Appendix 2 — Technical Deviation List (Q-32705)
Pos. | Document, Code and Standard Paragraph | Document Requirement | Deviation Description and Technical Justification | Contractor Response | Company Acceptance | Status |
---|
D01 | Tank DS EXP‑MH‑14KS/1500 (lines 105–111) | ATEX Zone 1 & 2; IIA/IIB; T3; IIC available | Configure IIC variants across assembly if IIC is mandated by EPC; provide matching certification. | A — Provide IIC variants if required | Accepted — IIC mandated; configure IIC‑certified components and supply certificate EP‑002. Citations: Tank DS lines 105–111; EPC dwg 200‑91‑EL‑DWG‑00032_B lines 24305–24311. | Closed |
D02 | Offer Q‑32705‑1 (lines 50–52) | Power topology acceptance | Accept separate external feeds: 230/240V 1Φ for heater; 3Φ for chiller | A — Standard packaged topology | Accepted — Separate feeds as offered. Citation: Offer Q‑32705‑1 p.1 lines 50–52. | Closed |