Hazardous-Area Component Matrix — Q-32859
Client_Profile: ADNOC
Component | Claimed Area Class | Gas Group | T‑Class | Evidence (doc+line) |
---|---|---|---|---|
Tank Shower Electrical/Instr. (base) | Zone 1 & 2 | IIA/IIB (IIC available) | T3 | Datasheet EXP‑MH‑14KS/1500, lines 105–111 |
Chiller Unit (package) | Zone‑1 | IIB | T3 | Chiller Datasheet, lines 103–105 |
Chiller Control Panel IP | — | — | — | IP66 (panel) — Chiller Datasheet, line 116 |
Chiller Instruments IP | — | — | — | IP65 (instruments) — Chiller Datasheet, line 116 |
Chiller Pump Motor IP | — | — | — | IP55 (motor) — Chiller Datasheet, line 117 |
Proximity Switch(es) | Zone 1 & 2 | IIA/IIB | — | Offer Q‑32859‑1 p.2, lines 156–169 |
SS316 Junction Box (alarm) | Zone 1 | — | — | Offer Q‑32859‑1 p.2, lines 173–181 |
SS316 Junction Box (heater/light) | Zone 1 | — | — | Offer Q‑32859‑1 p.2, lines 200–211 |
Weakest‑Link Consolidation (per unit)
- Area Class: For non‑H₂ service, Zone‑1 IIB T3 via chiller. For H₂ service, configure IIC T3 end‑to‑end (tank shower IIC variant + chiller certification to be matched in submittals).
- IP Baseline: IP55 due to pump motor; check MR minimums for instruments/motors; deviation only if motor IP65 mandated.
Auto‑Flags
- Weakest_Link_Flag: TRUE (Area Class = IIB via chiller for non‑H₂; IIC configured for H₂; IP weakest = IP55 motor).
- Dual Power: TRUE candidate — Offer indicates 415 VAC 3Φ chiller plus 230/240 VAC shower feed (Offer p.4 lines 364–366; Datasheet lines 109–113).