
Electrical Building: Concrete (stick built) SUBSTATION and E-Houses
Mechanical Building: Compressor Building
Operation Building
Central Control Building (Instrumentation Building)
Jetty Control Building (Instrumentation Building)
Analyzer Shelter (Instrumentation Building)
Instrument Equipment Shelter (Instrumentation Building)
The building tags are as listed in [10] - RNLG-000-CV-NM-0001 (215122C-000-NM-2000-0001) Buildings List.
11.0
INSULATION
The insulation codes will be as per the dedicated specifications:
[6] - RLNG-000-IL-SP-0001 (FEED ref: 359665-0809-070-SP-9999-011 / CTR ref: 215122C-000-JSD- 2200-0001) Specification for Thermal and Acoustic Insulation
[7] - RLNG-000-IL-SP-0002 (CTR ref: 215122C-000-JSD-2250-0001) Specification for PFP/CSP Material for Piping and Equipment.
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 24 OF 38
12.0 HVAC EQUIPMENT IDENTIFICATION
HVAC Equipment (Fans, Air Handling Units, filters…) shall be tagged as follow:
Building Tag
BB(B)-NN(A)
Refer to section 10.0 TECHNICAL BUILDINGS, INDUSTRIAL AND NON-INDUSTRIAL BUILDINGS.
Hyphen separator
HVAC Equipment code
L(L)
Equipment type Modifier
(M)(M)
One-to two letter code used to indicate Equipment type or function. Refer to Attachment 7 - HVAC - EQUIPMENT TYPE PREFIX . One-or two letter code used to indicate Equipment type prefix modifier. Se One-letter code used to indicate Equipment type or function. Refer to Attachment 8 - HVAC - EQUIPMENT TYPE MODIFIER.
Hyphen separator Sequential Number
NNN
3 digits
-
Each equipment component of packaged equipment shall have a unique number assigned.
-
HVAC Local Control panels, instrumentation and instrument cables linked to the HVAC shall be tagged as per [2] - RLNG-000-IC-PP-0001 (215122C-000-JSD-1500-0001) I&C System numbering procedure.
-
Electrical Power Distribution Panels, Electrical Components and Electrical Cables linked to the
HVAC shall be tagged as per the electrical tagging.
Limit switch & SOV of Gas and Fire dampers shall be tagged as per Instrument and Fire And Gas Numbering.
- Strainers or any inline piping element shall be tagged as per Attachment 6 - Piping Specialty.
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 25 OF 38
13.0 CIVIL ASSET NUMBERING
The several assets from the Civil are numbered as per the below two tables:
CIVIL ASSETS
CODE
STRUCTURE of TAG
EXAMPLE
Structural (named from an equipment)
STR
(UUU-XX-NNN(A) = Equipment tag)- STR-NNN
111-E-005-STR-001
Structural (not named from an equipment)
STR
AAA-STR-NNN
AAA-PR-NNN
AAA-PS-NNN
A12-STR-002
A11-PR-003
G60-PS-001
Piperack
Pipe sleeper
Foundation for building in concrete
Foundation for building (shelter, or structural building)
PR
PS
FDN
FDN
Foundation for equipment
FDN
Foundation for structural (named from an equipment) Foundation for structural (not named from an equipment)
FDN
FDN
Foundation for piperack
FDN
(BB(B)-NN(A) = Building Tag)-FDN- LMM, Note 1
SS-T1-FDN-A06, Note 1
(BB(B)-NN(A) = Building Tag)-FDN- LMM, Note 1
MB-11-FDN-B12, Note 1
(UUU-XX-NNN(A) = Equipment tag)- FDN-LMM, Note 1
111-E-005-FDN-001, Note 1
(UUU-XX-NNN(A) = Equipment tag)- FDN-LMM, Note 1
111-E-005-FDN-001, Note 1
(AAA-STR-NNN=tag structure)-FDN- LMM, Note 1
A12-STR-002-FDN- C04, Note 1
(AAA-PR-NNN = Pipe rack Tag)-FDN- LMM, Note 1 (AAA-XX-XXX=tag pipe support)-FDN- LMM, Note 1
FDN
A11-PR-003-FDN-A06, Note 1
A12-FDN-007
A12-PSS-007
A12-PSN-007
A12-PPF-007
A12-ETS-007
A12-ITS-007
A12-SH-007
A12-RC-007
Foundation for pipe support Piping Support Structure (critical lines) Piping support (non-critical lines)
Piping pedestal foundation
Electrical Tray Support
Instrumentation Tray Support
Plant Shelter
Road Crossing / Bridge
Platform (named from an equipment)
PSS
AAA -PSS-NNN
PSN
AAA -PSN-NNN
PPF
ETS
AAA -PPF-NNN
AAA -ETS-NNN
ITS
AAA -ITS-NNN
AAA -SH-NNN
AAA -RC-NNN
SH
RC
PF
(UUU-XX-NNN(A) = Equipment tag)-PF- NNN
112-C-005-PF-03
Platform (at grade)
PF
AAA-PF-NNN
Any other asset
YY(Y(Y))
AAA-YYYY-NNN, where YYYY from the table below
A12- PF-007
C34-CULV-004
For WBS Numbering please refer to RLNG-000-PM-PP-3107. WBS are further granularly arrangement with Process Unit. Unit and WBS number. relation is also provided in the Document
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 26 OF 38
Note 1: The 3 characters “LMM” coming after “-FDN” could be
sequential, or
a Letter and 2 numbers, where the letter and numbers represent the grid of the foundation.
In the table above:
UUU-X(X)-NNN(A)
AAA
BB(B)-NN(A)
YY(Y(Y))
Refers to the numbering of Main Equipment, in section 2.1 Area Code, from WBS (Work Breakdown Structure) Procedure, and as preliminary example, Refer to document RLNG-000-PM-PP-3107 “Geographical Work Breakdown Structure” [3] – Paragraph 3.1 ATTACHMENT 1: List of Geographical Work Breakdown System codes Refer to section 10.0 TECHNICAL BUILDINGS, INDUSTRIAL AND NON-INDUSTRIAL BUILDINGS Refer to the table below
CODE YY(Y(Y))
BW
CB
BUND WALL
CATCH BASIN
CULV
CULVERT
CIVIL ASSETS
FC
GT
KB
MH
OD
PL
PT
SU
TP
VP
CO
DB
DH
PB
DT
GT
ST
FENCE
GATE
CURB
MANHOLE
OPEN DITCH
PILE
PIT
SUMP/SUMP BOX
CONCRETE TRENCH FOR PIPING
VALVE PIT/VALVE BOX
CLEAN OUT
DUCT BANK
DRAIN HUB
PULLING BOX
DITCH
GUTTER
SAND TRAP
WMH
WEIR MANHOLE
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 27 OF 38
CODE YY(Y(Y))
CIVIL ASSETS
DV
LS
FB
JB
FH
FM
UD
VD
ICB
OCB
DCB
DF
DF
OB
DIVERTER BOX
DIVERTER BOX – LNG
DIVERTER BOX - FIRST FLUSH BASIN
DITCH WATER CATCH BASIN (JUNCTION BOX)
FIRE WATER HYDRANT
FIRE WATER MONITOR
U-DITCH
V-DITCH
INLET CATCH BASIN
OUTLET CATCH BASIN
WEIR BOX
DRT CATCH BASIN
DRIP FUNNEL
DRIP FUNNEL
14.0 MARINE
The several assets from the Marine are numbered as per the below two tables:
Marine ASSETS
STRUCTURE of TAG
EXAMPLE
Marine Equipment
AAA-YY(Y(Y))-NN
E25-QRH-01
Marine Structures
AAA-YYY-NN
E25-MD-01
Marine Piling
AAA- YYY-NNN -PL-LMM, Note 1
E25-MD-01-PL-A06
Note 1: The 3 characters “LMM” coming after “-PL” could be
sequential, or
a Letter and 2 numbers, where the letter and numbers represent the grid of the pile.
In the table above:
AAA
NN YYY
Area Code, from WBS (Work Breakdown Structure), Refer to document RLNG-000-PM-PP-3107 “Geographical Work Breakdown Structure” [3] – Paragraph 3.1 ATTACHMENT 1: List of Geographical Work Breakdown System codes Sequential Number Refer to the table below
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 28 OF 38
MARINE ASSETS
CODE YYY
ATN
BAS
BD
BER
BLA
BOL
CAS
CPS
CUS
EP
Aids to Navigation
Berth Aid System
Berthing Dolphin
Berth
Boat Landing
Bollard
Causeway
Capstan
Current Censor
Expansion Loop
EMS
Environmental Monitoring System
FEN
JTY
HST
IMP
IMT
LLD
MD
NAV
PC
PLT
QRH
TRE
WST
WTS
WW
Fender
Jetty
HeadStock
Impounding Basin Platform
Impounding Basin Trench
Large LED Display
Mooring Dolphin
Navigation System
Pile Cap
Loading Platform
Quick Release Hook
Trestle
Weather Station
Wave and tide Sensor
Walkway
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 29 OF 38
15.0
FIRE FIGHTING AND SAFETY EQUIPMENT NUMBERING
Firefighting and safety equipment shall be tagged as follow:
Unit Number Hyphen separator Functional Identification Hyphen separator Sequential Number
UUU
XX
NNN
Refer to Attachment 1 – Unit Numbering
Indicate the Fire Protection and Personnel Protection Equipment type
3 digits
CODE XX
Fire Protection and Personnel Protection Equipment
DP
DS
DV
FH
FP
FX
GE
HB
HM
HR
HX
OM
SA
SC
SE
SF
SH
SS
WM
WS
Dry Chemical Extinguishing System
Deluge Skid
Deluge Valve
Fire Hydrant
Fire Point
Fire Extinguisher
Gaseous Extinguishing System
Hose Box
Hydrant Monitor
Hose Reel
High Expansion Foam System
Oscillating Monitor
Air breathing Apparatus
International Ship to Shore Connection
Eye Wash Station
First Aid Kit
Smoke Hood
Safety Shower with Eyewash
Water Mist Extinguishing System
Windsock
Example:
111-FX-001 - Fire Extinguisher for LNG Train 1
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 30 OF 38
16.0 ATTACHMENTS
16.1
Attachment 1 - Unit Numbering
Units
Description
000
010
013
019
020
021
035
042
044
053
058
059
060
061
076
077
079
080
081
082
083
084
085
086
088
099
101
111
112
115
General
Feed Gas Inlet facilities
HHR Unit (Future) & Booster Compression (Future)
LNG Storage Tanks area (Tanks excluded)
LNG Storage Tank 1 & 2
LNG Loading Facilities
Refrigerant Storage
Air & Nitrogen
Chilled Water Unit
Outfall Pumping Basin
Fuel Gas
Dry Flare
BOG Compression
BOG Flare
Utility & Potable Water Production
Fire Water
Sanitary Sewer / Sewage Treatment
ICSS, DCS, SIS (FGS is in unit 083)
Telecom
HVAC
Fire Fighting And Fire Gas System
Technical Buildings: Central Control Building (CCB), Instrument Equipment Shelter (IES) and Electrical Sub Stations (SS)
Industrial and Non-Industrial Buildings
Open Drains
Diesel and Emergency Power
Inlet, Utilities and Storage - General
LNG train 1 - General
LNG train 1 - Liquefaction Unit
LNG train 1 - Nitrogen Rejection Unit
LNG train 1 - Cold Closed Drain
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 31 OF 38
Units
Description
177
182
183
186
188
201
211
212
215
277
282
283
286
288
LNG train 1 - Fire Water
LNG train 1 - HVAC
LNG train 1 - Fire Fighting And Fire Gas System
LNG train 1 - Open Drains
LNG train 1 - Diesel and Emergency Power
LNG train 2 - General
LNG train 2 - Liquefaction Unit
LNG train 2 - Nitrogen Rejection Unit
LNG train 2 - Cold Closed Drain
LNG train 2 - Fire Water
LNG train 2 - HVAC
LNG train 2 - Fire Fighting And Fire Gas System
LNG train 2 - Open Drains
LNG train 2 - Diesel and Emergency Power
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 32 OF 38
16.2
Attachment 2 - Service - Fluid Codes
Description
Accidentally contaminated
Bog flare
Boil-off gas
Biocide
Fluid Code
AC
BF
BG
BI
Clean agent fire extinguishing (in buildings only) CA
Continuously contaminated
Dry flare
Corrosion inhibitor
Closed drain
Clean Runoff
Chilled cooling water supply
Clean water
Chilled cooling water return
Dry air
Defrost gas
Open drain
Dry chemical powder
Ethylene
Foam concentrate
Diesel
Fuel gas
Foam solution / fire suppressant
Fire water
CC
CD
CI
CL
CR
CS
CW
CZ
DA
DG
DO
DP
ET
FC
FD
FG
FS
FW
Description Seal gas Hydrocarbon condensate Hydrocarbon liquid Hydrocarbon vapor Instrument air
Liquefied natural gas Liquid nitrogen Lube oil Mixed refrigerant Utility nitrogen, refrigerant N2 Oil mist Plant air Propane Pump trim Potable water Scale inhibitor Sanitary sewer Utility water Atmospheric vent Vessel trim Warm liquid drain Process water Wet flare
Fluid Code
GS
HC
HL
HV
IA
LG
LN
LO
MR
N2
OM
PA
PR
PT
PW
SI
SS
UW
VG
VT
WL
WP
WF
The latest information about service / fluid codes shall be taken from the PID legend sheet.
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 33 OF 38
16.3
Attachment 3 - Equipment Code identification
DESCRIPTION
Agitator / Mixer
Air cooler Bay
Column
Column Internal
Deaerator
Exchanger / Air Cooler
Exchanger Internal
Diesel Generator
Electrical Heater
Filter / Coalescer
Fan
Air Cooler Motor (Fan)
Gear Box
Heater
Handling / Crane / Davit Crane
Compressor
Compressor Motor
Compressor LP Casing
Compressor MP Casing
Compressor HP Casing
Inlet Guide Vane
Loading / Unloading Arms
Pumps
Pump motor
Tank
Telecommunication Tower
Basin, Sump, Pit, Stormceptor
Vessel
Vessel Internal
Liquid Turbine Pump
Package units (incl. Flare, …)
Code
AG
B
C
CI
DA
E
EI
EG
EH
F
FA
FAM
GB
H
J
K
KM
LPC
MPC
HPC
IGV
LA
P
PM
T
TW
U
V
VI
XP
Z
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 34 OF 38
16.4
Attachment 4 - Electrical Equipment Type Code
CODE DESCRIPTION
ACDB UPS AC Distribution Board
AP
Annunciation Panel
ASD
Adjustable Speed Drive
AWL
Aircraft Warning Light
AWLP Aircraft Warning Light Panel
BAT
Battery
BC
BD
BDS
CAP
CB
Battery Charger
Bus Duct
Battery Disconnector Switch
Capacitor Bank
Circuit Breaker
CCT
Lighting or small power Circuit
Control Panel
Change over Switch
CP
CS
DB
CODE DESCRIPTION Isolator Switch
ISO
JB
LCS
LDB
LF
Junction Box
Local Control Station
Lighting Distribution Board
Light Fixture
MAM Motor Ammeter MCC Motor Control Center (690/415 LV Switchgear) Main Junction Box (3 ph + N) MJB MVP Motorized Valve Panel NDS NER OLTC On load Tap Changer OWS Operating Workstation Patch panel
Neutral Disconnecting Switch
Neutral Earthing Resistor
PAP
Electrical Distribution Board in building
PDB
Power distribution Board
DCDB UPS DC Distribution Board
ECMS Electrical Control & Monitoring System
EEB
EEP
ELA
Electrical Earth Bar
Electrical Earth Pit
Lightning Arrestor
ELDB Emergency Light Distribution Board
EPB
Emergency Push Button
ES
Earthing Switch
PEC RMU RP SA
Photoelectric Cell
Ring Main Unit
Relay panel
Solar panel array
SDB
Small Power distribution board
SH
SL
SO
Space Heater
Strobe Light
Small Power Socket Outlet
ESDB Emergency Small Power Panel
SPS
Solar Power System
EWS
Engineering Workstation
GCP Generator Control Panel
SS
Soft Starters
SWG
Switchgear
HFC
HFR
HFX
HTP
INV
IRP
Harmonic Filter Capacitor
THY
Thyristor Panel
Harmonic Filter Resistor
Harmonic Filter Reactor
Heat Tracing Panel
Inverter
Instrumentation Panel - Interposing Relay Panel
TJP
Telecom power junction box
TR UPS WO
Transformer
Uninterruptible Power Supply
Welding Outlets
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 35 OF 38
16.5
Attachment 5 - Electrical - Voltage Code
Voltage Code A B C D
E F G H J
Voltage
132 KV 33 kV 11 kV / 13.8 kV 6.6 kV
3.3 kV 690 V 415 V 240 V 110 V DC
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 36 OF 38
16.6
Attachment 6 - Piping Specialty
SP ident
DESCRIPTION
SPC
SPH
Special Check valve (Non-Slam Axial type, Dual plate, Tilting Disc, or depending on the case “dissimilar type” or other check valve with specific requirement not covered by piping class items) Hose connection
SPI
Mechanical Interlock
Miscellaneous (Other than SPC, SPH, SPI, SPS and SPV)
Flame arrestor
Injection Quill
Flexible hose
Liquid Trap
Isolating Joint
Barred Tee
Anchor Flange
Corrosion Coupons
SPX
Corrosion Probe
Special Flange - (Item not covered by Piping class)
Multi-tap Orifice Flange
Special Spool
Special Blank and Spacer - (Item not covered by Piping class)
Vacuum Breaker Valve, Air Release Valve
Expansion Joint
Sight Glass
Insulation Kit
Spray Nozzle
SPS
SPV
Strainer (Item or range not covered by Piping class or/and with specific Process requirement. It can cover Y type, T type, Bucket Type and all Conical Strainers). Special Valves (Valves with specific design requirement or performance not covered by Piping class items).
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 37 OF 38
16.7
Attachment 7 - HVAC - EQUIPMENT TYPE PREFIX
Letter AC
Air Cooled Condensing Unit / Air Condenser
Equipment Type
AH B CB CF CH D
E EH FC G L N
P PU S SU T V
VB W X Y
Air Handling Unit Damper Constant Volume Box Chemical Filter Unit Chiller Moisture Eliminator
Exchanger Electrical heater Fan Coil Unit Grille / Diffuser Sound attenuator Louvre / Wind Shield
Pump Package Unit Air filters / Strainer Split Unit Tank Valve
Variable Volume Box Steam or adiabatic humidifier Exhaust Fan Supply Fan
16.8
Attachment 8 - HVAC - EQUIPMENT TYPE MODIFIER
Letter A B C E F G FG M N P S T U V X
Equipment Type Modifier
Warm air curtain (exchanger) Balancing (damper) Blast (damper) Smoke (exhaust fan / damper) Fire (damper) Gas (damper) Fire and Gas (damper) Motor / Motorized (damper / valve) Non-return (damper) Pressure relief (damper) Shut-off (damper) Floor transfer (grille) Pneumatic (damper / valve) Modulating (damper) Return / Exhaust (grille / diffuser)
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.
RUWAIS LNG PROJECT
EQUIPMENT AND COMPONENT NUMBERING PROCEDURE
COMPANY DOCUMENT REF. RLNG-000-PM-PP-2003
CONTRACTOR DOC. REF.
215122C-000-PP-2003
REVISION: 0D
PAGE 38 OF 38
Letter Y
Supply (grille / diffuser)
Equipment Type Modifier
16.9
Attachment 9 – Manual Valve Type Code
Valve Type Code BV BFV CHV DIV FHV GV GLV NLV PLG
Description
Ball Valve Butterfly Valve Check Valve Diaphragm Valve Fire Hydrant Valve Gate Valve Globe Valve Needel Valve Plug Valve
The terms of Contract / Agreement No: CON22-146 shall apply for any disclosure of this document to any third party.