1
2
3
4
5
6
7
8
9
10
11
12
13
SIGNAL SYMBOLS
MEASUREMENT ELEMENTS
RELIEF VALVES
IDENTIFICATION LETTERS OR INSTRUMENT FUNCTIONS
NOTE 2
INSTRUMENT CONNECTION TO PROCESS
GENERAL SYMBOL
XXX
(1)
(2)
(3)
PSV : PRESSURE RELIEF VALVE
FIRST-LETTER
SUCCEEDING LETTERS
MEASURED OR
INITIATING VARIABLE
MODIFIER
READOUT OR
PASSIVE FUNCTION
OUTPUT FUNCTION
MODIFIER
A
B
C
D
E
F
G
H
I
J
M
S
S
M
S
S
R O F Y L P P A L L A H S 6 4 1
2 2 N O C
:
O N T N E M E E R G A
/
T C A R T N O C F O S M R E T E H T
.
I
Y T R A P D R H T Y N A O T T N E M U C O D S H T F O E R U S O L C S D Y N A
I
I
ELECTRICAL SIGNAL
SYSTEM LINK (SOFTWARE OR DATA LINK)
PNEUMATIC LINE
CAPILLARY TUBING
HYDRAULIC SIGNAL
INSTRUMENT VALVE SYMBOLS
NOTES 1,3
SPRING DIAPHRAGM ACTUATED VALVE
SPRING DIAPHRAGM ACTUATED VALVE WITH HANDWHEEL
ANGLE CONTROL VALVE
THREE-WAY CONTROL VALVE
LEVEL SYMBOLS
XXX
PRESSURE SYMBOLS
LEVEL ELEMENT XXX DENOTES:
CAP = CAPACITANCE DIS = DISPLACER DP = DIFFERENTIAL PRESSURE GWR = GUIDED WAVE RADAR MG = MAGNETIC RAD = RADAR RES = RESISTANCE US = ULTRASONIC VIB = VIBRATION
XXX
(2)
(3)
XXX (1)
P
NOTE 4
PILOT OPERATED PRESSURE RELIEF VALVE
XXX
(1)
(2)
(4)
(4)
XXX
(1)
PRESSURE AND VACUUM RELIEF VALVE
VACUUM BREAKER
PRESSURE TAP
DIFFERENTIAL PRESSURE TAPS
TEMPERATURE SYMBOLS
NOTE 8
0B
SKIN
(2)
XXX
(1)
RUPTURE DISC FOR PRESSURE OR VACUUM RELIEF
SELF ACTIVATED BACK PRESSURE REDUCING REGULATOR (INTERNAL SENSING)
SURFACE MEASURING POINT
SELF ACTIVATED BACK PRESSURE REDUCING REGULATOR (EXTERNAL SENSING)
SELF ACTIVATED PRESSURE REDUCING REGULATOR (INTERNAL SENSING)
INTRUSIVE MEASURING POINT
FLOW SYMBOLS
SELF ACTIVATED PRESSURE REDUCING REGULATOR (EXTERNAL SENSING)
PISTON ACTUATED VALVE
PISTON ACTUATED VALVE WITH HANDWHEEL
MOTOR OPERATED VALVE
TWO-WAY SOLENOID VALVE
FI
RO
RO
SENSOR
THREE-WAY SOLENOID VALVE
S
SENSOR TYPE
FOUR-WAY SOLENOID VALVE
ORIFICE PLATE
ACTUATOR SYMBOLS
AVERAGING PITOT TUBE
SPRING DIAPHRAGM ACTUATOR
TURBINE OR PROPELLER TYPE
SPRING DIAPHRAGM ACTUATOR WITH HANDWHEEL
PRESSURE BALANCED DIAPHRAGM ACTUATOR
VORTEX
M
MAGNETIC
TM
THERMAL MASS
SINGLE OR DOUBLE ACTING CYLINDER PISTON (PNEUMATIC)
POSITIVE DISPLACEMENT TYPE
MOTOR OPERATED ACTUATOR
HAND ACTUATOR
SINGLE SOLENOID ACTUATOR
SINGLE SOLENOID ACTUATOR WITH MANUAL RESET
CORIOLIS TYPE
ULTRASONIC IN LINE
VENTURI TUBE
FLOW NOZZLE
INSTRUMENTATION VENDOR BREAK
BV
R
1
XXX:
PSV, PVV, PSE OR TSV
(1)
(2)
(3)
SEQUENTIAL NUMBER
SET PRESSURE (BARG)
DESCRIPTION: - INLET ORIFICE DIAMETER - ORIFICE LETTER - OUTLET ORIFICE DIAMETER
(4)
VACUUM SETTING (BARG)
FUNCTION SYMBOLS
NOTE 1
ROTAMETER
FUNCTION
RESTRICTION ORIFICE NOTE 6
SPECIAL RESTRICTION ORIFICE WITH NOISE ATTENUATION NOTE 6
UNIT NUMBER
NOTE 5
HIGH HIGH ALARM OR EMERGENCY ACTION
ZZZ
XXXXXX
YYYY(ZZ)
HH H
L LL
HIGH ALARM
LOW ALARM
INSTRUMENT NUMBER
NOTE 2
LOW LOW ALARM OR EMERGENCY ACTION
NOTE 7
NOTE 7
XXX NOTE 9
FIELD MOUNTED INSTRUMENT
INSTRUMENT MOUNTED ON CENTRAL CONTROL ROOM PANEL OR ANALYSER SHELTER OR IES.
0B
0B
INSTRUMENT FUNCTION MOUNTED ON LOCAL PANEL
COMPUTER FUNCTION ( PRIMARY LOCATION )
INSTRUMENT WITH DUAL FUNCTION OR SERVICE
SHARED DISPLAY, SHARED CONTROL ACCESSIBLE TO OPERATOR THROUGH DCS CONSOLE
SHARED DISPLAY, SHARED CONTROL FUNCTION ACCESSIBLE TO OPERATOR THROUGH PACKAGE PLC (SUPPLIED BY VENDOR)
SAFETY OR LOGIC SYSTEM WITH XX : US FOR CONTROL LOGIC AND UZ FOR SAFETY LOGIC ZZZ : DCS,SIS,FGS,MMS
SAFETY OR LOGIC THROUGH PACKAGE PLC (SUPPLIED BY VENDOR) WITH XX : US FOR CONTROL LOGIC AND UZ FOR SAFETY LOGIC ZZZ : PLC,SPLC,CCS,TGS,MMS
ZZZ
0B
ZZZ
MISCELLANEOUS
OPTICAL AUDIBLE ALARM
OPTICAL SIGNAL
PUSH BUTTON
PRESSURE POINT
XX
XX
R
R
PP
A
B
ANALYSIS
BURNER FLAME
BD
BLOWDOWN
C
D
E
CONDUCTIVITY (ELECTRICAL)
DENSITY (MASS) OR SPECIFIC GRAVITY
VOLTAGE (EMF)
ESD
EMERGENCY SHUTDOWN
F
G
H
I
J
K
L
M
FLOW RATE
GAGING (DIMENSIONAL)
HAND (MANUALLY INITIATED)
CURRENT (ELECTRICAL)
POWER
TIME OR TIME SCHEDULE, KEYPHASOR
LEVEL
MOISTURE ,HUMIDITY OR MOTOR LOOP
MO
MOTOR OPERATED
ALARM
USER’S CHOICE
USER’S CHOICE
USER’S CHOICE
CONTROL
DIFFERENTIAL
EMERGENCY
RATIO (FRACTION)
SCAN
SENSOR (PRIMARY ELEMENT)
GLASS,GAUGE
INDICATE
CONTROL STATION
LIGHT(PILOT),STATUS
HIGH
LOW
MIDDLE OR INTERMEDIATE
O
P
Q
R
S
USER’S CHOICE
PRESSURE OR VACUUM
QUANTITY, EVENT OR FIRE & GAS DETECTION
RADIOACTIVITY OR RESTRICTION, RUNNING
INTEGRATE OR TOTALIZE
ORIFICE
(RESTRICTION)
POINT (TEST CONNECTION) , PROBE
RECORD OR PRINT
SPEED OR FREQUENCY
SAFETY
SWITCH
SD
SHUT DOWN
T
U
V
W
X
Y
Z
TEMPERATURE
MULTIVARIABLE
VIBRATION
WEIGHT OR FORCE
ON/OFF
USER’S CHOICE
POSITION
FOR SIS IDENTIFIER
MULTIFUNCTION
WELL
TRANSMIT
MULTIFUNCTION
VALVE, DAMPER OR LOUVER
MULTIFUNCTION
UNCLASSIFIED
UNCLASSIFIED
UNCLASSIFIED
RELAY, COMPUTEOR SOLENOID DRIVER, ACTUATE, UNCLASSIFIED FINAL CONTROL ELEMENT OR SAFETY RELATED INSTRUMENT
VALVES DESIGNATION
NOTE 2
BDV DV ESDV FV/HV/LV/PV/TV MOV SDV ASV XV
BLOWDOWN VALVE DELUGE VALVE EMERGENCY SHUTDOWN VALVE ANALOG OR ON/OFF CONTROL VALVES MOTOR OPERATED VALVE SHUTDOWN VALVE ANTI SURGE VALVE ON/OFF VALVE
FUNCTION BLOCKS
REFER TO LIST BELOW FOR INDICATION
DESIGNATION
SIGNAL
14
NOTES:
15
16
FUNCTION SYMBOLS ARE BASED ON ANSI/ISA-S5.1. FUNCTION LABELS AND IDENTIFICATION ARE BASED ON DOCUMENT: N° RLNG-000-IC-PP-0001(INSTRUMENT & CONTROL NUMBERING PROCEDURE). TYPE OF VALVE BODY FOLLOWING SELECTION CRITERIA. REMOTE SENSING LINE (IF REQUIRED). ALL INSTRUMENT TAGS ARE PRECEDED BY THE UNIT NUMBER (SHOWN ON PID BY GENERAL NOTE). UNIT NUMBER WILL BE SHOWN ON INSTRUMENT TAGS, ONLY IN CASE OF UNIT NUMBER IS DIFFERENT OF PID UNIT NUMBER. A STRAIGHT RUN OF 10 HOLE DIAMETERS IS REQUIRED AFTER ANY R.O. PLATE OR AFTER THE LAST R.O. IN MULTIPLATE INSTALLATION. WHERE THE HOLD SIZE IS 10% N.P.S. AN ELBOW MAY BE INSTALLED IMMEDIATELY DOWNSTREAM. FOR ON-LINE ANALYSER AND TRANSMITTER, THE TYPE OF ANALYSIS IS DEFINED OUTSIDE THE SYMBOL: GC: GAS CHROMATOGRAPH O2: OXYGEN ANALYSER FID: FLAME IONISATION DETECTION ANALYSER H2O: MOISTURE ANALYSER FREE CL2: FREE CHLORINE ANALYSER
ALL TEMPERATURE ELEMENT WILL BE RTD TYPE UNLESS IDENTIFIED AS TERMOCOUPLE (TC) TYPE ON P&ID. FIELD INSTRUMENT LOCATION SHALL BE MENTIONED IN P&ID WITH BUILDING TAG.
0B
A
B
C
D
E
F
G
SUM/ADD
DIVIDE/RATIO
X
MULTIPLY
HIGH SELECTOR
LOW SELECTOR
DIFFERENCE
INPUT/OUTPUT THE FOLLOWING:
n
AVERAGE
INTEGRAL
n
ROOT EXTRACT
M
K
-K
nn
X X
f(x) f(x)
MIDDLE SIGNAL SELECT
PROPORTIONAL
REVERSE PROPORTIONAL
HIGH LIMITER
LOW LIMITER
EXPONENTIAL
VARIABLE FUNCTION (PRESSURE, TEMPERATURE…)
POSITIVE BIAS
NEGATIVE BIAS
ABBREVIATIONS
A/M ASC
ASD BTEX BV C
CCS DCS ESD
FGS GC HHV IES IGV LCP
AUTO/MAN ANTI-SURGE CONTROL SYSTEM
0B
0B
ADJUSTABLE SPEED DRIVE BENZENE TOLUENE XYLENE ANALYSIS BY VENDOR CLOSE
COMPRESSOR CONTROL SYSTEM DISTRIBUTED CONTROL SYSTEM EMERGENCY SHUTDOWN
FIRE AND GAS SYSTEM CHROMATOGRAPHY HIGHER HEATING VALUE INSTRUMENTED EQUIPMENT SHELTER INLET GUIDE VANE LOCAL CONTROL PANEL
0B
LOR MCC MMS MW O PLC
PST PV RTD
S/D
SCS SIS SK
SP
LOCAL OFF REMOTE MOTOR CONTROL CENTER MACHINE MONITORING SYSTEM MOLECULAR WEIGHT OPEN PROGRAMMABLE LOGIC CONTROLLER
0B
PARTIAL STROKE TEST PROCESS VARIABLE RESISTANCE TEMPERATURE DEVICE
SHUTDOWN
0B
SPCS
SPLC
TC TGS TSO UCP VFD XOOY
SAMPLE CONDITIONING SYSTEM SAFETY INSTRUMENTED SYSTEM SKIN
SET POINT
A D E I H O P R MV
ANALOG DIGITAL VOLTAGE CURRENT HYDRAULIC ELECTROMAGNETIC PNEUMATIC RESISTANCE MILLIVOLT
0B
0A
0
12-Feb-2025
18-Oct-2024
05-Jul-2024
REV
DATE
SCALE:
DRAWN:
IFD - Issued for Design
VCH
AK/SB/JGO
ADE
IFH - ISSUED FOR HAZOP
VCH
AK/SB/JGO
ADE
ICR - ISSUED FOR CLIENT REVIEW
VCH
AK/SB/JGO
ADE
DESCRIPTION
CHKD:
DRAWN
CHKD
APPRD
APPRD:
NONE
VCH
AK/SB/JGO
ADE
H
CONTRACTOR
PROJECT TITLE
SAMPLE PRE CONDITIONING SYSTEM
SAFETY PROGRAMMABLE LOGIC CONTROLLER
THERMOCOUPLE TANK GAUGING SYSTEM TIGHT SHUT-OFF UNIT CONTROL PANEL (PLC PACKAGE) VARIABLE FREQUENCY DRIVE X OUT OF Y VOTING SYSTEM
RUWAIS LNG PROJECT
DRAWING TITLE
PIPING & INSTRUMENTATION DIAGRAM UNIT 000 GENERAL INSTRUMENTATION SYMBOLS
UNIT:
000 CONTR. PROJ. No.
PLANT:
RUWAIS
215122C
DOC. CLASS:
1.5 CONT. DWG. No.:
DOC. CAT:
2
215122C-000-PID-0090-0004
ADNOC GAS AGREEMENT No.
4700022871
OC DWG. No.:
ADNOC GAS PROJ. No.
ADNOC GAS DWG. No.
22-146
RLNG-000-PR-PID-0004
SHEET
REV.
0B 01/01 SHEET SIZE : A1
I
J
i
I
d p . B 0 _ 4 0 0 0
D P R P
0 0 0
G N L R
: .
O N D A C
2
3
4
5
6
7
8
9
10
11
12
13
14
15
Project: Q-32859 - NMDC - Ruwais Folder: RFQ Files