Infinity

Not logged in
Home

❯

Reference Examples

❯

Q 32976 Tecnmont SKIKDA

❯

RFQ Files

❯

Reference Documents

❯

4439 KK SE 352001001_0

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-BENZENE <> A SKIKDA ALGERIE

CT-EPC/017/SH/EPM/RPC-X/2023

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

1

of 65

ISSUE 0

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

0 Issue

05.Dec.2024 Date

IFR - Issued for Review Reason for Issue – Revision Description

R. Gunjal Prep’d

N. Metrillo Chk’d

E. Magadeev App’d

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

2 of 65

ISSUE 0

1 2 3 4 5 6

7

8

SCOPE REFERENCE DOCUMENTS ABBREVIATIONS LAWS & REGULATIONS CODES & STANDARDS ENVIRONMENTAL CONDITIONS

6.1 Buildings 6.2 Outdoor

GENERAL REQUIREMENTS

7.1 General

SUPPLY CONDITIONS 8.1 Cable Sizes 8.2 Cable Ends 8.3 Identification and Marking on Cables 8.4 Identification and Marking on Cable Drums 8.5 Identification and Marking on Drums for Fiber Optic Cables

9

TESTING ON INSTRUMENT CABLES

9.1 Test on Construction Characteristics 9.2 Test on Physical Characteristics 9.3 Test on Electrical Characteristics

TESTING ON FIBER OPTIC CABLES

10 11 GENERAL NOTES

Cable Types: Thermocouple K Type Cables

1 2

Single Pair Shielded 1x2x18 AWG Single Pair Shielded 12x2x20 AWG

Identification Code:

F-Kx-A1 F-Kx-A12

Armoured cables for Analogue Signals 4-20mA and Digital signals, FRT Flame Retardant

Single Pair Shielded 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded 2x2x1.5 mm2 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 Multipair, Individual and Overall Shielded 24x2x0.5 mm2 Single Pair Shielded Ex-i Service 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded Ex-i Service 2x2x1.5 mm2

3 4 5 6 7 8 9 10 11 Multipair, Individual and Overall Shielded Ex-i Service 6x2x0.5 mm2 / 8x2x0.5 mm2 F-IS-C6 / F-IS-C8 12 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2F-IS-C12 / F-IS-C16 13 Multipair, Individual and Overall Shielded Ex-i Service 20x2x0.5 mm2 14 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2

F-C1 F-C2 F-C6 / F-C8 F-C12 / F-C16 F-C20 F-C24 F-IS-C1 F-IS-C2

F-IS-C20 F-IS-C24

Armoured cables for Power Supply Output (solenoid, lamp, relay coil etc. 24Vdc), FRT Flame Retardant

Single Pair 1x2x2.5 mm2

15 16 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 17 Multipair 12x2x2.5 mm2 18 Multipair 16x2x2.5 mm2

Armoured Cables for RTD and 3-wire Application, FRT Flame Retardant

Single Triad, Shielded 1x3x1.5 mm2

19 20 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 21 Multi-Triad, Individual and Overall Shielded 12x3x1.5 mm2 / 16x3x1.5 mm2 22 Multi-Triad, Individual and Overall Shielded 24x3x1.5 mm2 23 24 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2

Single Triad, Shielded Ex-i Service 1x3x1.5 mm2

F-D1 F-D6 / F-D8 F-D12 F-D16

F-E1 F-E6 / F-E8 F-E12 / F-E16 F-E24 F-IS-E1 F-IS-E6 / F-IS-E8

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Page 5 5 5 5 6 7 7 7 8 8 9 9 9 9 9 10 10 10 10 10 11 11

12 12

13 13 14 14 15 15 16 16 17 17 18 18

19 19 20 20

21 21 22 22 23 23

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev Cable Types:

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

3 of 65

ISSUE 0

Identification Code:

Page

Armoured Cables for RTD and 3-wire Application, FRT Flame Retardant

25 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 26 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2

F-IS-E12 / F-IS-E16 F-IS-E24

Armoured cables for Analogue Signals 4-20mA and Digital signals, FRS Fire Resistant

Single Pair Shielded 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded 2x2x1.5 mm2

27 28 29 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 30 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 31 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 32 Multipair, Individual and Overall Shielded 24x2x0.5 mm2 33 34 35 Multipair, Individual and Overall Shielded Ex-i Service 6x2x0.5 mm2 / 8x2x0.5 mm2 F-IS-R6 / F-IS-R8 36 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2F-IS-R12 / F-IS-R16 37 Multipair, Individual and Overall Shielded Ex-i Service 20x2x0.5 mm2 38 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2

Single Pair Shielded Ex-i Service 1x2x1.5 mm2 Double Pair, Individual and Overall Shielded Ex-i Service 2x2x1.5 mm2

F-R1 F-R2 F-R6 / F-R8 F-R12 / F-R16 F-R20 F-R24 F-IS-R1 F-IS-R2

F-IS-R20 F-IS-R24

Armoured Cables for RTD and 3-wire Application, FRS Fire Resistant

Single Triad, Shielded 1x3x1.5 mm2

39 40 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 41 Multi-Triad, Individual and Overall Shielded 12x3x1.5 mm2 / 16x3x1.5 mm2 42 Multi-Triad, Individual and Overall Shielded 24x3x1.5 mm2 43 44 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2 45 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 46 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2

Single Triad, Shielded Ex-i Service 1x3x1.5 mm2

F-S1 F-S6 / F-S8 F-S12 / F-S16 F-S24 F-IS-S1 F-IS-S6 / F-IS-S8 F-IS-S12 / F-IS-S16 F-IS-S24

Armoured cables for Power Supply Output (solenoid, lamp, relay coil etc. 24Vdc), FRS Fire Resistant

Single Pair 1x2x2.5 mm2

47 48 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 49 Multipair 12x2x2.5 mm2 50 Multipair 16x2x2.5 mm2

F-T1 F-T6 / F-T8 F-T12 F-T16

Armoured cables for 230Vac Power Supply Output (Instruments External Supply) FRT Flame Retardant

Single Pair 1x2x2.5mm2 + G

51 52 Multipair 6x2x2.5mm2 + G / 8x2x2.5mm2 + G 53 Multipair 12x2x2.5 mm2 + G 54 Multipair 16x2x2.5 mm2 + G

F-U1 F-U6 / F-U8 F-U12 F-U16

Armoured cables for 230Vac Power Supply Output (Instruments External Supply) FRS Fire Resistant

1x2x2.5mm2 + G

55 56 Multicore 6x2x2.5mm2 + G / 8x2x2.5mm2 + G 57 Multipair 12x2x2.5 mm2 + G 58 Multipair 16x2x2.5 mm2 + G

Unarmoured Cables Inside Building - FRT Flame Retardant

F-V1 F-V6 / F-V8 F-V12 F-V16

Single Pair Shielded 1x2x1.5 mm2

Single Pair Shielded Ex-i Service 1x2x1.5 mm2

59 60 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 61 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 62 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 / 24x2x0.5 mm2 63 64 Multipair, Individual and Overall Shielded Ex-i Service 6x2x0.5 mm2 / 8x2x0.5 mm2 B-IS-A6 / B-IS-A8 65 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2B-IS-A12 / B-IS-A16 66 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2 67 68 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 69 Multipair 12x2x2.5 mm2 70 Multipair 16x2x2.5 mm2

B-A1 B-A6 / B-A8 B-A12 / B-A16 B-A20 / B-A24 B-IS-A1

B-IS-A24 B-B1 B-B6 / B-B8 B-B12 B-B16

Single Pair 1x2x2.5 mm2

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

24 24

25 25 26 26 27 27 28 28 29 29 30 30

31 31 32 32 33 33 34 34

35 35 36 36

37 37 38 38

39 39 40 40

41 41 42 42 43 43 44 44 45 45 46 46

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev Cable Types:

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

4 of 65

ISSUE 0

Identification Code:

Page

Unarmoured Cables Inside Building - FRT Flame Retardant

Single Triad, Shielded 1x3x1.5 mm2

Single Triad, Shielded Ex-i Service 1x3x1.5 mm2

71 72 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 73 74 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2 75 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 76 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2

Unarmoured Cables Inside Building - FRT Flame Retardant

Single Pair 1x2x2.5 mm2 + G

77 78 Multipair 6x2x2.5mm2 + G / 8x2x2.5mm2 + G

Unarmoured Cables Inside Building - FRS Fire Resistant

B-C1 B-C6 / B-C8 B-IS-C1 B-IS-C6 / B-IS-C8 B-IS-C12 / B-IS-C16 B-IS-C24

B-D1 B-D6 / B-D8

Single Pair 1x2x2.5 mm2

Single Pair Shielded 1x2x1.5 mm2

Single Pair Shielded Ex-i Service 1x2x1.5 mm2

B-R1 B-R6 / B-R8 B-R12 / B-R16 B-R20 / B-R24 B-IS-R1 B-IS-R8

79 80 Multipair, Individual and Overall Shielded 6x2x0.5 mm2 / 8x2x0.5 mm2 81 Multipair, Individual and Overall Shielded 12x2x0.5 mm2 / 16x2x0.5 mm2 82 Multipair, Individual and Overall Shielded 20x2x0.5 mm2 / 24x2x0.5 mm2 83 84 Multipair, Individual and Overall Shielded Ex-i Service 8x2x0.5 mm2 85 Multipair, Individual and Overall Shielded Ex-i Service 12x2x0.5 mm2 / 16x2x0.5 mm2B-IS-R12 / B-IS-R16 86 Multipair, Individual and Overall Shielded Ex-i Service 24x2x0.5 mm2 87 88 Multipair 6x2x2.5mm2 / 8x2x2.5mm2 89 Multipair 12x2x2.5 mm2 90 Multipair 16x2x2.5 mm2 91 92 Multi-Triad, Individual and Overall Shielded 6x3x1.5 mm2 / 8x3x1.5 mm2 93 Multi-Triad, Individual and Overall Shielded 12x3x1.5 mm2 / 16x3x1.5 mm2 94 Multi-Triad, Individual and Overall Shielded 24x3x1.5 mm2 95 96 Multi-Triad, Individual and Overall Shielded Ex-i 6x3x1.5 mm2 / 8x3x1.5 mm2 97 Multi-Triad, Individual and Overall Shielded Ex-i 12x3x1.5 mm2 / 16x3x1.5 mm2 98 Multi-Triad, Individual and Overall Shielded Ex-i 24x3x1.5 mm2 99 100 Multipair 6x2x2.5mm2 + G / 8x2x2.5mm2 + G

B-IS-R24 B-G1 B-G6 / B-G8 B-G12 B-G16 B-H1 B-H6 / B-H8 B-H12 / B-H16 B-H24 B-IS-H1 B-IS-H6 / B-IS-H8 B-IS-H12 / B-IS-H16 B-IS-H24 B-K1 B-K6 / B-K8

Single Triad, Shielded Ex-i Service 1x3x1.5 mm2

Single Triad, Shielded 1x3x1.5 mm2

Single Pair 1x2x2.5 mm2 + G

Earthing Cables

101 Earthing Cable 01C x 6 mm2 102 Earthing Cable 01C x 10 mm2 103 Earthing Cable 01C x 16 mm2 104 Earthing Cable 01C x 25 mm2

Armoured Fibre Optic Cables - Fire Resistant

105 106 107 108

8 Fibers, Single Mode 12 Fibers, Single Mode 24 Fibers, Single Mode 48 Fibers, Single Mode

E-06 E-10 E-16 E-25

FO-8 FO-12 FO-24 FO-48

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

47 47 48 48 49 49

50 50

51 51 52 52 53 53 54 54 55 55 56 56 57 57 58 58 59 59 60 60 61 61

62 62 63 63

64 64 65 65

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

5 of 65

ISSUE 0

1

SCOPE This document establishes the instrument general specification for the execution of the EPC phase of the project “REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-BENZENE<>”.

The guidelines reported in the present specification shall apply to the new LAB complex. Installation in the existing complex (i.e RA1K, etc.) shall follow the existing complex rules. All equipment, material and systems shall in all respect be suitable for reliable operation in service conditions stated in the Basic Engineering Design Data (BEDD, doc. № 4439-YZ-SG-000000001)

2

REFERENCE DOCUMENTS

4439-KK-SG-000000001

INSTRUMENT GENERAL SPECIFICATION

3

ABBREVIATIONS AND DEFINITIONS

Abbreviation

Description

CCTV

HSE

DCS

ESD

FGS

FOBB

MMS

MCR

MCB

RIB

TGS

Security closed circuit television

Health Safety Environment

Distributed Control System

Emergency Shut Down

Fire and Gas Detection System

Fiber Optic Back Bone

Machine Monitoring System

Main Control Room

Main Control Building

Remote Instrument Building

Tank Gauging System

CA / COMPANY / Maitre de l’Ouvrage

SONATRACH DC-EPM

CONTRACTOR / Entrepreneur

TECNIMONT SPA

PROJECT

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL-BENZENE <> A SKIKDA ALGERIE

4

LAWS & REGULATIONS

In general, the new LAB complex facilities will be designed in accordance with internationally recognized codes and standards.

The complete list of codes, standards and norms applicable to the EPC phase of LAB project and the associated utilities are listed in INDEX OF PROJECT REGULATIONS, CODES AND APPLICABLE STANDARDS 4439-YZ-PC-000000018.

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

6 of 65

ISSUE 0

Rev

5

CODES & STANDARDS

Document Number

BS-EN-60584-1/BS-EN-60584-3

ANSI/TIA/EIA 598-A

BS-EN-61073

BS-EN-60874

BS-EN-61274

EN 50288-7

EN 50290-2-22

EN 50290-2-29

Document Title Thermocouples - Part 1: EMF specifications and tolerances Thermocouples - Part 3: Extension and compensating cables - Tolerances and identification system Optical Fibre Cable Color Coding

Mechanical splicers and fusion splice protectors for optical fibres and cables

Connectors for Optical Fibres and Cables

Fibre Optic Adaptors

Multi-element metallic cables used in analogue and digital communication and control. Sectional specification for instrumentation and control cables.

Communication cables. Common design rules and construction. PVC sheathing compounds

Communication cables. Common design rules and construction. Cross-linked PE insulation compounds

ICEA S-82 552 (NEMA WC 55)

Instrumentation Cables and Thermocouple Wire – Oil resistance test

IEC 60228

Conductors of insulated cables

IEC 60331-11

IEC 60331-21

IEC 60331-25

IEC 60332-1-2

IEC 60332-3-22

IEC 60793-2-10

IEC 60793-2-50

IEC 60794-1-1

IEC 60794-1-2

IEC 60794-2

IEC 60794-3

IEC 61300

IEC 61515

IEC 61931

Tests for electric cables under fire conditions - circuit integrity – part 11: apparatus - fire alone at a flame temperature of at least 750 degrees C

Tests for electric cables under fire conditions - circuit integrity – procedures and requirements – cables of rated voltage up to and including 0.6/1.0 kV.

Tests for electric cables under fire conditions - Circuit Integrity Part 25: Procedures and requirements - Optical fibre cables

Tests on electric and optical fiber cables under fire conditions – Part 1-2: Test for vertical flame propagation for a single insulated wire or cable - Procedure for 1 kW pre-mixed flame

Tests on electric and optical fiber cables under fire conditions - part 3- 22: test for vertical flame spread of vertically-mounted bunched wires or cables - category A

Optical fibres - Part 2-10: Product specifications - Sectional specification for category A1 multimode fibres

Optical fibres - Part 2-50: Product Specifications - Sectional specification for class B single-mode fibres

Optical Fibre cables – Part 1-1: Generic specification – General

Optical Fibre cables – Part 1-2: Generic specification – Cross reference table for optical cable test procedures

Optical fibre cables - Part 2: Indoor cables - Sectional specification

Optical fibre cables - Part 3: Sectional specification - Outdoor cables

Fibre Optic interconnecting devices and passive components Basic test and measurement procedures

Mineral insulated thermocouple cables and thermocouples

Fibre Optic – Terminology

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

7 of 65

ISSUE 0

Document Number

Document Title

ITU-T G-651.X

Characteristics of a 50/125 µm multimode graded index optical fibre cable for the optical access network.

ITU-T G-652

Characteristic of a Single Mode Optical Fibre and Cable (ITU-T Recommendation).

ITU-T G-653

ITU-T G-654

ITU-T G-655

ITU-T G-656

UL 1581

Characteristics of a dispersion-shifted, single-mode optical fibre and cable (ITU-T Recommendation).

Characteristics of a cut-off shifted single-mode optical fibre and cable (ITU-T Recommendation).

Characteristics of a NON-ZERO dispersion-shifted, single-mode optical fibre and cable (ITU-T Recommendation).

Characteristics of a fibre and cable with non-zero dispersion for wideband optical transport (ITU-T Recommendation).

Reference Standard for Electrical Wires, Cables, and Flexible Cords – Sunlight resistance section 1200.

Vendor’s compliance with other than the above-mentioned Standards of Codes shall be declared for Owner’s approval.

6

ENVIRONMENTAL CONDITIONS

6.1 Buildings

Main control building and generally all indoor areas and rooms, where Cables will be installed, will be air conditioned. The air conditioning will be designed to guarantee the following indoor conditions:

Environmental Conditions

Temperature

Relative Humidity

Max temperature indoor min temperature indoor

25 °C 18 °C

50% ± 10 50% ± 10

a.

b.

c.

Design temperature for electrical equipment installed indoors shall be 1°C ÷ 47°C.

Vendor is required to provide details of the maximum/minimum temperature and relative humidity limits, within which Vendor can guarantee system performance, in the power on condition, during prolonged failure of the HVAC system.

Vendor shall state the maximum working temperature of all equipment supplied.

6.2 Outdoor

The most severe climatic data are defined below and shall be used to define the common design basis for the LAB complex in the existing industrial zone of Skikda. Refer to document ‘’BASIC ENGINEERING DESIGN DATA’’ № 4439-YZ-SG-000000001.

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

8 of 65

ISSUE 0

Environmental Conditions

Temperature:

Highest maximum on record

Lowest temperature - Minimum Design Metal Temperature

Max Design Temperature for Instrumentation (Outdoor)

Relative Humidity:

Annual average mean

Average min (%)

Average Max (%)

Design value for air fans, compressores and gas turbines (%)

Value

Notes

1

2

3, 4, 5

47 °C

1 °C

50 °C

72

69 (July)

79 (March)

72

Notes:

  1. This is the maximum shade air temperature that the equipment and systems must be physically designed for. Equipment must also be able to operate continuously at this temperature.

  2. This is the minimum shade air temperature that the equipment and systems must be designed for. Equipment must also be able to operate continuously at this temperature.

  3. Electrical/electronic equipment located outdoors shall be rated for an ambient temperature of 50°C. Electrical equipment (i.e. panels, etc.) to be located indoors and all cables shall be rated for continuous operation in an ambient temperature of 40°C.

  4. Electrical/electronic equipment and cables shall be located away from direct sunlight wherever possible. Equipment located outside shall be provided with sunshades or shields to protect the equipment from solar heat gain.

  5. All electronic devices in direct sunlight should be designed to withstand and operate with a surface temperature of 85°C. If this is not possible the Supplier shall design adequate sun shading and inform Owner’s Engineer of requirements.

7

GENERAL REQUIREMENTS

7.1 General

a) This Job Specification covers the following cables:

  • Thermocouple extension cables (millivolts)

  • Cables for analogue signals (continuous) - typically 4-20 mA and digital inputs

  • Cables for digital output signals (24Vdc)

  • Cables for instruments power supply (24Vdc)

  • Cables for instruments power supply (230Vac)

  • Cables for RTD signals and three wires application

  • Cables for Motor-operated valves (Control command only)

  • Fire Resistance Cables, for F&G detectors & F&G (Horn & Flashing light)

  • Cables for indoor analogue, digital and RTD signals

  • Fiber Optic Cables.

b)

c)

Field cables as above specified with the following details: Single and Multi-pair/Triple/Multi-wire shall be suitable for installation aboveground in cable tray, underground in cable ducts or direct buried with a suitable armouring. Detailed characteristics for each type of cable are listed in the dedicated cable type pages of this document.

Indoor cables as above specified with the following details: Single and Multi-pair/Triple/Multi-wire shall be suitable for installation aboveground or under false floor cable trays, without any armouring. Low smoke zero halogen cables to be used. Detailed characteristics for each type of cable are listed in the dedicated cable type pages of this document.

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

9 of 65

ISSUE 0

d)

Fire Resistance Cables as above specified with the following details: Fire-rated cable (without any fireproofing) shall be used when fire-resistance is required for aboveground wiring. Fire-rated cables shall be suitable for operability for at least 90 minutes when exposed to fire at 750°C as per IEC 60331 section 11.

8

SUPPLY CONDITIONS

8.1 Cable Sizes

Unless otherwise stated or agreed, cables shall be supplied in lengths provided in individual specification issued for order. Quantities of cable lengths (Bill of Material) to be supplied by Vendor shall be as specified. Cable type wise in Material Requisition 4439-KK-MR-352001. Vendor shall indicate in proposal, against each type of cable, minimum & maximum cable length possible in a single cable drum.

8.2 Cable Ends

The ends of each cable shall be protected by a suitable waterproof female compression plug fastened with adhesive tape, or with heat shrinkable sheath or hygroscopic plastic seal.

8.3

Identification and Marking on Cables In addition to the information required by the specified standard, the following information shall be printed at every 1 meter (maximum) on the external outer sheath of entire cable : Markings shall be able to withstand commercial/industrial cleaning agents, and the environmental conditions for which the cable is manufactured.

  • Cable Type (TCM Commodity Code)

  • Number of Pairs / Triads / Cores

  • Part Number

  • Insulation Type

  • Conductor Size and Number of Conductors

  • Temperature Range

  • Rated Voltage

  • Cable Construction

  • Construction Year

  • Applicable STD

  • Manufacturer’s Name

  • The Metrical Progressive Numeration

  • Fire Behavior when affected by fire

The Pair, Triads and Core numbers shall be printed on the wires at least every 50mm interval.

Example of Marking :

BKI032SE01P_1_____PP 1 Pair x 1 mm² 300/300V Cu/XLPE/LS0H 2019 Manufacturer name

  • Progressive length of cable at every meter

8.4

Identification and Marking on Cable Drums Cable drum should have identification plates (one on both sides of the drum), the identification plates should be white (300mm x 150mm) with black lettering weather resistant, the identification plate shall provide following:

  • Client - Location - Project

  • Cable voltage rating

  • Cable identification as per TCM commodity code

  • Total weight of cable and drum (kg)

  • PO ref. number and MR number

  • Cable type and size.

  • Drum cable length

  • Drum number (Drum number will be intimated by contractor after P.O.),

  • Construction year, total mass & tare

  • Manufacturers name

  • Minimum bending radius for installation

  • Maximum pulling tension

Vendor shall provide maximum length of each cable type in a cable drum. After Purchase order, Contractor will intimate drum wise required quantity to Vendor. Cable length tolerance on each drum: -0 % to +3 %.

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

10 of 65

ISSUE 0

8.5

Identification and Marking on Drums for Fiber Optic Cables The identification plate shall contain the following information for Fiber Optic Cables:

  • CLIENT – Location – PROJECT

  • Material Requisition Number

  • Manufacturer name and year of construction

  • Cable Type and Size (for instance: 12 cores 62.5/125 µm)

  • Fire behavior when affected by fire: (for instance: IEC 60332-3)

  • Reel Number (given to Vendor before starting with coil construction)

  • Reel length and gross weight

9

TESTING ON INSTRUMENT CABLES

Vendor will provide test certification of each cable in accordance with the requirements of applicable international, national codes and practices.

Factory test according to BS-EN 50288 (for cables 300/500V) or IEC 60502-1 (for cables 0.6/1kV up to 3kV) on all supplied cables shall be executed.

Type tests will be according to the relevant Inspection Test Plan Document attached in the Supply Specification 4439-KK-SS-352001.

Vendor shall provide a cable test certificate for each manufactured type of cable.

9.1

Test on Construction Characteristics

Following tests shall be performed:

  • Cable formation

  • Conductor configuration & diameters of conductor wire

  • Thickness of primary insulation,

  • Construction and thickness of electrostatic shields and configuration & diameter of drain wires

  • Thickness of outer sheath

  • Execution/thickness of Armour

  • Cable outside diameter

  • Cable length tolerances : -0% to +3%

9.2

Test on Physical Characteristics

Following tests shall be performed:

  • Testing of Mechanical properties (Tensile stress, Elongation at break) of primary insulation and the outer sheath

with and without ageing / Thermal ageing shall be carried out according to the EN 50288-7.

  • Test of thermoplastic properties of primary insulation & outer sheath shall be carried out

according to the EN 50288-7.

  • Circuit Integrity Fire Test as per IEC 60331-21

  • Bending Test as per IEC 60794-1-2E6

  • Oxygen index shall be carried out as per IEC 60811 & IEC 60502-1 (As far as applicable).

9.3

Test on Electrical Characteristics

Following tests shall be performed:

  • Continuity test

  • Voltage test

  • Measurement of Electrical resistance of conductor

  • Measurement of Electrical resistance of drain wire

  • Measurement of Inductance and capacitance values between the conductors

  • Measurement of Insulation resistance shall be in accordance with the respective Standards.

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

11 of 65

ISSUE 0

10

TESTING ON FIBER OPTIC CABLES Vendor will provide test certification of each cable in accordance with the requirements of applicable international, national codes and practices.

Type tests will be according to the relevant Inspection Test Plan Document attached in the Supply Specification 4439-KK-SS-352001.

Vendor shall provide a cable test certificate for each manufactured type of cable.

The tests shall include for each testing length, optical time domain reflectometry measurement (OTDR) and attenuation coefficient. For runs over 100 meters the test shall be made at both ends and the two measurements compared. Differences greater than could be caused from instrument resolution shall be investigated and resolved. Attenuation coefficient shall be measured to ensure compliance with the design specification. The measurement shall be summarized in a graphic (Back Scattering Diagram) which shall also be used for localized losses detection during installation. In particular the tests carried out by the Supplier shall be the following:

  • Attenuation measurements for each fibre in dB/km (average and maximum) in all the cable lengths of the supplied lot.
  • Back scattering diagram.
  • General inspection on construction conformance.
  • Certified test-reports for all deliverables.
  • Test and certification of bandwidth and attenuation, continuity on drums attenuation on drums.

Moreover, for each fibre:

  • Attenuation coefficient and chromatic dispersion wavelengths for 1310 nm and 1550 nm (single-mode fibre only)
  • Zero dispersion wave length
  • Zero dispersion slope

The tests to be performed by the Manufacturer shall demonstrate that the cable has been provided and constructed in accordance with the specifications and applicable standards.

11 GENERAL NOTES

Pair Identification:

  1. Single pair conductor shall have polarity sign (+) or (-) stamped.

  2. In multipair cable each pair shall be numbered (on each conductor). On all conductor polarity sign (+) or (-) shall be stamped.

  3. Numbering and polarity shall be made at regular distances of 100 mm with contrasting color (i.e. Number white for black wire).

Inner Sheath Thickness

  1. Minimum 1 mm for cable diameter under armour up to 25mm. 1,2 mm for cable over 25 mm (under armour).

Outer Sheath Thickness

  1. Minimum 1,4 mm for cable diameter under outer sheath up to 20 mm. Min. 2 mm for cable from 20 to 25 mm (under sheath), and min. 2,5 mm up to 3 mm for higher dimensions.

  2. Thickness should be determined following the formula T = 0,04 x D 1,1 (min 1,3 mm), where “D” is the diameter under outer sheath.

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

12 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

1

TBD

TBD

F-Kx-A1

2

TBD

TBD

F-Kx-A12

1x2x16 AWG Kx Type Armoured Thermocouple Cable

12x2x20 AWG Kx Type Armoured Thermocouple Multicable

BS-EN-60584

Thermocouple type Kx

Yellow (+) / Red (-)

16 AWG

EN 50290-2-29

XLPE - Resistance 90°C

Yellow / Red

EN 50288-7 Table 1

N/A

Not Required

≥ 20 times/m

BS-EN-60584

Thermocouple type Kx

Yellow (+) / Red (-)

20 AWG

EN 50290-2-29

XLPE - Resistance 90°C

Yellow / Red

EN 50288-7 Table 1

Max lay of Length up to 1,5 mm2 ≤ 100mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

Not Required

Not Required

Not Required

Not required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Yellow

Steel wire armour

PVC-TI3 (90°)

Yellow

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Yellow

Steel wire armour

PVC-TI3 (90°)

Yellow

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; BS-EN-60584

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

13 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

3

TBD

TBD

F-C1

4

TBD

TBD

F-C2

1x2x1.5mm2 Single Pair Armoured Cable for Analogue and Digital Signals - Flame Retardant

2x2x1.5mm2 Double Pair Armoured Cable for Analogue and Digital Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

14 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

5

TBD

TBD

6

TBD

TBD

F-C6 / F-C8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant

F-C12 / F-C16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

15 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

7

TBD

TBD

F-C20

8

TBD

TBD

F-C24

20x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant

24x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

16 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

9

TBD

TBD

F-IS-C1

10

TBD

TBD

F-IS-C2

1x2x1.5mm2 Single Pair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant

2x2x1.5mm2 Double Pair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

Yes

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

17 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

11

TBD

TBD

12

TBD

TBD

F-IS-C6 / F-IS-C8 6x2x0.5mm2 / 8x2x0.5mm2 Single Pair I.S. Armoured Cable forAnalogue and Digital Signals - Flame Retardant

F-IS-C12 / F-IS-C16 12x2x0.5mm2 / 16x2x0.5mm2 Multpair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

Yes

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

18 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

13

TBD

TBD

F-IS-C20

14

TBD

TBD

F-IS-C24

20x2x0.5mm2 Multpair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant

24x2x0.5mm2 Multpair I.S. Armoured Cable for Analogue and Digital Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

Yes

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

19 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

15

TBD

TBD

F-D1

1x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant

16

TBD

TBD

F-D6 / F-D8 6x2x2.5mm2 / 8x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

Red / Black

EN 50228-7 Table 1

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

20 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

17

TBD

TBD

F-D12

18

TBD

TBD

F-D16

12x2x2.5 mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant

16x2x2.5 mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black

EN 50228-7 Table 1

Red / Black

EN 50228-7 Table 1

Max length of lay up to 2.5 mm2 ≤ 150 mm

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

21 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

19

TBD

TBD

F-E1

1x3x1.5 mm2 Single Triad Armoured Cable for RTD and 3 wire devices - Flame Retardant

20

TBD

TBD

F-E6 / F-E8 6x3x1.5 mm2 / 8x3x1.5 mm2 Multitrad Armoured Cable for RTD and 3 wire devices - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

22 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

21

TBD

TBD

F-E12 / F-E16 12x3x1.5mm2 / 16x3x1.5mm2 Multitrad Armoured Cable for RTD and 3 wire devices - Flame Retardant

22

TBD

TBD

F-E24

24x3x1.5 mm2 Multitrad Armoured Cable for RTD and 3 wire devices - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

23 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

23

TBD

TBD

F-IS-E1

1x3x1.5mm2 Single Triad Armoured I.S Cable for RTD and 3 wire devices - Flame Retardant

24

TBD

TBD

F-IS-E6 / F-IS-E8 6x3x1.5mm2 / 8x3x1.5mm2 Multitrad Armoured I.S. Cable for RTD and 3 wire devices - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

24 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

25

TBD

TBD

F-IS-E12 / F-IS-E16 12x3x1.5mm2 / 16x3x1.5mm2 Multitrad Armoured I.S. Cable for RTD and 3 wire devices - Flame Retardant

26

TBD

TBD

F-IS-E24

24x3x1.5 mm2 Multitrad Armoured I.S. Cable for RTD and 3 wire devices - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

Not Required

EN 50290-2-22

PVC-TI3 (90°)

Light Blue

Steel wire armour

PVC-TI3 (90°)

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

25

of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

27

TBD

TBD

F-R1

28

TBD

TBD

F-R2

1x2x1.5 mm2 Single Pair Armoured Cable for Analogue and Digital Signals - Fire Resistant

2x2x1.5 mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red

Not Required

EN 50290-2-22

SHF 2

Red

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

SHF 1

Red

SHF 1

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

26

of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

29

TBD

TBD

30

TBD

TBD

F-R6 / F-R8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Armoured Cable forAnalogue and Digital Signals - Fire Resistant

F-R12 / F-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red

Not Required

EN 50290-2-22

SHF 2

Red

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

SHF 1

Red

SHF 1

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

27

of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

31

TBD

TBD

F-R20

32

TBD

TBD

F-R24

20x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant

24x2x0.5mm2 Multipair Armoured Cable for Analogue and Digital Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red

Not Required

EN 50290-2-22

SHF 2

Red

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

SHF 1

Red

SHF 1

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

28 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

33

TBD

TBD

F-IS-R1

34

TBD

TBD

F-IS-R2

1x2x1.5mm2 Single Pair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant

2x2x1.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

29 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

35

TBD

TBD

36

TBD

TBD

F-IS-R6 / F-IS-R8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant

F-IS-R12 / F-IS-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

30 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

37

TBD

TBD

F-IS-R20

38

TBD

TBD

F-IS-R24

20x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant

24x2x0.5mm2 Multipair Armoured I.S. Cable for Analogue and Digital Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

31 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

39

TBD

TBD

F-S1

40

TBD

TBD

F-S6 / F-S8

1x3x1.5mm2 Single Triad Armoured Cable for RTD and 3 wire devices - Fire Resistant

6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Armoured Cable for RTD and 3 wire devices - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red

Not Required

EN 50290-2-22

SHF 2

Red

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

SHF 1

Red

SHF 1

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

32 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

41

TBD

TBD

F-S12 / F-S16

42

TBD

TBD

F-S24

12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Armoured Cable for RTD and 3 wire devices - Fire Resistant

24x3x1.5mm2 Multitriad Armoured Cable for RTD and 3 wire devices - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red

Not Required

EN 50290-2-22

SHF 2

Red

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

SHF 1

Red

SHF 1

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

33 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

43

TBD

TBD

F-IS-S1

1x3x1.5mm2 Single Triad Armoured Cable for RTD and 3 wire devices - Fire Resistant

44

TBD

TBD

F-IS-S6 / F-IS-S8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Armoured I.S. Cable for RTD and 3 wire devices - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

34 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

45

TBD

TBD

F-IS-S12 / F-IS-S16 12x3x1.5 mm2 / 16x3x1.5 mm2 Multitriad Armoured I.S. Cable for RTD and 3 wire devices - Fire Resistant

46

TBD

TBD

F-IS-S24

24x3x1.5 mm2 Multitriad Armoured I.S. Cable for RTD and 3 wire devices - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Not Required

EN 50290-2-22

SHF 2

Red with Light Blue Stripe

Tinned Copper Wire Braid

SHF 1

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

35 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

47

TBD

TBD

F-T1

1x2x2.5 mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant

48

TBD

TBD

F-T6 / F-T8 6x2x2.5mm2 / 8x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

Red / Black

EN 50228-7 Table 1

Red / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

SHF 2

Red

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

SHF 2

Red

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

SHF 1

Red

SHF 1

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

36 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

49

TBD

TBD

F-T12

50

TBD

TBD

F-T16

12x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant

16x2x2.5mm2 Armoured Cable for DO Signals and 24V Powered Instruments - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

MICA tape + EP Rubber

MICA tape + EP Rubber

Red / Black

EN 50228-7 Table 1

Red / Black

EN 50228-7 Table 1

Max length of lay up to 2.5 mm2 ≤ 150 mm

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

SHF 2

Red

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

SHF 2

Red

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

SHF 1

Red

SHF 1

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

37 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

51

TBD

TBD

F-U1

1x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant

52

TBD

TBD

F-U6 / F-U8 6x2x2.5mm2 + Ground / 8x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

2.5 mm2 + G 2.5mm2

EN 50290-2-29

XLPE - Resistance 90°C

2.5 mm2 + G 2.5mm2

EN 50290-2-29

XLPE - Resistance 90°C

Brown / Light Blue / Yellow/Green

Brown / Light Blue / Yellow/Green

IEC 60502

N/A

Not Required

≥ 20 times/m

IEC 60502

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

Not Required

IEC 60502: EN 50290-2-22

IEC 60502: EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

IEC 60502; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

38 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

53

TBD

TBD

F-U12

54

TBD

TBD

F-U16

12x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant

16x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

2.5 mm2 + G 2.5mm2

EN 50290-2-29

XLPE - Resistance 90°C

2.5 mm2 + G 2.5mm2

EN 50290-2-29

XLPE - Resistance 90°C

Brown / Light Blue / Yellow/Green

Brown / Light Blue / Yellow/Green

IEC 60502

IEC 60502

Max length of lay up to 2.5 mm2 ≤ 150 mm

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

Not Required

IEC 60502: EN 50290-2-22

IEC 60502: EN 50290-2-22

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

PVC-TI3 (90°)

Black

Steel wire armour

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

39 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

55

TBD

TBD

F-V1

1x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant

56

TBD

TBD

F-V6 / F-V8 6x2x2.5 mm2 + Ground / 8x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

2.5 mm2 + G 2.5mm2

EN 50290-2-29

MICA tape + EP Rubber

2.5 mm2 + G 2.5mm2

EN 50290-2-29

MICA tape + EP Rubber

Brown / Light Blue / Yellow/Green

Brown / Light Blue / Yellow/Green

IEC 60502

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

IEC 60502

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Not Required

Not Required

IEC 60502: EN 50290-2-22

IEC 60502: EN 50290-2-22

PVC-TI3 (90°)

Black

PVC-TI3 (90°)

Black

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

PVC-TI3 (90°)

Black

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

IEC 60502; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

40 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

57

TBD

TBD

F-V12

58

TBD

TBD

F-V16

12x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant

16x2x2.5mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

2.5 mm2 + G 2.5mm2

EN 50290-2-29

MICA tape + EP Rubber

2.5 mm2 + G 2.5mm2

EN 50290-2-29

MICA tape + EP Rubber

Brown / Light Blue / Yellow/Green

Brown / Light Blue / Yellow/Green

IEC 60502

IEC 60502

Max length of lay up to 2.5 mm2 ≤ 150 mm

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Not Required

Not Required

IEC 60502: EN 50290-2-22

IEC 60502: EN 50290-2-22

PVC-TI3 (90°)

Black

PVC-TI3 (90°)

Black

Sheaths

Armour

Tinned Copper Wire Braid

Tinned Copper Wire Braid

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

PVC-TI3 (90°)

Black

PVC-TI3 (90°)

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

41 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

59

TBD

TBD

60

TBD

TBD

B-A1 1x2x1.5mm2 Single Pair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant

B-A6 / B-A8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Black

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

42 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

61

TBD

TBD

62

TBD

TBD

B-A12 / B-A16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant

B-20 / B-24 20x2x0.5mm2 / 24x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Black

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

43 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

63

TBD

TBD

64

TBD

TBD

B-IS-A1 1x2x1.5 mm2 Single Pair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Flame Retardant

B-IS-A6 / B-IS-A8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Unarmoured I.S. Cable forAnalogue, Digital and Interconnecting Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Light Blue

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

44 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

65

TBD

TBD

66

TBD

TBD

B-IS-A12 / B-IS-A16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured I.S. Cable forAnalogue, Digital and Interconnecting Signals - Flame Retardant

B-IS-A24 24x2x0.5mm2 Multipair Unarmoured I.S. Cable forAnalogue, Digital and Interconnecting Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Light Blue

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

45 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

67

TBD

TBD

68

TBD

TBD

B-B1 1x2x2.5 mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant

B-B6 / B-B8 6x2x2.5mm2 / 8x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

Red / Black

EN 50228-7 Table 1

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Black

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

46 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

69

TBD

TBD

70

TBD

TBD

B-B12 12x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant

B-B16 16x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black

EN 50228-7 Table 1

Red / Black

EN 50228-7 Table 1

Max length of lay up to 2.5 mm2 ≤ 150 mm

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Black

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

47 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

71

TBD

TBD

72

TBD

TBD

B-C1 1x3x1.5mm2 Single Triad Unarmoured Cable for RTD, 3 wire devices and Interconnecting SIgnals - Flame Retardant

B-C6 / B-C8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Black

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

48 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

73

TBD

TBD

74

TBD

TBD

B-IS-C1 1x3x1.5 mm2 Single Triad Unarmoured I.S. Cable for RTD, 3 wire devices and Interconnecting SIgnals

  • Flame Retardant

B-IS-C6 / B-IS-C8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Light Blue

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

49 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

75

TBD

TBD

76

TBD

TBD

B-C12 / B-C16 12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant

B-C24 24x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

XLPE - Resistance 90°C

XLPE - Resistance 90°C

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Required

Required

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Light Blue

Light Blue

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

50 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

77

TBD

TBD

B-D1

1x2x2.5 mm2 + Ground Unarmoured Cable for AC Power Supplied Instruments - Flame Retardant

78

TBD

TBD

B-D6 / B-D8 6x2x2.5mm2 + Ground / 8x2x2.5mm2 + Ground Unarmoured Cable for AC Power Supplied Instruments - Flame Retardant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

2.5 mm2 + G 2.5mm2

EN 50290-2-29

XLPE - Resistance 90°C

2.5 mm2 + G 2.5mm2

EN 50290-2-29

XLPE - Resistance 90°C

Brown / Light Blue / Yellow/Green

Brown / Light Blue / Yellow/Green

IEC 60502

N/A

Not Required

≥ 20 times/m

IEC 60502

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

Wrapping of non-hygroscopic tape

Wrapping of non-hygroscopic tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

Not Required

IEC 60502: EN 50290-2-22

IEC 60502: EN 50290-2-22

N/A

N/A

N/A

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Black

Black

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

IEC 60502; IEC 60228

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

51 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

79

TBD

TBD

80

TBD

TBD

B-R1 1x2x1.5 mm2 Single Pair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

B-R6 / B-R8 6x2x0.5mm2 / 8x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

52 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

81

TBD

TBD

82

TBD

TBD

B-R12 / B-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

B-R20 / B-R24 20x2x0.5mm2 / 24x2x0.5mm2 Multipair Unarmoured Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

53 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

83

TBD

TBD

84

TBD

TBD

B-IS-R1 1x2x1.5 mm2 Single Pair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

B-IS-R8 8x2x0.5 mm2 Multipair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

1.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

54 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

85

TBD

TBD

86

TBD

TBD

B-IS-R12 / B-IS-R16 12x2x0.5mm2 / 16x2x0.5mm2 Multipair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

B-IS-R24 24x2x0.5 mm2 Multipair Unarmoured I.S. Cable for Analogue, Digital and Interconnecting Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

White (+) / Black (-)

0.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

White / Black

EN 50228-7 Table 1

White / Black

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

55 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

87

TBD

TBD

88

TBD

TBD

B-G1 1x2x2.5 mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant

B-G6 / B-G8 6x2x2.5mm2 / 8x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

Red / Black

EN 50228-7 Table 1

Red / Black

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

56 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

89

TBD

TBD

90

TBD

TBD

B-G12 12x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant

B-G16 16x2x2.5mm2 Unarmoured Cable for DO Signals and 24V Powered Instruments and Interconnecting Signals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

Red (+) / Black (-)

2.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

Red / Black

EN 50228-7 Table 1

Red / Black

EN 50228-7 Table 1

Max length of lay up to 2.5 mm2 ≤ 150 mm

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

57 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

91

TBD

TBD

92

TBD

TBD

B-H1 1x3x1.5 mm2 Single Triad Unarmoured Cable for RTD, 3 wire devices and Interconnecting SIgnals - Fire Resistant

B-H6 / B-H8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

58 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

93

TBD

TBD

94

TBD

TBD

B-H12 / B-H16 12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant

B-H24 24x3x1.5mm2 Multitriad Unarmoured Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

59 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

95

TBD

TBD

96

TBD

TBD

B-IS-H1 1x3x1.5mm2 Single Triad Unarmoured I.S. Cable for RTD, 3 wire devices and Interconnecting SIgnals

  • Fire Resistant

B-IS-H6 / B-IS-H8 6x3x1.5mm2 / 8x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Required

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

60 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

97

TBD

TBD

98

TBD

TBD

B-IS-H12 / B-IS-H16 12x3x1.5mm2 / 16x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant

B-IS-H24 24x3x1.5mm2 Multitriad Unarmoured I.S. Cable for RTD and 3 wire devices and Interconnecting SIgnals - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Red (24Vdc) / Black (-) / White (COM)

Red (24Vdc) / Black (-) / White (COM)

1.5 mm2

EN 50290-2-29

1.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

Red / Black / White

EN 50228-7 Table 1

Red / Black / White

EN 50228-7 Table 1

Max length of lay up to 1,5 mm2 ≤ 100 mm

Max length of lay up to 1,5 mm2 ≤ 100 mm

Wrapping of non-hygroscopic tapes and fillers

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Required

Required

≥ 4 times/m

PET Tape

Not Required

Required

Required

Laminated Screening Tape (Aluminum/Polyester)

Laminated Screening Tape (Aluminum/Polyester)

20% min.

20% min.

Stranded tinned copper 0.5 mm2

Stranded tinned copper 0.5 mm2

Not Required

EN 50290-2-22

N/A

N/A

N/A

Not Required

EN 50290-2-22

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red with Light Blue Stripe

Red with Light Blue Stripe

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

300/500 V

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

EN 50228-7; IEC 60228

YES

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

61 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

99

TBD

TBD

B-K1

1x2x2.5 mm2 + Ground Unarmoured Cable for AC Power Supplied Instruments - Fire Resistant

100

TBD

TBD

B-K6 / B-K8 8x2x2.5 mm2 + Ground / 8x2x2.5 mm2 + Ground Armoured Cable for AC Power Supplied Instruments - Fire Resistant

IEC 60228

IEC 60228

Class 2 (stranded) Annealed Copper

Class 2 (stranded) Annealed Copper

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

Brown (PH) / Light Blue (LN) / Yellow/Green (Earth)

2.5 mm2

EN 50290-2-29

2.5 mm2

EN 50290-2-29

MICA Tape + EP Rubber

MICA Tape + EP Rubber

Brown / Light Blue / Yellow/Green

Brown / Light Blue / Yellow/Green

IEC 60502

N/A

Not Required

≥ 20 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

IEC 60502

Max length of lay up to 2.5 mm2 ≤ 150 mm

Wrapping of non-hygroscopic tapes and fillers

≥ 4 times/m

PET Tape

Not Required

Not Required

Not Required

N/A

N/A

N/A

Not Required

Not Required

IEC 60502: EN 50290-2-22

IEC 60502: EN 50290-2-22

N/A

N/A

N/A

N/A

N/A

N/A

LSZH Compound (Low Smoke Zero Halogen)

LSZH Compound (Low Smoke Zero Halogen)

Red

Red

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

0.6 / 1 kV

2 Kv

BY VENDOR

BY VENDOR

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

IEC 60331-11-21

BY VENDOR

BY VENDOR

IEC 60502; IEC 60228

NO

ICEA S-82-552

IEC 60332-1-2

IEC 60332-3-22 Cat. A

IEC 60331-11-21

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

62 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

101

TBD

TBD

E-06

102

TBD

TBD

E-10

01C x 6 mm², Yellow-Green Earthing Cable

01C x 10 mm², Yellow-Green Earthing Cable

IEC 60228-7 Class 2

Straned annealed copper

N/A

IEC 60228-7 Class 2

Straned annealed copper

N/A

6 mm² (07 strands, Strand dia (*) )

10 mm² (07 strands, Strand dia (*) )

As per IEC 60227-3

As per IEC 60227-3

PVC

PVC

Yellow / Green

Yellow / Green

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

450 / 750 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

450 / 750 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

IEC 60228-7 Class 2; IEC 60227-3

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

63 of 65

ISSUE 0

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Conductor

Insulation

Cabling & Assembling

Reference Standard

Type

Colour & Polarity

Size

Ref. Std.

Type

Colour

Thickness (mm)

Cabling Element

Assembling Element

Overall Cabling

Overall Assembling

Moisture Barrier

Pair/Triple/Quads Shield

Shields Ground Wire Communication Wire

Overall Shield

Shield Type

Overlapping

Drain Wire

Ground PE and size

Reference Standard

Inner Sheath Material

Inner Sheath Colour

Sheaths

Armour

Outer Sheath

Outer Sheath Colour

Marking

Bending Radius

Voltage Rating

Voltage Test

Mutual / Grounded Capacitance

Inductance / Conductor Inductance

103

TBD

TBD

E-16

104

TBD

TBD

E-25

01C x 16 mm², Yellow-Green Earthing Cable

01C x 25 mm², Yellow-Green Earthing Cable

IEC 60228-7 Class 2

Straned annealed copper

N/A

IEC 60228-7 Class 2

Straned annealed copper

N/A

16 mm² (07 strands, Strand dia (*) )

25 mm² (07 strands, Strand dia (*) )

As per IEC 60227-3

As per IEC 60227-3

PVC

PVC

Yellow / Green

Yellow / Green

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

BY VENDOR

450 / 750 V

2 Kv

BY VENDOR

BY VENDOR

BY VENDOR

450 / 750 V

2 Kv

BY VENDOR

BY VENDOR

Other Cable Information

Sunlight Resistance

Oil Resistance

Flame Retardant

UL 1581 Section 1200

UL 1581 Section 1200

ICEA S-82-552

IEC 60332-1-2

ICEA S-82-552

IEC 60332-1-2

Fire Retardant (No fire Propagation)

IEC 60332-3-22 Cat. A

IEC 60332-3-22 Cat. A

Fire Resistant

Cable Size (ID) min/Max (mm)

Cable Size OD) min/Max (mm)

Reference STD. Main Applicable Standards

Ex-I Circuit

Cable to be used in Ex-i Circuit

Purchase

MR Number

PO Number

Manufacturer

Supplier

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

IEC 60228-7 Class 2; IEC 60227-3

NO

Not Required

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

64 of 65

ISSUE 0

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Type

Composition

Ref. Norm.

Tube

Secondary Coating

Loose Tube Material

Tubes

Identification

Fire Barrier

Loose

Tight

Wire

Central str. Members

Dielectric GRP Rod

105

TBD

TBD

FO-8

106

TBD

TBD

FO-12

8 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant

12 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant

9/125 µm Single Mode

Single Tube

9/125 µm Single Mode

Single Tube

IEC 60793-2, IEC 60794-1

IEC 60793-2, IEC 60794-1


Yes


Yes

Colours according to ANSI/TIA/EIA 598-A

Colours according to ANSI/TIA/EIA 598-A

MICA/Glass Tape

MICA/Glass Tape

Yes



No

Yes



No

Filling Compound

Yes (inside tube)

Yes (inside tube)

Strength Member

Glass Fiber Reinforced Plastic Rod (FRP)

Glass Fiber Reinforced Plastic Rod (FRP)

Pheripheral str. Member Aramid / Glass

Material

Thickness

Material

Thickness

Material

Thickness

Material

Thickness

Colour

Ref. Norm.

Marking

Inner Sheath

Armour

Intermediate Sheath

Outer Sheath

Core Diameter

Cladding Diameter

Coating Diameter

Attenuation (Typical / Maximum)

Fire Test

Voltage Grade

Reference STD.

Yes

LSZH


Yes

LSZH


Coated Stainless Steel Corrugated Tape

Coated Stainless Steel Corrugated Tape

EN 50288-7

LSZH

Vendor to advice

LSZH


Black

EN 50288-7

LSZH

Vendor to advice

LSZH


Black

EN 50290-2-22

EN 50290-2-22

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

9 µm

125 ± 0.7 µm

245 ± 10 µm

0.32 / 0.4 dB/km

9 µm

125 ± 0.7 µm

245 ± 10 µm

0.32 / 0.4 dB/km

IEC 60331-25 / IEC 60332-3-22

IEC 60331-25 / IEC 60332-3-22



Main Applicable Standards

IEC 60793-2; IEC 60794-1; EN 50288-7

Purchase

MR Number

PO Number

Manufacturer

Supplier

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15

16

17

18

19

20

21

22

23

24

25

26

27

28

29

30

31

32

33

34

35

36

37

38

39

40

41

42

43

44

45

46

47

48

49

50

Item & Technical Specification- DATA SHEET FOR SIGNAL/SPECIAL/FIBER OPTIC INSTRUMENTATION CABLE

Rev

REALISATION EN EPC D’INSTALLATIONS DE PRODUCTION DE LINEAR-ALKYL- BENZENE <> A SKIKDA ALGERIE

TCM IDENTIFICATION CODE 4439-KK-SE-352001001

Sheet

65 of 65

ISSUE 0

Filling Compound

Yes (inside tube)

Yes (inside tube)

Strength Member

Glass Fiber Reinforced Plastic Rod (FRP)

Glass Fiber Reinforced Plastic Rod (FRP)

TCM Commodity Code

MR Ident Code

Client ID Code

Cable Description

TECHNICAL DATA

Type

Composition

Ref. Norm.

Tube

Secondary Coating

Loose Tube Material

Tubes

Identification

Fire Barrier

Loose

Tight

Wire

Central str. Members

Dielectric GRP Rod

Pheripheral str. Member Aramid / Glass

Material

Thickness

Material

Thickness

Material

Thickness

Material

Thickness

Colour

Ref. Norm.

Marking

Inner Sheath

Armour

Intermediate Sheath

Outer Sheath

Core Diameter

Cladding Diameter

Coating Diameter

Attenuation (Typical / Maximum)

Fire Test

Voltage Grade

Reference STD.

107

TBD

TBD

FO-24

108

TBD

TBD

FO-48

24 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant

48 Fibers, Single Mode, Armoured Fiber Optic Cable - Fire Resistant

9/125 µm Single Mode

9/125 µm Single Mode

Multitube (4 tubes, 6 fibers each)

Multitube (4 tubes, 12 fibers each)

IEC 60793-2, IEC 60794-1

IEC 60793-2, IEC 60794-1


Yes


Yes

Colours according to ANSI/TIA/EIA 598-A

Colours according to ANSI/TIA/EIA 598-A

MICA/Glass Tape

MICA/Glass Tape

Yes



No

Yes



No

Yes

LSZH


Yes

LSZH


Coated Stainless Steel Corrugated Tape

Coated Stainless Steel Corrugated Tape

EN 50288-7

LSZH

Vendor to advice

LSZH


Black

EN 50288-7

LSZH

Vendor to advice

LSZH


Black

EN 50290-2-22

EN 50290-2-22

See paragraph 8.3 of this specification

See paragraph 8.3 of this specification

9 µm

125 ± 0.7 µm

245 ± 10 µm

0.32 / 0.4 dB/km

9 µm

125 ± 0.7 µm

245 ± 10 µm

0.32 / 0.4 dB/km

IEC 60331-25 / IEC 60332-3-22

IEC 60331-25 / IEC 60332-3-22



Main Applicable Standards

IEC 60793-2; IEC 60794-1; EN 50288-7

Purchase

MR Number

PO Number

Manufacturer

Supplier

BY VENDOR

BY VENDOR

BY VENDOR

BY VENDOR

This document is property of Tecnimont S.p.A. and cannot be used by others for any purpose, without prior written consent.

Project: Q-32976 - Tecnmont SKIKDA Folder: Reference Documents


Loading authentication...

Graph View

Backlinks

  • 00 Index

Created with Infinity Constructor © 2025

  • Elynox | Go Further