REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION
DE LINEAR-ALKYL-BENZENE <
CT-EPC/017/SH/EPM/RPC-X/2023
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
1
of 65
ISSUE 0
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
0 Issue
05.Dec.2024 Date
IFR - Issued for Review Reason for Issue – Revision Description
R. Gunjal Prep’d
N. Metrillo Chk’d
E. Magadeev App’d
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
2 of 65
ISSUE 0
1 2 3 4 5 6
7
8
SCOPE REFERENCE DOCUMENTS ABBREVIATIONS LAWS & REGULATIONS CODES & STANDARDS ENVIRONMENTAL CONDITIONS
6.1 Buildings 6.2 Outdoor
GENERAL REQUIREMENTS
7.1 General
SUPPLY CONDITIONS 8.1 Cable Sizes 8.2 Cable Ends 8.3 Identification and Marking on Cables 8.4 Identification and Marking on Cable Drums 8.5 Identification and Marking on Drums for Fiber Optic Cables
9
TESTING ON INSTRUMENT CABLES
9.1 Test on Construction Characteristics 9.2 Test on Physical Characteristics 9.3 Test on Electrical Characteristics
TESTING ON FIBER OPTIC CABLES
10 11 GENERAL NOTES
Cable Types: Thermocouple K Type Cables
1 2
Single Pair Shielded 1x2x18 AWG Single Pair Shielded 12x2x20 AWG
Identification Code:
F-Kx-A1 F-Kx-A12
Armoured cables for Analogue Signals 4-20mA and Digital signals, FRT Flame Retardant
Single Pair Shielded 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded 2x2x1.5 mm2 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 Multipair, Individual and Overall Shielded 24x2x0.5 mm2 Single Pair Shielded Ex-i Service 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded Ex-i Service 2x2x1.5 mm2
3 4 5 6 7 8 9 10 11 Multipair, Individual and Overall Shielded Ex-i Service 6x2x0.5 mm2 / 8x2x0.5 mm2 F-IS-C6 / F-IS-C8 12 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2F-IS-C12 / F-IS-C16 13 Multipair, Individual and Overall Shielded Ex-i Service 20x2x0.5 mm2 14 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2
F-C1 F-C2 F-C6 / F-C8 F-C12 / F-C16 F-C20 F-C24 F-IS-C1 F-IS-C2
F-IS-C20 F-IS-C24
Armoured cables for Power Supply Output (solenoid, lamp, relay coil etc. 24Vdc), FRT Flame Retardant
Single Pair 1x2x2.5 mm2
15 16 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 17 Multipair 12x2x2.5 mm2 18 Multipair 16x2x2.5 mm2
Armoured Cables for RTD and 3-wire Application, FRT Flame Retardant
Single Triad, Shielded 1x3x1.5 mm2
19 20 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 21 Multi-Triad, Individual and Overall Shielded 12x3x1.5 mm2 / 16x3x1.5 mm2 22 Multi-Triad, Individual and Overall Shielded 24x3x1.5 mm2 23 24 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2
Single Triad, Shielded Ex-i Service 1x3x1.5 mm2
F-D1 F-D6 / F-D8 F-D12 F-D16
F-E1 F-E6 / F-E8 F-E12 / F-E16 F-E24 F-IS-E1 F-IS-E6 / F-IS-E8
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Page 5 5 5 5 6 7 7 7 8 8 9 9 9 9 9 10 10 10 10 10 11 11
12 12
13 13 14 14 15 15 16 16 17 17 18 18
19 19 20 20
21 21 22 22 23 23
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev Cable Types:
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
3 of 65
ISSUE 0
Identification Code:
Page
Armoured Cables for RTD and 3-wire Application, FRT Flame Retardant
25 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 26 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2
F-IS-E12 / F-IS-E16 F-IS-E24
Armoured cables for Analogue Signals 4-20mA and Digital signals, FRS Fire Resistant
Single Pair Shielded 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded 2x2x1.5 mm2
27 28 29 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 30 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 31 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 32 Multipair, Individual and Overall Shielded 24x2x0.5 mm2 33 34 35 Multipair, Individual and Overall Shielded Ex-i Service 6x2x0.5 mm2 / 8x2x0.5 mm2 F-IS-R6 / F-IS-R8 36 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2F-IS-R12 / F-IS-R16 37 Multipair, Individual and Overall Shielded Ex-i Service 20x2x0.5 mm2 38 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2
Single Pair Shielded Ex-i Service 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded Ex-i Service 2x2x1.5 mm2
F-R1 F-R2 F-R6 / F-R8 F-R12 / F-R16 F-R20 F-R24 F-IS-R1 F-IS-R2
F-IS-R20 F-IS-R24
Armoured Cables for RTD and 3-wire Application, FRS Fire Resistant
Single Triad, Shielded 1x3x1.5 mm2
39 40 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 41 Multi-Triad, Individual and Overall Shielded 12x3x1.5 mm2 / 16x3x1.5 mm2 42 Multi-Triad, Individual and Overall Shielded 24x3x1.5 mm2 43 44 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2 45 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 46 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2
Single Triad, Shielded Ex-i Service 1x3x1.5 mm2
F-S1 F-S6 / F-S8 F-S12 / F-S16 F-S24 F-IS-S1 F-IS-S6 / F-IS-S8 F-IS-S12 / F-IS-S16 F-IS-S24
Armoured cables for Power Supply Output (solenoid, lamp, relay coil etc. 24Vdc), FRS Fire Resistant
Single Pair 1x2x2.5 mm2
47 48 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 49 Multipair 12x2x2.5 mm2 50 Multipair 16x2x2.5 mm2
F-T1 F-T6 / F-T8 F-T12 F-T16
Armoured cables for 230Vac Power Supply Output (Instruments External Supply) FRT Flame Retardant
Single Pair 1x2x2.5mm2 + G
51 52 Multipair 6x2x2.5mm2 + G / 8x2x2.5mm2 + G 53 Multipair 12x2x2.5 mm2 + G 54 Multipair 16x2x2.5 mm2 + G
F-U1 F-U6 / F-U8 F-U12 F-U16
Armoured cables for 230Vac Power Supply Output (Instruments External Supply) FRS Fire Resistant
1x2x2.5mm2 + G
55 56 Multicore 6x2x2.5mm2 + G / 8x2x2.5mm2 + G 57 Multipair 12x2x2.5 mm2 + G 58 Multipair 16x2x2.5 mm2 + G
Unarmoured Cables Inside Building - FRT Flame Retardant
F-V1 F-V6 / F-V8 F-V12 F-V16
Single Pair Shielded 1x2x1.5 mm2
Single Pair Shielded Ex-i Service 1x2x1.5 mm2
59 60 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 61 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 62 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 / 24x2x0.5 mm2 63 64 Multipair, Individual and Overall Shielded Ex-i Service 6x2x0.5 mm2 / 8x2x0.5 mm2 B-IS-A6 / B-IS-A8 65 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2B-IS-A12 / B-IS-A16 66 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2 67 68 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 69 Multipair 12x2x2.5 mm2 70 Multipair 16x2x2.5 mm2
B-A1 B-A6 / B-A8 B-A12 / B-A16 B-A20 / B-A24 B-IS-A1
B-IS-A24 B-B1 B-B6 / B-B8 B-B12 B-B16
Single Pair 1x2x2.5 mm2
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
24 24
25 25 26 26 27 27 28 28 29 29 30 30
31 31 32 32 33 33 34 34
35 35 36 36
37 37 38 38
39 39 40 40
41 41 42 42 43 43 44 44 45 45 46 46
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev Cable Types:
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
4 of 65
ISSUE 0
Identification Code:
Page
Unarmoured Cables Inside Building - FRT Flame Retardant
Single Triad, Shielded 1x3x1.5 mm2
Single Triad, Shielded Ex-i Service 1x3x1.5 mm2
71 72 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 73 74 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2 75 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 76 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2
Unarmoured Cables Inside Building - FRT Flame Retardant
Single Pair 1x2x2.5 mm2 + G
77 78 Multipair 6x2x2.5mm2 + G / 8x2x2.5mm2 + G
Unarmoured Cables Inside Building - FRS Fire Resistant
B-C1 B-C6 / B-C8 B-IS-C1 B-IS-C6 / B-IS-C8 B-IS-C12 / B-IS-C16 B-IS-C24
B-D1 B-D6 / B-D8
Single Pair 1x2x2.5 mm2
Single Pair Shielded 1x2x1.5 mm2
Single Pair Shielded Ex-i Service 1x2x1.5 mm2
B-R1 B-R6 / B-R8 B-R12 / B-R16 B-R20 / B-R24 B-IS-R1 B-IS-R8
79 80 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 81 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 82 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 / 24x2x0.5 mm2 83 84 Multipair, Individual and Overall Shielded Ex-i Service 8x2x0.5 mm2 85 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2B-IS-R12 / B-IS-R16 86 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2 87 88 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 89 Multipair 12x2x2.5 mm2 90 Multipair 16x2x2.5 mm2 91 92 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 93 Multi-Triad, Individual and Overall Shielded 12x3x1.5 mm2 / 16x3x1.5 mm2 94 Multi-Triad, Individual and Overall Shielded 24x3x1.5 mm2 95 96 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2 97 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 98 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2 99 100 Multipair 6x2x2.5mm2 + G / 8x2x2.5mm2 + G
B-IS-R24 B-G1 B-G6 / B-G8 B-G12 B-G16 B-H1 B-H6 / B-H8 B-H12 / B-H16 B-H24 B-IS-H1 B-IS-H6 / B-IS-H8 B-IS-H12 / B-IS-H16 B-IS-H24 B-K1 B-K6 / B-K8
Single Triad, Shielded Ex-i Service 1x3x1.5 mm2
Single Triad, Shielded 1x3x1.5 mm2
Single Pair 1x2x2.5 mm2 + G
Earthing Cables
101 Earthing Cable 01C x 6 mm2 102 Earthing Cable 01C x 10 mm2 103 Earthing Cable 01C x 16 mm2 104 Earthing Cable 01C x 25 mm2
Armoured Fibre Optic Cables - Fire Resistant
105 106 107 108
8 Fibers, Single Mode 12 Fibers, Single Mode 24 Fibers, Single Mode 48 Fibers, Single Mode
E-06 E-10 E-16 E-25
FO-8 FO-12 FO-24 FO-48
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
47 47 48 48 49 49
50 50
51 51 52 52 53 53 54 54 55 55 56 56 57 57 58 58 59 59 60 60 61 61
62 62 63 63
64 64 65 65
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
5 of 65
ISSUE 0
1
SCOPE
This document establishes the instrument general specification for the execution of the EPC phase of the project
“REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-BENZENE<
The guidelines reported in the present specification shall apply to the new LAB complex. Installation in the existing complex (i.e RA1K, etc.) shall follow the existing complex rules. All equipment, material and systems shall in all respect be suitable for reliable operation in service conditions stated in the Basic Engineering Design Data (BEDD, doc. № 4439-YZ-SG-000000001)
2
REFERENCE DOCUMENTS
4439-KK-SG-000000001
INSTRUMENT GENERAL SPECIFICATION
3
ABBREVIATIONS AND DEFINITIONS
Abbreviation
Description
CCTV
HSE
DCS
ESD
FGS
FOBB
MMS
MCR
MCB
RIB
TGS
Security closed circuit television
Health Safety Environment
Distributed Control System
Emergency Shut Down
Fire and Gas Detection System
Fiber Optic Back Bone
Machine Monitoring System
Main Control Room
Main Control Building
Remote Instrument Building
Tank Gauging System
CA / COMPANY / Maitre de l’Ouvrage
SONATRACH DC-EPM
CONTRACTOR / Entrepreneur
TECNIMONT SPA
PROJECT
REALISATION EN EPC D’INSTALLATIONS DE
PRODUCTION DE LINEAR-ALKYL-BENZENE
<
4
LAWS & REGULATIONS
In general, the new LAB complex facilities will be designed in accordance with internationally recognized codes and standards.
The complete list of codes, standards and norms applicable to the EPC phase of LAB project and the associated utilities are listed in INDEX OF PROJECT REGULATIONS, CODES AND APPLICABLE STANDARDS 4439-YZ-PC-000000018.
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
6 of 65
ISSUE 0
Rev
5
CODES & STANDARDS
Document Number
BS-EN-60584-1/BS-EN-60584-3
ANSI/TIA/EIA 598-A
BS-EN-61073
BS-EN-60874
BS-EN-61274
EN 50288-7
EN 50290-2-22
EN 50290-2-29
Document Title Thermocouples - Part 1: EMF specifications and tolerances Thermocouples - Part 3: Extension and compensating cables - Tolerances and identification system Optical Fibre Cable Color Coding
Mechanical splicers and fusion splice protectors for optical fibres and cables
Connectors for Optical Fibres and Cables
Fibre Optic Adaptors
Multi-element metallic cables used in analogue and digital communication and control. Sectional specification for instrumentation and control cables.
Communication cables. Common design rules and construction. PVC sheathing compounds
Communication cables. Common design rules and construction. Cross-linked PE insulation compounds
ICEA S-82 552 (NEMA WC 55)
Instrumentation Cables and Thermocouple Wire – Oil resistance test
IEC 60228
Conductors of insulated cables
IEC 60331-11
IEC 60331-21
IEC 60331-25
IEC 60332-1-2
IEC 60332-3-22
IEC 60793-2-10
IEC 60793-2-50
IEC 60794-1-1
IEC 60794-1-2
IEC 60794-2
IEC 60794-3
IEC 61300
IEC 61515
IEC 61931
Tests for electric cables under fire conditions - circuit integrity – part 11: apparatus - fire alone at a flame temperature of at least 750 degrees C
Tests for electric cables under fire conditions - circuit integrity – procedures and requirements – cables of rated voltage up to and including 0.6/1.0 kV.
Tests for electric cables under fire conditions - Circuit Integrity Part 25: Procedures and requirements - Optical fibre cables
Tests on electric and optical fiber cables under fire conditions – Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame
Tests on electric and optical fiber cables under fire conditions - part 3- 22: test for vertical flame spread of vertically-mounted bunched wires or cables - category A
Optical fibres - Part 2-10: Product specifications - Sectional specification for category A1 multimode fibres
Optical fibres - Part 2-50: Product Specifications - Sectional specification for class B single-mode fibres
Optical Fibre cables – Part 1-1: Generic specification – General
Optical Fibre cables – Part 1-2: Generic specification – Cross reference table for optical cable test procedures
Optical fibre cables - Part 2: Indoor cables - Sectional specification
Optical fibre cables - Part 3: Sectional specification - Outdoor cables
Fibre Optic interconnecting devices and passive components Basic test and measurement procedures
Mineral insulated thermocouple cables and thermocouples
Fibre Optic – Terminology
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
7 of 65
ISSUE 0
Document Number
Document Title
ITU-T G-651.X
Characteristics of a 50/125 µm multimode graded index optical fibre cable for the optical access network.
ITU-T G-652
Characteristic of a Single Mode Optical Fibre and Cable (ITU-T Recommendation).
ITU-T G-653
ITU-T G-654
ITU-T G-655
ITU-T G-656
UL 1581
Characteristics of a dispersion-shifted, single-mode optical fibre and cable (ITU-T Recommendation).
Characteristics of a cut-off shifted single-mode optical fibre and cable (ITU-T Recommendation).
Characteristics of a NON-ZERO dispersion-shifted, single-mode optical fibre and cable (ITU-T Recommendation).
Characteristics of a fibre and cable with non-zero dispersion for wideband optical transport (ITU-T Recommendation).
Reference Standard for Electrical Wires, Cables, and Flexible Cords – Sunlight resistance section 1200.
Vendor’s compliance with other than the above-mentioned Standards of Codes shall be declared for Owner’s approval.
6
ENVIRONMENTAL CONDITIONS
6.1 Buildings
Main control building and generally all indoor areas and rooms, where Cables will be installed, will be air conditioned. The air conditioning will be designed to guarantee the following indoor conditions:
Environmental Conditions
Temperature
Relative Humidity
Max temperature indoor min temperature indoor
25 °C 18 °C
50% ± 10 50% ± 10
a.
b.
c.
Design temperature for electrical equipment installed indoors shall be 1°C ÷ 47°C.
Vendor is required to provide details of the maximum/minimum temperature and relative humidity limits, within which Vendor can guarantee system performance, in the power on condition, during prolonged failure of the HVAC system.
Vendor shall state the maximum working temperature of all equipment supplied.
6.2 Outdoor
The most severe climatic data are defined below and shall be used to define the common design basis for the LAB complex in the existing industrial zone of Skikda. Refer to document ‘’BASIC ENGINEERING DESIGN DATA’’ № 4439-YZ-SG-000000001.
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
8 of 65
ISSUE 0
Environmental Conditions
Temperature:
Highest maximum on record
Lowest temperature - Minimum Design Metal Temperature
Max Design Temperature for Instrumentation (Outdoor)
Relative Humidity:
Annual average mean
Average min (%)
Average Max (%)
Design value for air fans, compressores and gas turbines (%)
Value
Notes
1
2
3, 4, 5
47 °C
1 °C
50 °C
72
69 (July)
79 (March)
72
Notes:
-
This is the maximum shade air temperature that the equipment and systems must be physically designed for. Equipment must also be able to operate continuously at this temperature.
-
This is the minimum shade air temperature that the equipment and systems must be designed for. Equipment must also be able to operate continuously at this temperature.
-
Electrical/electronic equipment located outdoors shall be rated for an ambient temperature of 50°C. Electrical equipment (i.e. panels, etc.) to be located indoors and all cables shall be rated for continuous operation in an ambient temperature of 40°C.
-
Electrical/electronic equipment and cables shall be located away from direct sunlight wherever possible. Equipment located outside shall be provided with sunshades or shields to protect the equipment from solar heat gain.
-
All electronic devices in direct sunlight should be designed to withstand and operate with a surface temperature of 85°C. If this is not possible the Supplier shall design adequate sun shading and inform Owner’s Engineer of requirements.
7
GENERAL REQUIREMENTS
7.1 General
a) This Job Specification covers the following cables:
-
Thermocouple extension cables (millivolts)
-
Cables for analogue signals (continuous) - typically 4-20 mA and digital inputs
-
Cables for digital output signals (24Vdc)
-
Cables for instruments power supply (24Vdc)
-
Cables for instruments power supply (230Vac)
-
Cables for RTD signals and three wires application
-
Cables for Motor-operated valves (Control command only)
-
Fire Resistance Cables, for F&G detectors & F&G (Horn & Flashing light)
-
Cables for indoor analogue, digital and RTD signals
-
Fiber Optic Cables.
b)
c)
Field cables as above specified with the following details: Single and Multi-pair/Triple/Multi-wire shall be suitable for installation aboveground in cable tray, underground in cable ducts or direct buried with a suitable armouring. Detailed characteristics for each type of cable are listed in the dedicated cable type pages of this document.
Indoor cables as above specified with the following details: Single and Multi-pair/Triple/Multi-wire shall be suitable for installation aboveground or under false floor cable trays, without any armouring. Low smoke zero halogen cables to be used. Detailed characteristics for each type of cable are listed in the dedicated cable type pages of this document.
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
9 of 65
ISSUE 0
d)
Fire Resistance Cables as above specified with the following details: Fire-rated cable (without any fireproofing) shall be used when fire-resistance is required for aboveground wiring. Fire-rated cables shall be suitable for operability for at least 90 minutes when exposed to fire at 750°C as per IEC 60331 section 11.
8
SUPPLY CONDITIONS
8.1 Cable Sizes
Unless otherwise stated or agreed, cables shall be supplied in lengths provided in individual specification issued for order. Quantities of cable lengths (Bill of Material) to be supplied by Vendor shall be as specified. Cable type wise in Material Requisition 4439-KK-MR-352001. Vendor shall indicate in proposal, against each type of cable, minimum & maximum cable length possible in a single cable drum.
8.2 Cable Ends
The ends of each cable shall be protected by a suitable waterproof female compression plug fastened with adhesive tape, or with heat shrinkable sheath or hygroscopic plastic seal.
8.3
Identification and Marking on Cables In addition to the information required by the specified standard, the following information shall be printed at every 1 meter (maximum) on the external outer sheath of entire cable : Markings shall be able to withstand commercial/industrial cleaning agents, and the environmental conditions for which the cable is manufactured.
-
Cable Type (TCM Commodity Code)
-
Number of Pairs / Triads / Cores
-
Part Number
-
Insulation Type
-
Conductor Size and Number of Conductors
-
Temperature Range
-
Rated Voltage
-
Cable Construction
-
Construction Year
-
Applicable STD
-
Manufacturer’s Name
-
The Metrical Progressive Numeration
-
Fire Behavior when affected by fire
The Pair, Triads and Core numbers shall be printed on the wires at least every 50mm interval.
Example of Marking :
BKI032SE01P_1_____PP 1 Pair x 1 mm² 300/300V Cu/XLPE/LS0H 2019 Manufacturer name
- Progressive length of cable at every meter
8.4
Identification and Marking on Cable Drums Cable drum should have identification plates (one on both sides of the drum), the identification plates should be white (300mm x 150mm) with black lettering weather resistant, the identification plate shall provide following:
-
Client - Location - Project
-
Cable voltage rating
-
Cable identification as per TCM commodity code
-
Total weight of cable and drum (kg)
-
PO ref. number and MR number
-
Cable type and size.
-
Drum cable length
-
Drum number (Drum number will be intimated by contractor after P.O.),
-
Construction year, total mass & tare
-
Manufacturers name
-
Minimum bending radius for installation
-
Maximum pulling tension
Vendor shall provide maximum length of each cable type in a cable drum. After Purchase order, Contractor will intimate drum wise required quantity to Vendor. Cable length tolerance on each drum: -0 % to +3 %.
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
10 of 65
ISSUE 0
8.5
Identification and Marking on Drums for Fiber Optic Cables The identification plate shall contain the following information for Fiber Optic Cables:
-
CLIENT – Location – PROJECT
-
Material Requisition Number
-
Manufacturer name and year of construction
-
Cable Type and Size (for instance: 12 cores 62.5/125 µm)
-
Fire behavior when affected by fire: (for instance: IEC 60332-3)
-
Reel Number (given to Vendor before starting with coil construction)
-
Reel length and gross weight
9
TESTING ON INSTRUMENT CABLES
Vendor will provide test certification of each cable in accordance with the requirements of applicable international, national codes and practices.
Factory test according to BS-EN 50288 (for cables 300/500V) or IEC 60502-1 (for cables 0.6/1kV up to 3kV) on all supplied cables shall be executed.
Type tests will be according to the relevant Inspection Test Plan Document attached in the Supply Specification 4439-KK-SS-352001.
Vendor shall provide a cable test certificate for each manufactured type of cable.
9.1
Test on Construction Characteristics
Following tests shall be performed:
-
Cable formation
-
Conductor configuration & diameters of conductor wire
-
Thickness of primary insulation,
-
Construction and thickness of electrostatic shields and configuration & diameter of drain wires
-
Thickness of outer sheath
-
Execution/thickness of Armour
-
Cable outside diameter
-
Cable length tolerances : -0% to +3%
9.2
Test on Physical Characteristics
Following tests shall be performed:
- Testing of Mechanical properties (Tensile stress, Elongation at break) of primary insulation and the outer sheath
with and without ageing / Thermal ageing shall be carried out according to the EN 50288-7.
- Test of thermoplastic properties of primary insulation & outer sheath shall be carried out
according to the EN 50288-7.
-
Circuit Integrity Fire Test as per IEC 60331-21
-
Bending Test as per IEC 60794-1-2E6
-
Oxygen index shall be carried out as per IEC 60811 & IEC 60502-1 (As far as applicable).
9.3
Test on Electrical Characteristics
Following tests shall be performed:
-
Continuity test
-
Voltage test
-
Measurement of Electrical resistance of conductor
-
Measurement of Electrical resistance of drain wire
-
Measurement of Inductance and capacitance values between the conductors
-
Measurement of Insulation resistance shall be in accordance with the respective Standards.
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
11 of 65
ISSUE 0
10
TESTING ON FIBER OPTIC CABLES Vendor will provide test certification of each cable in accordance with the requirements of applicable international, national codes and practices.
Type tests will be according to the relevant Inspection Test Plan Document attached in the Supply Specification 4439-KK-SS-352001.
Vendor shall provide a cable test certificate for each manufactured type of cable.
The tests shall include for each testing length, optical time domain reflectometry measurement (OTDR) and attenuation coefficient. For runs over 100 meters the test shall be made at both ends and the two measurements compared. Differences greater than could be caused from instrument resolution shall be investigated and resolved. Attenuation coefficient shall be measured to ensure compliance with the design specification. The measurement shall be summarized in a graphic (Back Scattering Diagram) which shall also be used for localized losses detection during installation. In particular the tests carried out by the Supplier shall be the following:
- Attenuation measurements for each fibre in dB/km (average and maximum) in all the cable lengths of the supplied lot.
- Back scattering diagram.
- General inspection on construction conformance.
- Certified test-reports for all deliverables.
- Test and certification of bandwidth and attenuation, continuity on drums attenuation on drums.
Moreover, for each fibre:
- Attenuation coefficient and chromatic dispersion wavelengths for 1310 nm and 1550 nm (single-mode fibre only)
- Zero dispersion wave length
- Zero dispersion slope
The tests to be performed by the Manufacturer shall demonstrate that the cable has been provided and constructed in accordance with the specifications and applicable standards.
11 GENERAL NOTES
Pair Identification:
-
Single pair conductor shall have polarity sign (+) or (-) stamped.
-
In multipair cable each pair shall be numbered (on each conductor). On all conductor polarity sign (+) or (-) shall be stamped.
-
Numbering and polarity shall be made at regular distances of 100 mm with contrasting color (i.e. Number white for black wire).
Inner Sheath Thickness
- Minimum 1 mm for cable diameter under armour up to 25mm. 1,2 mm for cable over 25 mm (under armour).
Outer Sheath Thickness
-
Minimum 1,4 mm for cable diameter under outer sheath up to 20 mm. Min. 2 mm for cable from 20 to 25 mm (under sheath), and min. 2,5 mm up to 3 mm for higher dimensions.
-
Thickness should be determined following the formula T = 0,04 x D 1,1 (min 1,3 mm), where “D” is the diameter under outer sheath.
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
12 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
1
TBD
TBD
F-Kx-A1
2
TBD
TBD
F-Kx-A12
1x2x16 AWG Kx Type Armoured Thermocouple Cable
12x2x20 AWG Kx Type Armoured Thermocouple Multicable
BS-EN-60584
Thermocouple type Kx
Yellow (+) / Red (-)
16 AWG
EN 50290-2-29
XLPE - Resistance 90°C
Yellow / Red
EN 50288-7 Table 1
N/A
Not Required
≥ 20 times/m
BS-EN-60584
Thermocouple type Kx
Yellow (+) / Red (-)
20 AWG
EN 50290-2-29
XLPE - Resistance 90°C
Yellow / Red
EN 50288-7 Table 1
Max lay of Length up to 1,5 mm2 ≤ 100mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
Not Required
Not Required
Not Required
Not required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Yellow
Steel wire armour
PVC-TI3 (90°)
Yellow
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Yellow
Steel wire armour
PVC-TI3 (90°)
Yellow
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; BS-EN-60584
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
13 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
3
TBD
TBD
F-C1
4
TBD
TBD
F-C2
1x2x1.5mm2 Single Pair Armoured Cable for Analogue and Digital Signals - Flame Retardant
2x2x1.5mm2 Double Pair Armoured Cable for Analogue and Digital Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
14 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
5
TBD
TBD
6
TBD
TBD
F-C6 / F-C8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant
F-C12 / F-C16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
15 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
7
TBD
TBD
F-C20
8
TBD
TBD
F-C24
20x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant
24x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
16 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
9
TBD
TBD
F-IS-C1
10
TBD
TBD
F-IS-C2
1x2x1.5mm2 Single Pair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant
2x2x1.5mm2 Double Pair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
Yes
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
17 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
11
TBD
TBD
12
TBD
TBD
F-IS-C6 / F-IS-C8 6x2x0.5mm2 / 8x2x0.5mm2 Single Pair I.S. Armoured Cable forAnalogue and Digital Signals - Flame Retardant
F-IS-C12 / F-IS-C16 12x2x0.5mm2 / 16x2x0.5mm2 Multpair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
Yes
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
18 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
13
TBD
TBD
F-IS-C20
14
TBD
TBD
F-IS-C24
20x2x0.5mm2 Multpair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant
24x2x0.5mm2 Multpair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
Yes
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
19 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
15
TBD
TBD
F-D1
1x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant
16
TBD
TBD
F-D6 / F-D8 6x2x2.5mm2 / 8x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
Red / Black
EN 50228-7 Table 1
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
20 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
17
TBD
TBD
F-D12
18
TBD
TBD
F-D16
12x2x2.5 mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant
16x2x2.5 mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black
EN 50228-7 Table 1
Red / Black
EN 50228-7 Table 1
Max length of lay up to 2.5 mm2 ≤ 150 mm
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
21 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
19
TBD
TBD
F-E1
1x3x1.5 mm2 Single Triad Armoured Cable for RTD and 3 wire devices - Flame Retardant
20
TBD
TBD
F-E6 / F-E8 6x3x1.5 mm2 / 8x3x1.5 mm2 Multitrad Armoured Cable for RTD and 3 wire devices - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
22 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
21
TBD
TBD
F-E12 / F-E16 12x3x1.5mm2 / 16x3x1.5mm2 Multitrad Armoured Cable for RTD and 3 wire devices - Flame Retardant
22
TBD
TBD
F-E24
24x3x1.5 mm2 Multitrad Armoured Cable for RTD and 3 wire devices - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
23 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
23
TBD
TBD
F-IS-E1
1x3x1.5mm2 Single Triad Armoured I.S Cable for RTD and 3 wire devices - Flame Retardant
24
TBD
TBD
F-IS-E6 / F-IS-E8 6x3x1.5mm2 / 8x3x1.5mm2 Multitrad Armoured I.S. Cable for RTD and 3 wire devices - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
24 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
25
TBD
TBD
F-IS-E12 / F-IS-E16 12x3x1.5mm2 / 16x3x1.5mm2 Multitrad Armoured I.S. Cable for RTD and 3 wire devices - Flame Retardant
26
TBD
TBD
F-IS-E24
24x3x1.5 mm2 Multitrad Armoured I.S. Cable for RTD and 3 wire devices - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
Not Required
EN 50290-2-22
PVC-TI3 (90°)
Light Blue
Steel wire armour
PVC-TI3 (90°)
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
25
of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
27
TBD
TBD
F-R1
28
TBD
TBD
F-R2
1x2x1.5 mm2 Single Pair Armoured Cable for Analogue and Digital Signals - Fire Resistant
2x2x1.5 mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red
Not Required
EN 50290-2-22
SHF 2
Red
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
SHF 1
Red
SHF 1
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
26
of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
29
TBD
TBD
30
TBD
TBD
F-R6 / F-R8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Armoured Cable forAnalogue and Digital Signals - Fire Resistant
F-R12 / F-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red
Not Required
EN 50290-2-22
SHF 2
Red
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
SHF 1
Red
SHF 1
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
27
of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
31
TBD
TBD
F-R20
32
TBD
TBD
F-R24
20x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant
24x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red
Not Required
EN 50290-2-22
SHF 2
Red
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
SHF 1
Red
SHF 1
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
28 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
33
TBD
TBD
F-IS-R1
34
TBD
TBD
F-IS-R2
1x2x1.5mm2 Single Pair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant
2x2x1.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
29 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
35
TBD
TBD
36
TBD
TBD
F-IS-R6 / F-IS-R8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant
F-IS-R12 / F-IS-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
30 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
37
TBD
TBD
F-IS-R20
38
TBD
TBD
F-IS-R24
20x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant
24x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
31 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
39
TBD
TBD
F-S1
40
TBD
TBD
F-S6 / F-S8
1x3x1.5mm2 Single Triad Armoured Cable for RTD and 3 wire devices - Fire Resistant
6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Armoured Cable for RTD and 3 wire devices - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red
Not Required
EN 50290-2-22
SHF 2
Red
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
SHF 1
Red
SHF 1
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
32 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
41
TBD
TBD
F-S12 / F-S16
42
TBD
TBD
F-S24
12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Armoured Cable for RTD and 3 wire devices - Fire Resistant
24x3x1.5mm2 Multitriad Armoured Cable for RTD and 3 wire devices - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red
Not Required
EN 50290-2-22
SHF 2
Red
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
SHF 1
Red
SHF 1
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
33 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
43
TBD
TBD
F-IS-S1
1x3x1.5mm2 Single Triad Armoured Cable for RTD and 3 wire devices - Fire Resistant
44
TBD
TBD
F-IS-S6 / F-IS-S8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Armoured I.S. Cable for RTD and 3 wire devices - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
34 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
45
TBD
TBD
F-IS-S12 / F-IS-S16 12x3x1.5 mm2 / 16x3x1.5 mm2 Multitriad Armoured I.S. Cable for RTD and 3 wire devices - Fire Resistant
46
TBD
TBD
F-IS-S24
24x3x1.5 mm2 Multitriad Armoured I.S. Cable for RTD and 3 wire devices - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Not Required
EN 50290-2-22
SHF 2
Red with Light Blue Stripe
Tinned Copper Wire Braid
SHF 1
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
35 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
47
TBD
TBD
F-T1
1x2x2.5 mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant
48
TBD
TBD
F-T6 / F-T8 6x2x2.5mm2 / 8x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
Red / Black
EN 50228-7 Table 1
Red / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
SHF 2
Red
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
SHF 2
Red
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
SHF 1
Red
SHF 1
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
36 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
49
TBD
TBD
F-T12
50
TBD
TBD
F-T16
12x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant
16x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
MICA tape + EP Rubber
MICA tape + EP Rubber
Red / Black
EN 50228-7 Table 1
Red / Black
EN 50228-7 Table 1
Max length of lay up to 2.5 mm2 ≤ 150 mm
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
SHF 2
Red
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
SHF 2
Red
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
SHF 1
Red
SHF 1
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
37 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
51
TBD
TBD
F-U1
1x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant
52
TBD
TBD
F-U6 / F-U8 6x2x2.5mm2 + Ground / 8x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
2.5 mm2 + G 2.5mm2
EN 50290-2-29
XLPE - Resistance 90°C
2.5 mm2 + G 2.5mm2
EN 50290-2-29
XLPE - Resistance 90°C
Brown / Light Blue / Yellow/Green
Brown / Light Blue / Yellow/Green
IEC 60502
N/A
Not Required
≥ 20 times/m
IEC 60502
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
Not Required
IEC 60502: EN 50290-2-22
IEC 60502: EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
IEC 60502; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
38 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
53
TBD
TBD
F-U12
54
TBD
TBD
F-U16
12x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant
16x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
2.5 mm2 + G 2.5mm2
EN 50290-2-29
XLPE - Resistance 90°C
2.5 mm2 + G 2.5mm2
EN 50290-2-29
XLPE - Resistance 90°C
Brown / Light Blue / Yellow/Green
Brown / Light Blue / Yellow/Green
IEC 60502
IEC 60502
Max length of lay up to 2.5 mm2 ≤ 150 mm
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
Not Required
IEC 60502: EN 50290-2-22
IEC 60502: EN 50290-2-22
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
PVC-TI3 (90°)
Black
Steel wire armour
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
39 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
55
TBD
TBD
F-V1
1x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant
56
TBD
TBD
F-V6 / F-V8 6x2x2.5 mm2 + Ground / 8x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
2.5 mm2 + G 2.5mm2
EN 50290-2-29
MICA tape + EP Rubber
2.5 mm2 + G 2.5mm2
EN 50290-2-29
MICA tape + EP Rubber
Brown / Light Blue / Yellow/Green
Brown / Light Blue / Yellow/Green
IEC 60502
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
IEC 60502
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Not Required
Not Required
IEC 60502: EN 50290-2-22
IEC 60502: EN 50290-2-22
PVC-TI3 (90°)
Black
PVC-TI3 (90°)
Black
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
PVC-TI3 (90°)
Black
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
IEC 60502; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
40 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
57
TBD
TBD
F-V12
58
TBD
TBD
F-V16
12x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant
16x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
2.5 mm2 + G 2.5mm2
EN 50290-2-29
MICA tape + EP Rubber
2.5 mm2 + G 2.5mm2
EN 50290-2-29
MICA tape + EP Rubber
Brown / Light Blue / Yellow/Green
Brown / Light Blue / Yellow/Green
IEC 60502
IEC 60502
Max length of lay up to 2.5 mm2 ≤ 150 mm
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Not Required
Not Required
IEC 60502: EN 50290-2-22
IEC 60502: EN 50290-2-22
PVC-TI3 (90°)
Black
PVC-TI3 (90°)
Black
Sheaths
Armour
Tinned Copper Wire Braid
Tinned Copper Wire Braid
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
PVC-TI3 (90°)
Black
PVC-TI3 (90°)
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
41 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
59
TBD
TBD
60
TBD
TBD
B-A1 1x2x1.5mm2 Single Pair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant
B-A6 / B-A8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Black
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
42 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
61
TBD
TBD
62
TBD
TBD
B-A12 / B-A16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant
B-20 / B-24 20x2x0.5mm2 / 24x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Black
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
43 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
63
TBD
TBD
64
TBD
TBD
B-IS-A1 1x2x1.5 mm2 Single Pair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant
B-IS-A6 / B-IS-A8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Unarmoured I.S. Cable forAnalogue, Digital and Interconnecting Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Light Blue
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
44 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
65
TBD
TBD
66
TBD
TBD
B-IS-A12 / B-IS-A16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured I.S. Cable forAnalogue, Digital and Interconnecting Signals - Flame Retardant
B-IS-A24 24x2x0.5mm2 Multipair Unarmoured I.S. Cable forAnalogue, Digital and Interconnecting Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Light Blue
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
45 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
67
TBD
TBD
68
TBD
TBD
B-B1 1x2x2.5 mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant
B-B6 / B-B8 6x2x2.5mm2 / 8x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
Red / Black
EN 50228-7 Table 1
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Black
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
46 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
69
TBD
TBD
70
TBD
TBD
B-B12 12x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant
B-B16 16x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black
EN 50228-7 Table 1
Red / Black
EN 50228-7 Table 1
Max length of lay up to 2.5 mm2 ≤ 150 mm
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Black
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
47 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
71
TBD
TBD
72
TBD
TBD
B-C1 1x3x1.5mm2 Single Triad Unarmoured Cable for RTD, 3 wire devices and Interconnecting SIgnals - Flame Retardant
B-C6 / B-C8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Black
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
48 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
73
TBD
TBD
74
TBD
TBD
B-IS-C1 1x3x1.5 mm2 Single Triad Unarmoured I.S. Cable for RTD, 3 wire devices and Interconnecting SIgnals
- Flame Retardant
B-IS-C6 / B-IS-C8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Light Blue
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
49 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
75
TBD
TBD
76
TBD
TBD
B-C12 / B-C16 12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant
B-C24 24x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
XLPE - Resistance 90°C
XLPE - Resistance 90°C
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Required
Required
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Light Blue
Light Blue
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
50 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
77
TBD
TBD
B-D1
1x2x2.5 mm2 + Ground Unarmoured Cable for AC Power Supplied Instruments - Flame Retardant
78
TBD
TBD
B-D6 / B-D8 6x2x2.5mm2 + Ground / 8x2x2.5mm2 + Ground Unarmoured Cable for AC Power Supplied Instruments - Flame Retardant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
2.5 mm2 + G 2.5mm2
EN 50290-2-29
XLPE - Resistance 90°C
2.5 mm2 + G 2.5mm2
EN 50290-2-29
XLPE - Resistance 90°C
Brown / Light Blue / Yellow/Green
Brown / Light Blue / Yellow/Green
IEC 60502
N/A
Not Required
≥ 20 times/m
IEC 60502
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
Wrapping of non-hygroscopic tape
Wrapping of non-hygroscopic tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
Not Required
IEC 60502: EN 50290-2-22
IEC 60502: EN 50290-2-22
N/A
N/A
N/A
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Black
Black
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
IEC 60502; IEC 60228
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
51 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
79
TBD
TBD
80
TBD
TBD
B-R1 1x2x1.5 mm2 Single Pair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
B-R6 / B-R8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
52 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
81
TBD
TBD
82
TBD
TBD
B-R12 / B-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
B-R20 / B-R24 20x2x0.5mm2 / 24x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
53 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
83
TBD
TBD
84
TBD
TBD
B-IS-R1 1x2x1.5 mm2 Single Pair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
B-IS-R8 8x2x0.5 mm2 Multipair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
1.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
54 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
85
TBD
TBD
86
TBD
TBD
B-IS-R12 / B-IS-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
B-IS-R24 24x2x0.5 mm2 Multipair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
White (+) / Black (-)
0.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
White / Black
EN 50228-7 Table 1
White / Black
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
55 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
87
TBD
TBD
88
TBD
TBD
B-G1 1x2x2.5 mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant
B-G6 / B-G8 6x2x2.5mm2 / 8x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
Red / Black
EN 50228-7 Table 1
Red / Black
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
56 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
89
TBD
TBD
90
TBD
TBD
B-G12 12x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant
B-G16 16x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
Red (+) / Black (-)
2.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
Red / Black
EN 50228-7 Table 1
Red / Black
EN 50228-7 Table 1
Max length of lay up to 2.5 mm2 ≤ 150 mm
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
57 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
91
TBD
TBD
92
TBD
TBD
B-H1 1x3x1.5 mm2 Single Triad Unarmoured Cable for RTD, 3 wire devices and Interconnecting SIgnals - Fire Resistant
B-H6 / B-H8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
58 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
93
TBD
TBD
94
TBD
TBD
B-H12 / B-H16 12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant
B-H24 24x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
59 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
95
TBD
TBD
96
TBD
TBD
B-IS-H1 1x3x1.5mm2 Single Triad Unarmoured I.S. Cable for RTD, 3 wire devices and Interconnecting SIgnals
- Fire Resistant
B-IS-H6 / B-IS-H8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Required
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
60 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
97
TBD
TBD
98
TBD
TBD
B-IS-H12 / B-IS-H16 12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant
B-IS-H24 24x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Red (24Vdc) / Black (-) / White (COM)
Red (24Vdc) / Black (-) / White (COM)
1.5 mm2
EN 50290-2-29
1.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
Red / Black / White
EN 50228-7 Table 1
Red / Black / White
EN 50228-7 Table 1
Max length of lay up to 1,5 mm2 ≤ 100 mm
Max length of lay up to 1,5 mm2 ≤ 100 mm
Wrapping of non-hygroscopic tapes and fillers
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Required
Required
≥ 4 times/m
PET Tape
Not Required
Required
Required
Laminated Screening Tape (Aluminum/Polyester)
Laminated Screening Tape (Aluminum/Polyester)
20% min.
20% min.
Stranded tinned copper 0.5 mm2
Stranded tinned copper 0.5 mm2
Not Required
EN 50290-2-22
N/A
N/A
N/A
Not Required
EN 50290-2-22
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red with Light Blue Stripe
Red with Light Blue Stripe
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
300/500 V
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
EN 50228-7; IEC 60228
YES
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
61 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
99
TBD
TBD
B-K1
1x2x2.5 mm2 + Ground Unarmoured Cable for AC Power Supplied Instruments - Fire Resistant
100
TBD
TBD
B-K6 / B-K8 8x2x2.5 mm2 + Ground / 8x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant
IEC 60228
IEC 60228
Class 2 (stranded) Annealed Copper
Class 2 (stranded) Annealed Copper
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)
2.5 mm2
EN 50290-2-29
2.5 mm2
EN 50290-2-29
MICA Tape + EP Rubber
MICA Tape + EP Rubber
Brown / Light Blue / Yellow/Green
Brown / Light Blue / Yellow/Green
IEC 60502
N/A
Not Required
≥ 20 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
IEC 60502
Max length of lay up to 2.5 mm2 ≤ 150 mm
Wrapping of non-hygroscopic tapes and fillers
≥ 4 times/m
PET Tape
Not Required
Not Required
Not Required
N/A
N/A
N/A
Not Required
Not Required
IEC 60502: EN 50290-2-22
IEC 60502: EN 50290-2-22
N/A
N/A
N/A
N/A
N/A
N/A
LSZH Compound (Low Smoke Zero Halogen)
LSZH Compound (Low Smoke Zero Halogen)
Red
Red
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
0.6 / 1 kV
2 Kv
BY VENDOR
BY VENDOR
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
IEC 60331-11-21
BY VENDOR
BY VENDOR
IEC 60502; IEC 60228
NO
ICEA S-82-552
IEC 60332-1-2
IEC 60332-3-22 Cat. A
IEC 60331-11-21
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
62 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
101
TBD
TBD
E-06
102
TBD
TBD
E-10
01C x 6 mm², Yellow-Green Earthing Cable
01C x 10 mm², Yellow-Green Earthing Cable
IEC 60228-7 Class 2
Straned annealed copper
N/A
IEC 60228-7 Class 2
Straned annealed copper
N/A
6 mm² (07 strands, Strand dia (*) )
10 mm² (07 strands, Strand dia (*) )
As per IEC 60227-3
As per IEC 60227-3
PVC
PVC
Yellow / Green
Yellow / Green
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
450 / 750 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
450 / 750 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
IEC 60228-7 Class 2; IEC 60227-3
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
63 of 65
ISSUE 0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Conductor
Insulation
Cabling & Assembling
Reference Standard
Type
Colour & Polarity
Size
Ref. Std.
Type
Colour
Thickness (mm)
Cabling Element
Assembling Element
Overall Cabling
Overall Assembling
Moisture Barrier
Pair/Triple/Quads Shield
Shields Ground Wire Communication Wire
Overall Shield
Shield Type
Overlapping
Drain Wire
Ground PE and size
Reference Standard
Inner Sheath Material
Inner Sheath Colour
Sheaths
Armour
Outer Sheath
Outer Sheath Colour
Marking
Bending Radius
Voltage Rating
Voltage Test
Mutual / Grounded Capacitance
Inductance / Conductor Inductance
103
TBD
TBD
E-16
104
TBD
TBD
E-25
01C x 16 mm², Yellow-Green Earthing Cable
01C x 25 mm², Yellow-Green Earthing Cable
IEC 60228-7 Class 2
Straned annealed copper
N/A
IEC 60228-7 Class 2
Straned annealed copper
N/A
16 mm² (07 strands, Strand dia (*) )
25 mm² (07 strands, Strand dia (*) )
As per IEC 60227-3
As per IEC 60227-3
PVC
PVC
Yellow / Green
Yellow / Green
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
BY VENDOR
450 / 750 V
2 Kv
BY VENDOR
BY VENDOR
BY VENDOR
450 / 750 V
2 Kv
BY VENDOR
BY VENDOR
Other Cable Information
Sunlight Resistance
Oil Resistance
Flame Retardant
UL 1581 Section 1200
UL 1581 Section 1200
ICEA S-82-552
IEC 60332-1-2
ICEA S-82-552
IEC 60332-1-2
Fire Retardant (No fire Propagation)
IEC 60332-3-22 Cat. A
IEC 60332-3-22 Cat. A
Fire Resistant
Cable Size (ID) min/Max (mm)
Cable Size OD) min/Max (mm)
Reference STD. Main Applicable Standards
Ex-I Circuit
Cable to be used in Ex-i Circuit
Purchase
MR Number
PO Number
Manufacturer
Supplier
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
IEC 60228-7 Class 2; IEC 60227-3
NO
Not Required
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
64 of 65
ISSUE 0
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Type
Composition
Ref. Norm.
Tube
Secondary Coating
Loose Tube Material
Tubes
Identification
Fire Barrier
Loose
Tight
Wire
Central str. Members
Dielectric GRP Rod
105
TBD
TBD
FO-8
106
TBD
TBD
FO-12
8 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant
12 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant
9/125 µm Single Mode
Single Tube
9/125 µm Single Mode
Single Tube
IEC 60793-2, IEC 60794-1
IEC 60793-2, IEC 60794-1
Yes
Yes
Colours according to ANSI/TIA/EIA 598-A
Colours according to ANSI/TIA/EIA 598-A
MICA/Glass Tape
MICA/Glass Tape
Yes
No
Yes
No
Filling Compound
Yes (inside tube)
Yes (inside tube)
Strength Member
Glass Fiber Reinforced Plastic Rod (FRP)
Glass Fiber Reinforced Plastic Rod (FRP)
Pheripheral str. Member Aramid / Glass
Material
Thickness
Material
Thickness
Material
Thickness
Material
Thickness
Colour
Ref. Norm.
Marking
Inner Sheath
Armour
Intermediate Sheath
Outer Sheath
Core Diameter
Cladding Diameter
Coating Diameter
Attenuation (Typical / Maximum)
Fire Test
Voltage Grade
Reference STD.
Yes
LSZH
Yes
LSZH
Coated Stainless Steel Corrugated Tape
Coated Stainless Steel Corrugated Tape
EN 50288-7
LSZH
Vendor to advice
LSZH
Black
EN 50288-7
LSZH
Vendor to advice
LSZH
Black
EN 50290-2-22
EN 50290-2-22
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
9 µm
125 ± 0.7 µm
245 ± 10 µm
0.32 / 0.4 dB/km
9 µm
125 ± 0.7 µm
245 ± 10 µm
0.32 / 0.4 dB/km
IEC 60331-25 / IEC 60332-3-22
IEC 60331-25 / IEC 60332-3-22
Main Applicable Standards
IEC 60793-2; IEC 60794-1; EN 50288-7
Purchase
MR Number
PO Number
Manufacturer
Supplier
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
18
19
20
21
22
23
24
25
26
27
28
29
30
31
32
33
34
35
36
37
38
39
40
41
42
43
44
45
46
47
48
49
50
Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE
Rev
REALISATION EN EPC
D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-
BENZENE <
TCM IDENTIFICATION CODE 4439-KK-SE-352001001
Sheet
65 of 65
ISSUE 0
Filling Compound
Yes (inside tube)
Yes (inside tube)
Strength Member
Glass Fiber Reinforced Plastic Rod (FRP)
Glass Fiber Reinforced Plastic Rod (FRP)
TCM Commodity Code
MR Ident Code
Client ID Code
Cable Description
TECHNICAL DATA
Type
Composition
Ref. Norm.
Tube
Secondary Coating
Loose Tube Material
Tubes
Identification
Fire Barrier
Loose
Tight
Wire
Central str. Members
Dielectric GRP Rod
Pheripheral str. Member Aramid / Glass
Material
Thickness
Material
Thickness
Material
Thickness
Material
Thickness
Colour
Ref. Norm.
Marking
Inner Sheath
Armour
Intermediate Sheath
Outer Sheath
Core Diameter
Cladding Diameter
Coating Diameter
Attenuation (Typical / Maximum)
Fire Test
Voltage Grade
Reference STD.
107
TBD
TBD
FO-24
108
TBD
TBD
FO-48
24 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant
48 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant
9/125 µm Single Mode
9/125 µm Single Mode
Multitube (4 tubes, 6 fibers each)
Multitube (4 tubes, 12 fibers each)
IEC 60793-2, IEC 60794-1
IEC 60793-2, IEC 60794-1
Yes
Yes
Colours according to ANSI/TIA/EIA 598-A
Colours according to ANSI/TIA/EIA 598-A
MICA/Glass Tape
MICA/Glass Tape
Yes
No
Yes
No
Yes
LSZH
Yes
LSZH
Coated Stainless Steel Corrugated Tape
Coated Stainless Steel Corrugated Tape
EN 50288-7
LSZH
Vendor to advice
LSZH
Black
EN 50288-7
LSZH
Vendor to advice
LSZH
Black
EN 50290-2-22
EN 50290-2-22
See paragraph 8.3 of this specification
See paragraph 8.3 of this specification
9 µm
125 ± 0.7 µm
245 ± 10 µm
0.32 / 0.4 dB/km
9 µm
125 ± 0.7 µm
245 ± 10 µm
0.32 / 0.4 dB/km
IEC 60331-25 / IEC 60332-3-22
IEC 60331-25 / IEC 60332-3-22
Main Applicable Standards
IEC 60793-2; IEC 60794-1; EN 50288-7
Purchase
MR Number
PO Number
Manufacturer
Supplier
BY VENDOR
BY VENDOR
BY VENDOR
BY VENDOR
This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.
Project: Q-32976 - Tecnmont SKIKDA Folder: Reference Documents