Req_IDRequirementStatus_SuggestionOffer_Evidence_Doc + Page/LineRationale (1‑line)
R002IIC T3 across all electrics/instruments (H₂)Deviation RequiredOffer (Q-TEST-1), Haz Area; Chiller DS (IIB T4); Datasheet Note 7Offered IIB T4; H₂ requires IIC T3 end‑to‑end
R003External instruments ≥ IP65EquivalentOffer (Q-TEST-1), IP; Inst SpecInstrument IP65 ok; motor IP55 is lowest‑link (flag)
R004FAT/SAT/IFAT/CIT/SITDeviation RequiredOffer (Q-TEST-1), TestsOffer silent on IFAT/CIT/SIT; request confirmation
R005AVL enforcedDeviation RequiredOffer (Q-TEST-1), AVLOffer requests flexibility; project requires AVL