GENERAL NOTES: GENERAL NOTES:
- PLATFORM ACCESS TO BE PROVIDED FOR MANWAYS AND EQUIPMENT WHICH CANNOT BE ACCESSED FROM GRADE.
PERMANENT PLATFORMS ARE REQUIRED WHEN THE PLATFORM STRUCTURAL SUPPORT MEMBER ALLOW A CLEARANCE OF 7’-3” (2200 MM) OR GREATER ABOVE GRADE. TEMPORARY OR PORTABLE PLATFORMS ARE REQUIRED WHEN THE CLEARANCE BETWEEN PLATFORM STRUCTURAL SUPPORT MEMBERS AND GRADE WOULD BE LESS THAN 7’-3” (2200 MM).
- MATING PIPING/VESSEL FLANGES USED FOR INSTRUMENT CONNECTION SHALL BE OFF SAME FLANGE
CLASS AND FINISH AS THE FLANGES SPECIFIED FOR THE INSTRUMENTS.
- FOR PROJECTS WHERE METRIC UNITS ARE SPECIFIED: ALL DIMENSIONS ARE IN MILLIMETERS UNLESS
UNLESS SPECIFICALLY NOTED OTHERWISE.
NOTES:
- DEFINITION FOR PIPE ROUTING GUIDE WORDS
A) NO POCKET
THE PIPE SHALL NOT HAVE ANY LOW POINT, SO AS AVOID ANY LIQUID ACCUMULATION.
B) NO VAPOR POCKET
THE PIPE SHALL NOT HAVE ANY HIGH POINT, SO AS AVOID ANY VAPOR ACCUMULATION.
C) FREE DRAINING
THE PIPE SHALL BE DESIGNED SO AS TO MAKE THE LIQUID DRAIN FREELY TOWARD THE SPECIFIED DIRECTION.
D) SLOPE
THE PIPE SHALL BE CONTINUOUSLY SLOPED IN THE SPECIFIED DIRECTION WITH AT LEAST THE DESIGNATED SLOPING RATE.
E) GRAVITY FLOW
THE PIPE SHALL BE ROUTED SO AS TO ALLOW GRAVITY FLOW OF THE FLUID ALONG THE FULL LENGTH OF THE CIRCUIT.
-
HIGHER RATING COMPANION FLANGE SHALL BE APPLIED FOR THE RATING BREAK POINT.
-
THIS SYMBOL IS USED IN EACH P&ID.
1
-
HIGH POINT VENTS AND LOW POINT DRAINS USED FOR HYDRAULIC TEST PURPOSES ONLY ARE NOT SHOWN ON P&ID.
-
ALL VENTS, DRAINS AND BLEEDER VALVES ARE SCREW-CAPPED OR BLIND-FLANGED AS PER PIPING SPECIFICATION.
-
ON P&IDs, P&ID NUMBERING IS ABBREVIATED INTO XXXX-YYYY
XXXX: UNIT IDENTIFIER YYYY: SEQUENTIAL NUMBER
HOLDS:
EQUIPMENT LIST
LINE NUMBERING SEQUENCE; LINE INLETS AND OUTLETS TO/FROM P&ID’s
FROM 860-9-005 (FROM EQP#) (STREAM DESCRIPTION TO BE INDICATED WHERE NECESSARY
PID NUMBER
CONNECTOR NUMBER
PID NUMBER
4”-P-860-015-XXXX-NI
4”-P-860-016-XXXX-NI
CONNECTOR NUMBER
TO 860-V-007 (TO EQP#) (STREAM DESCRIPTION TO BE INDICATED WHERE NECESSARY, i.e. : BENZENE,LAB ETC)
PID NUMBER
6
1
PID NUMBER
GATE VALVE OR GENERAL VALVE
GLOBE VALVE
BUTTERFLY VALVE
BALL VALVE
CHECK VALVE
Y-TYPE GLOBE VALVE
ROTARY PLUG VALVE
6
1
CONNECTOR NUMBER
CONNECTOR NUMBER
PID NUMBER
PID NUMBER
2”-LPS-860-018-XXXX-HC
2”-LPC-860-019-XXXX-HC
CONNECTOR NUMBER
2”-P-860-017-XXXX-NI
CONNECTOR NUMBER
R E B M U N D P
I
P&ID:0860-0004
6
1
CLOSE DRAIN
XXXX XXX XXXX-YYYY
CONNECTOR NUMBER DESTINATION (SERVICE CODE) 6
1
LINE NUMBERING SEQUENCE ON P&ID’S SHALL BE FROM LEFT TO RIGHT. LINES CONTINUING TO OTHER P&ID’s SHALL TERMINATE ALONG SIDES AS INDICATED ABOVE. LINES CROSSING TO UNIT BATTERY LIMIT SHALL TERMINATE IN A “BL” BOX AT THE BOTTOM (PREFERRED LOCATION) OR TOP. THE BOX SHALL DESIGNATE AT WHICH UNIT LIMIT THE LINE ENTERS OR LEAVES THE UNIT AND ALSO IDENTIFY THE CONNECTING FLOW DIAGRAM CONNECTING FLOW DIAGRAM AND LINE NUMBER. SEE LINE NUMBERING CODE FOR EXPLANATION.
-
- CLOSED DRAIN OR OPEN DRAIN WHICHEVER IS APPLICABLE
LINE NUMBERING FOR LABK COMPLEX
SPADE AND SPACER
SPECTACLE BLIND (NORMAL OPEN)
SPECTACLE BLIND (NORMAL CLOSED)
REDUCER
FLANGE CONNECTION
RS
REMOVABLE SPOOL PIECE
860-V-006
OPEN DRAIN
1
NEEDLE VALVE
XXX
DESTINATION (SERVICE CODE)
PIPING FITTINGS AND LINE EQUIPMENT
VALVES
AUTO RECIRCULATION VALVE (SCHROEDER OR YARWAY TYPE)
ANGLE VALVE
THREE-WAY VALVE
DIAPHRAGM VALVE
PLUG VALVE
EXCESS FLOW VALVE
3
1
CONTROL VALVE
1
1
PENSTOCK
FOUR WAY
FLOW CONTROL
KNIFE WITH HANDWHEEL
KNIFE WITH ACTUATOR
ON/OFF VALVE
STOP CHECK
INTERMITTENT BLOWDOWN (BLOW-OFF)
CONTINUOUS BLOWDOWN
GATE WITH BODY BLEED
HYDRAULIC CONTROL
MANUAL VALVE DESIGNATION
I I
T T N N E E S S N N O O C C N N E E T T T T R R W W R R O O R R P P T T U U O O H H T T W W
I I
I I
, ,
E E S S O O P P R R U U P P Y Y N N A A R R O O F F S S R R E E H H T T O O Y Y B B D D E E S S U U E E B B T T O O N N N N A A C C D D N N A A Y Y T T R R E E P P O O R R P P S S T T N N O O M M N N C C E E T T S S
I I
’ ’
I I
T T N N E E M M U U C C O O D D S S H H T T
I I
LINE SIZE (INCHES)
FLUID SYMBOL
UNIT/SECTION NUMBER (3 DIGITS)
SEQUENTIAL LINE NUMBER (3 DIGITS)
PIPING MATERIAL SPECIFICATION
300#
600#
INSULATION DESIGNATION
4”-P-860-001-XXXXX *2-ET/ST
YY °C *1
*1 - YY INDICATES FLUID TEMPERATURE TO BE MAINTAINED BY TRACING IS SPECIFIED ON LINE/INSTRUMENT *2 - XXXXXX INDICATES PIPING CLASS WILL BE OF MAXIMUM 7 CHARACTERS. LAST TWO OR THREE CHARACTERS ARE USED TO IDENTIFY SPECIAL SERVICES (e.g. NA: NACE, NS: NACE SPECIAL, HY: HYDROGEN, BZ: BENZENE, BNS: BENZENE & NACE SPECIAL).
INSULATION DESIGNATIONS DESCRIPTION
DESIGNATION
1
SLOPE
HS#
T XXXX-YY
CP
SWING ELBOW
BLIND FLANGE
WELDED CAP
SCREWED CAP
COUPLING CONNECTION (FEMALE / MALE)
CLASS CHANGE
RATING BREAK
2
1
1
VENT
1
SLOPE
1
FREE DRAINING
HOSE STATION
1
TIE-IN POINT.
XXXX : UNIT/SECTION NUMBER YY : SEQUENTIAL NUMBER
CORROSION PROBE CONNECTION
“T” TYPE STRAINER
“Y” TYPE STRAINER
CC
ET
FP
HC
HT
JP
JR
JT
NI
PP
SP
ST
W
COLD CONSERVATION
ELECTRIC TRACING
FIRE PROTECTION
HEAT CONSERVATION
HOT OIL TRACING
PARTIAL JACKETING
1
REDUCED JACKETING
TOTAL JACKETING
NON INSULATED
PERSONNEL PROTECTION
PROTECTION FOR SOLAR RADIATION
STEAM TRACING
WINTERIZING
PIPING LINES
PRIMARY PROCESS LINE / FLOW DIRECTION
SECONDARY PROCESS LINE / FLOW DIRECTION
PIPING AND EQUIPMENT SHOWN ON OTHER P AND I DIAGRAMS
TRENCH
TRENCH LINE
ELECTRICALLY TRACED LINE / STEAM TRACED LINE
FUTURE PIPE LINE
1
CL
LINE NUMBER CHANGE
VALVE WITH PLUG
VALVE WITH THREADED CAP
STATIC MIXER
BASE LINE
VENDOR TCM
VENDOR / TCM SCOPE
XXXX XXX
CLOSED DRAIN CONNECTOR NUMBER DESTINATION (SERVICE CODE)
BIRD SCREEN
1
T
STEAM TRAP
FLEXIBLE HOSE
EXPANSION JOINT
SPRAY NOZZLE
BREATHER VALVE
E
W
SHOWER & EYE WASHER
MAN HOLE
VORTEX BREAKER
PULSATION DAMPENER
STEAM DESUPERHEATER
SILENCER
EJECTOR
BASKET TYPE STRAINER
DAMPER
VENT COVER
EXHAUST HEAD
NOTE REFERENCE SYMBOL (XX = NOTE NUMBER, ROTATE ARROW AS REQUIRED)
1
PERMANENT CONE STRAINER
TEMPORARY CONE STRAINER
1
A B CC CN FP FS GM GO H M MN MN5 MO ME MES OT RTSV SS ST T V X XN XX FB TE PE RB ROV CSC CSO LC LO NO NC
MONEL (ALLOY 400) TRIM (GREASE SEALED SEAT AND PACKING) MONEL (ALLOY 400) VALVE (GREASE SEALED SEAT AND PACKING) CABLE CONTROL SOLID ALLOY VALVE FULL PORT FIRE SAFE GEAR OPERATED OR MOTORIZED VALVE GEAR OPERATED VALVE HASTELLOY TRIM MONEL (ALLOY 400) TRIM MONEL (ALLOY 400) TRIM. CARBON STEEL VALVE IN COMPLIANCE WITH NACE MR0103 MONEL (ALLOY 400) TRIM. CARBON STEEL VALVE IN COMPLIANCE WITH NACE MR0175 MOTOR OPERATED VALVE METAL SEAT METAL SEAT STELLITE OVER TRAVEL ROTARY TIGHT SHUT-OFF VALVE STAINLESS STEEL STELLITE TRIM MONEL (ALLOY 400) TRIM (TEFLON INSERT WITH GREASE SEALED PACKING) V-PORT TYPE 316 STAINLESS STEEL TRIM VALVE TYPE 316 STAINLESS STEEL TRIM VALVE IN COMPLIANCE WITH NACE MR0103 18-8 STAINLESS STEEL TRIM VALVE FULL BORE PTFE SEAT PEEK SEAT REDUCED BORE REMOTELY OPERATED VALVE CAR SEAL CLOSED CAR SEAL OPEN LOCKED CLOSED LOCKED OPEN NORMAL OPEN NORMAL CLOSE
1
LETTERS AT STRAINERS DESIGNATE
XN
MN
TYPE 316 STAINLESS STEEL INTERNALS IN COMPLIANCE WITH NACE MR0103
MONEL (ALLOY 400) TRIM. CARBON STEEL INTERNALS IN COMPLIANCE WITH NACE MR0103
JACKETED LINE
BATTERY OR PACKAGE LIMITS
UG
UG
UNDERGROUND LINE
HT
HT
HOT OIL TRACING
LINE CROSSING (CONNECTED)
SPECIAL PIPING ITEM NUMBERING FOR LABK COMPLEX
SPRINKLER
LINE CROSSING (UNCONNECTED)
MIN.
MINIMUM DISTANCE
UNIT NUMBER (3 DIGIT)
SPECIAL PIPING ITEM TYPE
SEQUENTIAL NUMBER (3 DIGIT)
1
XXX-SPYYY-ZZZ
UG
UG
FIRE WATER MAIN (UNDER GROUND)
1
FIRE WATER MAIN (ABOVE GROUND)
DVWS
DVFS
DELUGE VALVE WATER STATION (FOR SPRAY SYSTEM)
DELUGE VALVE FOAM STATION (FOR FOAM SYSTEM)
1
FIRE FIGHTING EQUIPMENT
1
0
IFH–Issued for HAZOP
25/Jun/2024
IFA-Issued for Approval
K.Jeetu
K.Jeetu
A.Lo Verso/G.Acerbi/ E.Magadeev/ H.Aljarrah
A.Lo Verso/G.Acerbi/ E.Magadeev/ H.Aljarrah
A.Lo Verso
A.Lo Verso
ISOLATION BUTTERFLY VALVE (POST INDICATOR TYPE)
1
HYDRANT - TWO HOSE OUTLET AND PUMPER CONNECTION
LANCE MONITOR
1
EARTHING CONNECTION
1
OPEN WATER SPRAY NOZZLE/GAS NOZZLE
WATER HOSE REEL
CO2 GAS EXTINGUISHING SYSTEM
CLEAN AGENT GAS EXTINGUISHING SYSTEM XX SPECIFY GAS
SPRINKLER ALARM VALVE
DELUGE - VALVE
Realisation en EPC d'installations de production de
Realisation en EPC d'installations de production de
LINEAR-ALKYL-BENZENE <
PIPING & INSTRUMENTATION DIAGRAM GENERAL NOTES, SYMBOL AND LEGEND PIPING SYMBOLS 1
4439-VZ-DM-0000-0001
A1 A1
Echelle : Echelle :
1/1 1/1
1 of 1
Rev : Rev :
1
11/Oct/2024
Project: Q-32976 - Tecnmont SKIKDA Folder: Reference Documents