Vendor Offer — Extract (Mock)
Quote Ref: Q-TEST-1 | Date: 2025-08-13
- Model: EXP-MH-14KS/1500(F2)
- Qty: Process (H₂): 2; Process (non‑H₂): 3; Utility: 1; Portable Eyewash: 1
- Power: Immersion heater 230/240 VAC 1Φ; Chiller 415 VAC 3Φ (chiller provides 230 VAC feed to shower)
- Haz Area: Chiller panel Ex d; instruments and JBs Ex e; overall IIB T4 stated (confirm for H₂ units)
- IP: Chiller panel IP66; instruments IP65; motor IP55
- Tests: Not explicitly listing IFAT/CIT/SIT
- AVL: Requests sub‑vendor flexibility
- Painting: Stainless frame supplied unpainted (per project spec)
- Switch: Proximity switch offered in lieu of flow switch (manufacturer standard)