Targeted RFIs — Q-21699 (Saipem COMP2)
-
RFI‑IP: Provide enclosure ingress protection evidence per IEC 60529 for junction boxes, any local sign/light box, and any chiller or auxiliary outdoor enclosure to meet project minima.
- Spec citation: Reference Examples/Q-21699 - Saipem COMP2/RFQ Files/Instrumentation/200-51-IN-SPC-00021_00.md, lines 1721–1725 (IP66 outdoors; splash zone IP67).
- Deliverables: Manufacturer certificates or datasheets stating IP ratings; if splash zone, specific statement of IP67 compliance.
- EP placeholder(s): EP‑009 IP Certificates Pack — Parked.
-
RFI‑EMC: Provide EMC/EMI declaration for the tank shower assembly and associated electrical components.
- Quality pack citation: Reference Examples/Q-21699 - Saipem COMP2/Rev 1 Quote Sent/Quality Documents.md, lines 741–742; 751–752 (ATEX equipment register noted, not attached).
- Acceptable standards: IEC 61000‑6‑2/‑6‑4 or IEC 61326; NAMUR NE 21.
- Deliverables: EMC declaration(s) and test reports; ATEX/IECEx certificates/registers for electrical components if applicable.
- EP placeholder(s): EP‑007 EMC Declaration — Parked; EP‑008 ATEX/IECEx Register — Parked.
-
RFI‑FLP/BOM: Confirm flameproof selections and protection concepts per component (Ex d/e/tb) for all hazardous‑area items.
- Datasheet citations: Reference Examples/Q-21699 - Saipem COMP2/Rev 1 Quote Sent/Datasheets and CoCs.md, lines 212–218 (ATEX Zone 1/2 IIA/IIB T3; IIC available; non‑flameproof models available) and lines 468–471 (availability note).
- Spec citation (protection concept): Reference Examples/Q-21699 - Saipem COMP2/RFQ Files/Instrumentation/200-51-IN-SPC-00021_00.md, lines 1771–1780 (Field instruments Ex ‘d’ default; IECEx certification).
- Deliverables: Explicit BOM indicating FLP vs non‑FLP; per‑component protection concept and certificates.